Plan Review Details - Permit 06071230
Plan Review Stops For Permit 06071230
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-13 Cont ID  
Sent By mjacobs Date 2007-02-13 Time 12:07 Rev Time 0.00
Received By mjacobs Date 2007-02-13 Time 10:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-22 Cont ID  
Sent By mjacobs Date 2007-01-22 Time 18:36 Rev Time 0.00
Received By mjacobs Date 2007-01-22 Time 17:03 Sent To PC
Notes
2007-01-22 18:24:10BUILDING PLAN REVIEW
 PERMIT: 06071230
 ADD: 205 N.DIXIE HWY
 CONT: H.A. CONTRACTING CORP.
 TEL: (305)591-9212
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 2ND
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)WPB AMENDMENTS 108.3*THE VALUE IS TO LOW. IF IN
 THE OPINION OF THE BUILDING OFFICIAL, THE CLAIMED
 VALUATION OF THE BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHINICAL OR PLUMBING SYSTEMS APPEARS
 TO BE UNDERESTIMATED ON THE APPLICATION, THE PERMIT
 SHALL BE DENIED. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUED STRUCTURAL ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COST, OVERHEAD AND PROFIT: EXCLUDING LAND.
 OUR VALUATION REFERENCE IS ICC (BVD) MARSHALL-SWIFT AND
 MEANS COST ANALYSIS SERVICES.
  
 3)THE IT EQUIP ROOM SHALL BE DESIGN TO NFPA. 75 CH.
 5.1. ALL WALL SHALL BE AT LEAST ONE HOUR RATED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
2007-01-05 18:30:59NEW RATED ROOM,, NOT ONLY DEMO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-11 Cont ID  
Sent By amorse Date 2006-08-11 Time 13:56 Rev Time 0.00
Received By amorse Date 2006-08-11 Time 13:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-05-03 Cont ID  
Sent By dpalmer Date 2007-05-03 Time 16:10 Rev Time 0.00
Received By dpalmer Date 2007-04-13 Time 14:54 Sent To  
Notes
2007-05-03 16:12:37****5/3/07***
  
  
 NEW SHEETS BROUGHT IN BY ENGINEER.
 NEW APC SHEETS ATTACHED TO PLANS AS E-MAILED. ALL
 EQUIPMENT ON LOAD SIDE OF POWERE PANEL IS UNDER UL FILE
 # AND SHALL BE INSTALLED PER LISTING.
 OWES FEES FOR 4X FEE FOR ORIGINAL SCOPE OF WORK WHIHC
 COMMENCED WITHOUT PERMITS.
2007-04-13 15:29:35** UNSAT **
  
 *** PROJECT IS CURRENTLY ON HOLD.THE OTHER TRADES MAY
 REVIEW.
  
  
 1) NOTE: *INFORMATION AS REQUESTED IN MEETING FOR
 LISTED ASSEMBLY OF EQUIPMENT COULD NOT BE LCOATED IN
 PACKAGE. THE DOCUMENTATION DOES NOT INDICATE LISTING OR
 SHOW DETAILS FOR CODE COMPLIANCE , INFACT, NOTES ON
 SHEETS MENTIONS THAT INSTALLATION FOR WIRING WHICH IS
 NOT PART FO THE EQUIPMENT SHALL MEET NATIONAL
 ELECTRICAL CODE.
  
  
 2) NOTE: * ALSO AN ON-SITE MEETING IS NOW SCHEDULED FOR
 TUESDAY 10:30AM THE 17TH OF APRIL TO GO OVER WORK WHICH
 WAS COMMENCED AND DONE W/OUT PERMIT FOR A CORRECT
 VALUATION OF WORK. CONTRACTOR COULD NOT PROVIDE THE
 VALUE FOR WORK DONE.
  
