Plan Review Details - Permit 06071278
Plan Review Stops For Permit 06071278
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2006-08-22 Cont ID  
Sent By lursu Date 2006-08-22 Time 14:43 Rev Time 0.00
Received By lursu Date 2006-08-22 Time 14:43 Sent To  
Notes
2006-08-22 00:00:00PERMIT MUST BE ATTACHED TO EXT #0002 ,
 UNIT 100 ,WHERE THE JOB SITE IS LOCATED.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By lursu Date 2006-08-10 Time 09:09 Rev Time 0.00
Received By lursu Date 2006-08-10 Time 09:09 Sent To  
Notes
2006-08-10 00:00:00PROJECT UNDER REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-08-23 Cont ID  
Sent By mjacobs Date 2007-08-23 Time 08:50 Rev Time 0.00
Received By mjacobs Date 2007-08-23 Time 08:12 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-08-09 Cont ID  
Sent By mjacobs Date 2007-08-09 Time 16:25 Rev Time 0.00
Received By mjacobs Date 2007-08-09 Time 14:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-04-23 Cont ID  
Sent By mjacobs Date 2007-04-23 Time 13:57 Rev Time 0.00
Received By mjacobs Date 2007-04-23 Time 12:39 Sent To  
Notes
2007-04-23 14:43:33BUILDING PLAN REVIEW
 PERMIT: 06071278
 ADD: 2400CENTREPARK WEST #100
 CONT: DAVCO ELECTRICAL CONTRACTORS, INC.
 TEL: (561)732-3434
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 3RD
 ACTION: DENIED
  
 1)61G1-16.004 TITLE BLOCK. INFORMATION REQUIRED ON
 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 2)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 3)FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-24 Cont ID  
Sent By mjacobs Date 2007-01-24 Time 17:32 Rev Time 0.00
Received By mjacobs Date 2007-01-24 Time 17:06 Sent To G
Notes
2007-01-24 17:32:30BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 2) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 16:40 Rev Time 0.00
Received By alange Date 2006-08-10 Time 16:40 Sent To  
Notes
2006-08-10 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-08-14 Cont ID  
Sent By jleahy Date 2007-08-14 Time 17:34 Rev Time 2.30
Received By jleahy Date 2007-08-14 Time 17:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-04-25 Cont ID  
Sent By jleahy Date 2007-04-25 Time 16:39 Rev Time 3.00
Received By jleahy Date 2007-04-25 Time 16:39 Sent To  
Notes
2007-04-25 16:50:08PANEL SCHEDULE "E
  
 SHOWS 2-P 70A BREAKER TO FEED TRANSFORMER
  
 RTU-3 SHOWS NO LOAD ON PANEL SCHEDULE.
  
 LOAD ON PANEL EXCEEDS GENERATOR OUTPUT (90 AMPERES)
  
 TWO OF THE LIGHTING LOADS ARE SHOWN AS 2-POLE 30A
  
 ALL DRAWINGS SHALL HAVE NAME OF PERSON WHO DID THE
 DESIGN
  
 PROVIDE LOADS THAT ARE ON IT PANEL FOR REVIEW.
  
 JAKE LEAHY

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 13:02 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 13:56 Sent To  
Notes
2006-12-17 14:02:35**** UNSAT2ND REVIEW ****
  
  
 1) NOTE: PLEASE SEE ALL COMMENTS WHICH WERE ATTACHED TO
 THE PERMITTED APPLICATION SUBMITTED ON THE FIRST
 REVIEW. PLEASE SEE PERMIT PACKAGE WAS SUBMITTEDBACK
 WITH ANY COMMENTS BEING ADDRESSED OR PLANS.
 PLEASE SEE RESPONSE ON COVER SHEET ONLY MENTIONS
 PLUMBING COMMENTS ADDRESSED. PLEASE KNOW COMMENTS FROM
 ALL TRADES MUST BE ADDRESS AND PLANS SUBMITTED
 ACCORDINGLY.
  
 2) NOTE: PLEASE SEE FLORIDA STATUES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By dpalmer Date 2006-08-09 Time 19:11 Rev Time 0.00
Received By dpalmer Date 2006-08-09 Time 18:30 Sent To  
Notes
2006-08-09 00:00:00***** UNSAT ****
  
 1) NOTE: PLEASE SEE THE 2002 NEC.
 225.31-225.39, 230.72
 PLEASE SEE THAT THIS OFFICE IS UNABLE TO
 VERIFY THIS AT THIS TIME.
  
 2) NOTE: PLEASE INDICATE ANY AND ALL
 CONTINUOOUS LOADS AT 125%.
 215.3,230.42 ETC.
  