 3) NOTE:* CALLED ENGINEER AND LEFT MESSAGE FORFOR
 NOTE NUMBER ONE ABOVE AND TO MEET ON-SITE.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-13 Cont ID  
Sent By dpalmer Date 2007-02-13 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2007-02-13 Time 08:05 Sent To  
Notes
2007-02-13 08:53:07*** UNSAT ***
  
  
 1) NOTE: PLANS ARE CURRENTLY TO FAILED STATUS AS SCOPE
 OF WORK AT SITE IS TO BE VERIFIED. THE PLANS CALLS FOR
 SOME AS EXISTING EQUIPMENT FOR UPS ETC , HOWEVER THIS
 SCOPE OF WORK WAS NOT PERMITTED AND IF THIS IS NEW
 EQUIPMENT THEN THE MANUFACTURES SPECS/CUT SHEETS ARE
 NEEDED.
 MUST SHOW AL LISTINGS FROM NRTL. 110.3, 90.7
 PLEASE KNOW A FIELD INSPECTION WILL BE REQUIRED PRIOR
 TO REVIEW STATUS CHANGE. THE EXISTING ROOMS WHICH WERE
 BEING MADE PART OF THE EXISTING COMPUTER ROOM DID NOT
 CONTAIN ELECTRICAL UPS SYSTEMS ON PREVIOUS PLANS, NOW
 PLANS CALLS FOR THESE AS EXISTING.
 PLEASE SEE ELECTRICAL SHEET WHICH ALSO MENTIONS THIS
 EQUIPMENT AS BEING RELOCATED.
  
  
 ** CALLED CONTRACTOR AND LEFT MESSAGE**
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By dpalmer Date 2007-01-05 Time 18:33 Rev Time 0.00
Received By dpalmer Date 2007-01-05 Time 09:40 Sent To  
Notes
2007-01-05 18:33:40** UNSAT **
  
  
 1) NOTE: PLEASE SEE PLANS SHALL BEAR THE CORRECT
 ADDRESS ON TITLE BLOCKS.
 PLEASE SEE THE PERMIT APPLICATION AND THE ADDRESS IN
 OUR SYSTEM APPLIED TO IS 205 N. DIXIE.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE PLANS SHALL REFERENCE ALL CODES
 WHICH ARE CURRENTLY RELEVANT TO THE DESIGN OF SAID
 PLANS AND WHICH SHALL ALSO BE STATED ON PLANS. PLEASE
 BE SURE TO SEE ALL OF THESE NEW SECTIONS WHICH ARE
 RELEVANT TO THE DESIGNS FOR THE SCOPE OF WORK BEING
 SHOWN AND PROPOSED.
 PLEASE ALSO SEE THAT THE FOLLOWING SHALL BE STATED ON
 THE PLANS AT A MINIMUM.
 2004 FBC W/2006 REVISIONS.
 2002 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
 2003 NFPA-75
  
 ** SIDE NOTE, AS OF 12/8/06 THE STATE OF FLORIDA HAS
 ADOPTED THE 2005 NFPA-70 (NEC) AND THE 2006 REVISIONS
 TO THE 2004 FBC. THIS IS GIVEN FOR INFORMATION ONLY.
 ALL PERMIT APPLICATIONS ON 12/8/06 OR LATER SHALL BE
 UNDER THE NEW CODES.
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK SHALL INCLUDE ALL LABOR AND MATERIALS. PLEASE ALSO
 SEE BUILDING REVIEW COMMENTS AS BASED ON THE SCOPE OF
 WORK SHOWN THE APPLIED VALUE IS LOW. PLEASE SEE THE
 VALUE HAS NOT CHANGED, HOWEVER THE SCOPE OF WORK HAS
 SUBSTANTIALLY INCREASED EVEN WITHOUT THE EQUIPMENT
 BEING INSTALLED.
 FBC 108.3
  
 4) NOTE: PLEASE SHOW AND INDICATE THE ACTUAL ATTACHMENT
 FOR THE GROUNDING OF THE TRANSFORMER PER 250.30,
 250.20. QUOTING GROUNDING "PER NEC 250" IS NOT
 PERMITTED. PLEASE SUBMIT DETAIL IN LIEU OF QUOTING THE
 CODE(S).
 FBC 106.1.2 ADMIN SECTION.
  
 5) NOTE: PLEASE SEE PANEL ON PLANS MENTIONS "EXISTING
 IT PANEL" YET THIS IS NOT POSSIBLE AS THIS PANEL WAS
 NOT LOCATED IN THE OLD COMPUTER ROOM. PLEASE CLARIFY
 THIS ON PLANS.
 FBC 106.1.2.
  
 6) NOTE: PLEASE SEE 450.3 FOR THE MAXIMUM OVER CURRENT
 PROTECTION PERMITTED ON THE TRANSFORMER AS SHOWN. (125%
 MAX).
  