 3) NOTE: PLEASE UPDATE PANEL SCHEDULES
 AS THE PANELS DID NOT SEEM TO GET ALL
 THE NEW CIRCUITS. "E". 408.4
 106.1.2 FBC ADMIN SECT
  
 4) NOTE: PLEASE PROVIDE A LAYOUT OF ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE AN
 OVERVIEW AS NO ELECTRICAL EQUIPMENT IS
 SHOWN. CAN NOT VERIFY ITEMS IN NOTE #1
 AT THIS TIME.
  
 5) NOTE: PLEASE SUBMIT SPECS/CUT SHEETS
 FROM THE MANUFACTURE FOR THE ATS.
 110.3, 90.8
 PLEASE ALSO SUBMIT THE SPECS/SHEETS FOR
 THE WP HOUSING AS THE GEN DOES NOT SHOW
 THIS.
  
 6) NOTE: PLEASE CORRLELATE THE OCP FOR
 THE NEW TRANSFORMER AS THE PANEL SHOWS
 ONE AND THE RISER SHOWS ANOTHER.
 450.3,
 FBC 106.1.2
  
 7) NOTE: PLEASE PROVIDE GROUNDING OF THE
 NEW TRANSFORMER.
 250.30,250.20,250.66 ETC
  
 8) NOTE: PLEASE SEE PLANS/DRAWINGS ARE
 NOT REQUIRED TO BE NOTARIZED, HOWEVER IF
 THEY ARE THEN THEY NEED TO BE CORRECTLY
 NOTARIZED AS REQUIRED PERFS 117.05
 PLEASE KNOW ONLY A STAMP AND SIGNATURE
 IS NOT ACCEPTABLE.
  
 9) NOTE: PLEASE SEE EXISTING MDP, IS
 BEING SHOWN AS MLO. PLEASE CLARIFY AS
 THIS CONTAINS MANY MORE THAN 6 MEANS OF
 DISCONNECT. 230.70
 PLEASE KNOW, ALL DISCONNECTING MEANS FOR
 SEC'S AND FEEDERS COMING INTO THE
 BUILDING SHALL BE GROUPED.
  
 10) NOTE: PLEASE PROVIDE PROPER LEGAL
 DOCUMENTATION THAT THIS GENERATOR ECT IS
 BEING PERMITTED ON THIS PROPERTY BY THE
 PROPERTY OWNER.
 PLEASE SEE THIS GEN SEEMS TO BE ONLY FOR
 ONE TENANT SPACEIN THE BUIDLING.
  
 11) NOTE: PLEASE SEE ALL PLANS, DESIGNS
 AND LOAD CALULATIONS SHALL CONTAIN A
 STATEMENT" DRAWN BY: PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPSOSIBLE FOR
 SAID PLANS AND DESIGNS.
 FBC 106.1.2
  
  
 ** UNABLE TO DO A COMPLETE REVIEW AT
 THIS TIME AS THERE ARE SOME MISSING
 ITEMS NEEDED.
 PLEASE BE SURE TO GO OVER PLANS AND
 RISER BEFORE RESUBMITTING.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-08-20 Cont ID  
Sent By mawillia Date 2007-08-20 Time 16:36 Rev Time 0.00
Received By mawillia Date 2007-08-20 Time 16:29 Sent To Z
Notes
2007-08-20 16:35:53*****APPROVED*****
  
  
 THE PREVIOUS FIRE PLAN REVIEW COMMENTS HAVE BEEN
 ADDRESSED;PLAN SHEET SP-1 STAMPED, INITIALED, AND
 DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-05-07 Cont ID  
Sent By mawillia Date 2007-05-07 Time 16:02 Rev Time 0.00
Received By mawillia Date 2007-05-07 Time 15:53 Sent To  
Notes
2007-05-07 16:02:02*****DENIED*****
  
  
  
 PLEASE BE ADVISED THAT THE PLAN REVIEW COMMENTS OF
 09/05/2006 HAVE NOT BEEN ADDRESSED.(SEE RE-PRINT)
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2007-01-08 Cont ID  
Sent By mawillia Date 2007-01-08 Time 13:25 Rev Time 0.00
Received By mawillia Date 2007-01-08 Time 13:25 Sent To  
Notes
2007-01-08 13:30:55*****DENIED*****
  
  
  
 PLEASE BE ADVISED THAT THE PLAN REVIEW COMMENTS OF
 09/05/2006 HAVE NOT BEEN ADDRESSED.(SEE RE-PRINT)
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2006-09-05 Time 10:33 Sent To  
Notes
2006-09-05 00:00:00***DENIED***
  
 1) PLEASE ILLUSTRATE BUILDING OPENINGS
 AS IT RELATES TO THE LOCATION OF THE
 GENERATOR.
  