  
 7) NOTE: PLEASE PROVIDE CALCULATIONS ON NEUTRAL
 CONDUCTORS FOR ALL NON-LINEAR CIRCUITS. PLEASE SEE ALL
 CIRCUITS WHICH CONTAIN THESE LOADS SHALL MEET THE
 SIZING REQUIREMENTS TO HANDLE AND ALLEVIATE THE OVER
 LOADING OF THE NEUTRAL ON A 3-PHASE 4-WIRE SYSTEM WITH
 PREDOMINATELY OR ACTUALLY IN MANY CASES ALL NON-LINEAR
 LOADS. PLEASE SEE THIS CAN BE DONE BY USING MANY
 METHODS, K-RATED TRANSFORMERS, FULL NEUTRAL LOAD
 CALCULATION ON EACH CIRCUIT AND FEEDERS BASED ON ALL
 NON-LINEAR LOADS OR THE SIZING OF THE NEUTRAL(S) AT
 200%.
 PLEASE SEE THE RISK OF FIRE, LIFE SAFETY AND CAUSE TO
 PROPERTY DAMAGE CAN BE SUBSTANTIAL AND IT IS THE
 CONCERN OF THE OFFICE BASED ON OUR INFORMATION KNOWN
 AND PLEASE SEE STUDIES IN WHITE PAPERS FROM NUMEROUS
 MANUFACTURES OF ELECTRONIC/COMPUTER EQUIPMENT WHICH
 INDICATE AS MUCH AS 1.7 TIMES THE RATED LOAD OF THE
 CONDUCTOR OR CIRCUIT AND FEEDERS.
 PLEASE SEE THE FOLLOWING CODES: THIS OFFICE IS AWARE OF
 WHAT A FPN MEANS, HOWEVER SEE SOME SECTIONS GIVEN WHICH
 DO NOT CONTAIN FPN.PLEASE SEE 210.4A (FPN), 220.22
 (FPN(2), 310.10, 310.15B4(C), 400.5, 520.44, 408.16,
 AND FBC 104.6ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
 PLEASE PROVIDE MORE INFORMATION ON WHAT STEPS WILL BE
 TAKEN TO ALLEVIATE THESES RISKS.
  
 8) NOTE: PLEASE SEE PANEL "HA", THE AIC RATING AS SHOWN
 IS BEING SHOWN AT 35K WHICH IS OK; HOWEVER IS THIS FOR
 ALL BRANCH BREAKERS?
 110.9,
 FBC 106.1.2 ADMIN SECTION
  
 9) NOTE: PLEASE SHOW/ INDICATE ANY AND ALL SMOKE
 DETECTION DEVICES ON PLANS (SHOWN) AND NOTE FOR BEING
 CONNECTED. SEPARATE PERMIT PLANS.
 PLEASE SEE FBC 11-4.28.2, .3(4) FOR ANY HORN AND STROBE
 DEVICES. PLEASE BE SURE THESE STATE THE MINIMUM
 LEVELS.
 75CD FOR STROBES.
  
 10) NOTE: PLESE ADJUST THE PERMIT APPLICATION FOR SCOPE
 OF WORK.
  
 ** PLEASE KNOW, PLANS PERMIT APPLICATION, MANUFACTURE
 SPECS/CUT SHEETS WILL BE REQUIRED FOR THE FUTURE
 EQUIPMENT FOR THE ROOM.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 12:32 Sent To  
Notes
2006-08-05 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE MORE DETAIL ON
 ELECTRICAL PLANS. PLEASE SEE PLANS SHOWS
 ON PANEL BEING MOVED, YET SHOWS THREE
 PANELS?
 PLEASE PROVIDE CIRCUITING AND CORRELATE
 WITH MINIMUM PANEL SCHEDULE(S) TO BE
 SUBMITTED.
 PLEASE SEE NEC 645 AND NFPA-75 FOR
 REQUIREMENTS OF IT ROOM.
 PLEASE SEE MISSING DISCONNECTING MEANS,
 GROUNDING SHUT OFF'S, FOR A/C EQUIPMENT
 AND ALL ELECTRICAL.
 IF A/C SYSTEM ARE DUCTED IN, PLEASE BE
 SURE TO PROVIDE FIRE DAMPERS AS
 REQUIRED.(MAY BE PART OF MECH REVIEW)
 PLEASE SEE BLDG REVIEW COMMENTS FOR MIN
 RATINGS OF ALL WALLS TO BE CLARIFIED.
  