 2) WORK TO COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 3) PLEASE PROVIDE VERIFICATION AS TO
 FUEL SOURCE, NATURAL GAS OR PROPANE.
 SPEC SHEETS INDICATE SEVERAL OPTIONS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-08-17 Cont ID  
Sent By kstevens Date 2007-08-17 Time 13:56 Rev Time 0.00
Received By kstevens Date 2007-08-17 Time 13:56 Sent To  
Notes
2007-08-17 13:56:51GAS PERMIT TO BE ISSUED WHEN ZONING APPROVAL AND
 GEN-COM IS ISSUED

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-06-04 Cont ID  
Sent By kstevens Date 2007-06-04 Time 15:13 Rev Time 0.00
Received By kstevens Date 2007-06-04 Time 15:12 Sent To  
Notes
2007-06-04 16:02:55GAS PLANS CORRECT, BUT WILL NOT BE PASSED IN THE
 COMPUTER UNTILL ZONING APPROVAL

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2007-03-06 Cont ID  
Sent By mperson Date 2007-03-06 Time 08:48 Rev Time 0.00
Received By mperson Date 2007-03-06 Time 08:48 Sent To PC
Notes
2007-03-06 10:14:25DENIED
 REFERENCE: FBC-2004 FUEL GAS:
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 THE FOLLOWING ARE FROM THE PREVIOUS REVIEW DATED
 8/21/06
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. NO,SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2
 NOTE: PLEASE PROVIDE MANUFACTURER SHEETS FOR THE
 FOLLOWING.
 A} MP REGULATOR
 B} GENERATOR
 9. OK, N/A
 10. OK, N/A
  
 THE FOLLOWING ARE NEW COMMENTS:
  
 11. PLEASE PROVIDE 2 COPIES OF SITE PLAN OR SURVEY AT
 THE TIME OF PERMIT APPLICATION THAT INCLUDE THE
 FOLOWING INFORMATION.
 A} THE CLEARLY MARKED PROPOSED LOCATION FOR THE
 INSTALLATION OF THE GENERATOR.
 B} INDICATION OF ALL DIMENTIONS FROM PROPERTY LINES
 AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
 C} INDICATION THAT THE GENERATOR EXHAUST IS NOT
 INSTALLED CLOSER THAN TEN FEET FROM ANY OPENING INTO
 THE DWELLING STRUCTURE. THIS INCLCES DOORS, WINDOWS AND
 ATTIC VENTILATION OPENINGS.
  
 12. PLEASE SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS/CUT SHEETS FOR GENERATOR, SHOWING
 LISTINGS FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY (NRTL). PLEASE INCLUDE INSTALLATIN
 INSTRUCTIONS INDICATING CLEARENCES TO DWELLINGS.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By kstevens Date 2006-08-21 Time 10:43 Rev Time 0.00
Received By kstevens Date 2006-08-21 Time 10:43 Sent To  
Notes
2006-08-21 00:00:00SEPARATE GAS PERMIT REQUIRED
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL) MANUF.
 SHEETS INDICATE EITHER NATURAL, LP, OR
 BOTH, (DUAL FUEL). PLEASE BE SPECIFIC.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (INDICATE IF CONNECTING TO
 EXISTING. - IF EXISTING SYSTEM PLEASE
 INDICATE BTU'S FOR ALL EXISTING (TOTAL)
 AND DISTANCE FROM METER TO MOST REMOTE
 APPLIANCE IN EXISTING).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (INCLUDING
 EXISTING IF APPLICABLE).
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. MANUF.
 SHEETS SUBMITTED DO NOT CONTAIN THE
 INSTALLATION INSTRUCTIONS WITH MINIMUM
 CLEARANCE REQUIREMENTS FROM STRUCTURES
 FOR SERVICE ETC.
  
 9. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 10. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-07-20 Cont ID  
Sent By adarroug Date 2007-07-20 Time 09:30 Rev Time 0.00
Received By adarroug Date 2007-07-20 Time 09:30 Sent To  
Notes
2007-08-01 13:21:47TO "COMM" BD#8
2007-07-20 09:31:04WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-04-20 Cont ID  
Sent By adarroug Date 2007-04-20 Time 16:37 Rev Time 0.00
Received By adarroug Date 2007-04-20 Time 16:37 Sent To  
Notes
2007-04-20 16:38:04TO "COMM' BD#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-01 Cont ID  
Sent By adarroug Date 2006-12-01 Time 10:47 Rev Time 0.00
Received By adarroug Date 2006-12-01 Time 10:47 Sent To  
Notes
2006-12-13 15:03:24TO "COMM" BD#25
2006-12-01 10:47:30WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 10:39 Rev Time 0.00
Received By mwennerg Date 2006-07-22 Time 17:04 Sent To  
Notes
2006-08-08 00:00:00TO "COMM" BD#26
2006-07-22 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 09:50 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 09:08 Sent To  
Notes
2006-08-21 00:00:00NATURAL GAS GENERATOR:
 SITE PLANS DO NOT INDICATE DISTANCES OR
 CLEARANCES FROM PROPERTY LINES,
 BUILDING, FRESH AIR INTAKES, WINDOWS,
 DOORS, ETC.
  
 PLEASE PROVIDE ANCHORING DETAIL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop Z ZONING
Rev No 5 Status P Date 2007-08-22 Cont ID  
Sent By jroach Date 2007-08-22 Time 09:31 Rev Time 0.00
Received By jroach Date 2007-08-22 Time 09:31 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-08-13 Cont ID  
Sent By jroach Date 2007-08-13 Time 21:31 Rev Time 0.00
Received By jroach Date 2007-08-13 Time 21:31 Sent To  
Notes
2007-08-13 21:35:20***FAILED***
  
 1) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MINOR
 AMENDMENT TO THE CENTREPARK WEST COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT.APPLICATION HAS
 BEEN SUBMITTED FOR THE MINOR AMENDMENT.HOWEVER,
 OUTSTANDING COMMENTS REGARDING THIS APPLICATION HAVE
 NOT YET BEEN ADDRESSED TO RECEIVE APPROVAL.
  
 2) ADEQUATE SCREENING SHALL BE PROVIDED, CONSISTING OF
 A SOLID WALL OF ADEQUATE HEIGHT LANDSCAPED WITH
 SHRUBS/HEDGES AT TWO (2) FOOT INTERVALS.LANDSCAPE
 PLANS WERE SUBMITTED AS PART OF THE MINOR AMENDMENT.
 HOWEVER, NO PLANS WERE SUBMITTED AS PART OF THE
 BUILDING PERMIT.ENSURE THAT THE COMMENTS FROM THE
 MINOR AMENDMENT REVIEW HAVE BEEN SUFFICIENTLY ADDRESSED
 (I.E. RELOCATION OF AN EXISTING SHADE TREE).
  
 ONCE THE MINOR AMENDMENT IS APPROVED, AND ALL PLANS
 SUBMITTED AS PART OF THE BUILDING PERMIT MATCH THOSE,
 THE PERMIT WILL BE APPROVED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-04-30 Cont ID  
Sent By jroach Date 2007-04-30 Time 10:29 Rev Time 0.00
Received By jroach Date 2007-04-30 Time 10:29 Sent To  
Notes
2007-04-30 10:30:54***FAILED***
  
 1) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MINOR
 AMENDMENT TO THE CENTREPARK WEST COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT.
  
 2) ADEQUATE SCREENING SHALL BE PROVIDED, CONSISTING OF
 A SOLID WALL OF ADEQUATE HEIGHT LANDSCAPED WITH
 SHRUBS/HEDGES AT TWO (2) FOOT INTERVALS.
  
 3) NO SURVEYS WERE PROVIDED WITH THE RESUBMITTAL.TWO
 (2) COPIES OF A CURRENT SURVEY SHALL BE PROVIDED
 SHOWING THE LOCATION OF THE GENERATOR WITH THE SETBACKS
 FROM THE PROPERTY LINES.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-07 Cont ID  
Sent By jroach Date 2007-01-07 Time 22:10 Rev Time 0.00
Received By jroach Date 2007-01-07 Time 22:10 Sent To  
Notes
2007-01-07 22:11:37***FAILED***
  
 1) PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, A MINOR
 AMENDMENT TO THE CENTREPARK WEST COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO AND APPROVED BY
 THE PLANNING AND ZONING DEPARTMENT.
  
 2) ADEQUATE SCREENING SHALL BE PROVIDED, CONSISTING OF
 A SOLID WALL OF ADEQUATE HEIGHT LANDSCAPED WITH
 SHRUBS/HEDGES AT TWO (2) FOOT INTERVALS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-17 Cont ID  
Sent By jroach Date 2006-08-17 Time 08:42 Rev Time 0.00
Received By jroach Date 2006-08-17 Time 08:42 Sent To  
Notes
2006-08-17 00:00:008/17/06 ***FAILED***
  
 1) PRIOR TO THE ISSUANCE OF A BUILDING
 PERMIT, A MINOR AMENDMENT TO THE
 CENTREPARK WEST COMMERCIAL PLANNED
 DEVELOPMENT (CPD) SHALL BE SUBMITTED TO
 AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT.
  
 2) ADEQUATE SCREENING SHALL BE PROVIDED,
 CONSISTING OF A SOLID WALL OF ADEQUATE
 HEIGHT LANDSCAPED WITH SHRUBS/HEDGES AT
 TWO (2) FOOT INTERVALS.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH,
 SENIOR PLANNER, AT (561) 822-1435.
  