 ** PLANS ARE NOT CLEAR AT THIS TIME FOR
 ALL MIN REQUIRMENTS PER ABOVE.
  
 408.4,240.4,240.24,408.7,110.26 ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-02-20 Cont ID  
Sent By mawillia Date 2007-02-20 Time 10:52 Rev Time 0.00
Received By mawillia Date 2007-02-20 Time 10:52 Sent To  
Notes
2007-02-20 10:54:30*****APPROVED*****
  
  
  
 NEW FIRE ALARM PLAN SHEET E-203 WAS STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-01-16 Cont ID  
Sent By mwennerg Date 2007-01-16 Time 11:28 Rev Time 0.00
Received By mwennerg Date 2007-01-16 Time 11:28 Sent To  
Notes
2007-01-16 11:41:31***PROVISO***
  
 1) PLANS APPROVED AND STAMPED ON 8/16/06.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS MAY BE REQUIRED
 FOR FIRE PROTECTION SYSYTEMS IF APPLICABLE AND
 DEPENDENT ON SCOPE OF WORK REGARDING THOSE SYSTEMS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-16 Cont ID  
Sent By mwennerg Date 2006-08-16 Time 14:45 Rev Time 0.00
Received By mwennerg Date 2006-08-16 Time 14:45 Sent To  
Notes
2006-08-16 00:00:00***APPROVED***
  
 1) CONSTRUCTION, ALTERATION AND
 DEMOLITION TO COMPLY WITH NFPA 241.
  
 2) PLANS SHOW NO WORK TO BE DONE ON FIRE
 SPRINKLER OR FIRE ALARM SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-12 Cont ID  
Sent By adarroug Date 2007-04-12 Time 11:53 Rev Time 0.00
Received By adarroug Date 2007-04-12 Time 11:53 Sent To  
Notes
2007-04-12 11:54:08TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-12 Cont ID  
Sent By adarroug Date 2007-02-12 Time 09:01 Rev Time 0.00
Received By adarroug Date 2007-02-12 Time 09:01 Sent To  
Notes
2007-02-12 09:02:09TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-17 Cont ID  
Sent By adarroug Date 2006-12-17 Time 13:50 Rev Time 0.00
Received By adarroug Date 2006-12-17 Time 13:50 Sent To  
Notes
2007-01-03 17:28:58TO "BOB"#7
2006-12-17 13:52:54WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-16 Cont ID  
Sent By mwennerg Date 2006-08-16 Time 14:49 Rev Time 0.00
Received By mwennerg Date 2006-07-22 Time 14:10 Sent To  
Notes
2006-08-02 00:00:00TO "BOB"#2
2006-07-22 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-04-17 Cont ID  
Sent By tgordon Date 2007-04-17 Time 11:13 Rev Time 1.00
Received By tgordon Date 2007-04-17 Time 11:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-02-13 Cont ID  
Sent By tgordon Date 2007-02-13 Time 15:46 Rev Time 0.30
Received By tgordon Date 2007-02-13 Time 15:46 Sent To  
Notes
2007-02-13 16:06:26*** DENIED ***
 1) PLEASE SUBMIT PRODUCT APPROVAL FOR PRE-ENGINEERED
 A/C CONDENSER STAND, PER FAC 9B-72.010 (31)(G).
 PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
 SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2007-01-08 Cont ID  
Sent By tgordon Date 2007-01-08 Time 12:01 Rev Time 0.30
Received By tgordon Date 2007-01-08 Time 12:01 Sent To  
Notes
2007-01-08 12:10:29*** DENIED ***
 1) PLEASE PROVIDE A DETAIL ON THE PLANS SHOWING HOW THE
 CONDENSER UNIT STAND IS TO BE MOUNTED TO THE ROOF TO
 WITH STAND140 MPH WIND LOADS, PER 2004 FBC 1609.
 AND HOW THE CONDENSER UNIT IS TO BE SECURED TO THE
 STAND.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 15:29 Rev Time 0.15
Received By tgordon Date 2006-08-04 Time 15:29 Sent To  
Notes
2006-08-04 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***