Plan Review Details - Permit 06071002
Plan Review Stops For Permit 06071002
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-08-16 Cont ID  
Sent By mperson Date 2006-08-16 Time 16:19 Rev Time 0.33
Received By mperson Date 2006-08-16 Time 16:19 Sent To PC
Notes
2006-08-16 00:00:00REFERENCE: GEN/RES PERMIT #06060589

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By mperson Date 2006-07-24 Time 14:21 Rev Time 0.45
Received By mperson Date 2006-07-24 Time 14:21 Sent To PC
Notes
2006-07-24 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2994 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (PLEASE REFERENCE THE
 ATTACHED SAMPLE ISOMETRIC GAS RISER
 DIAGRAM AND INDICATE THE LENGTHS OF THE
 ABOVE GROUND PIPE ON THE ISOMETRIC FOR
 RESUBMITTAL.)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES. (PLEASE
 INDICATE THIS ON THE ISOMETRIC.)
 3. TYPE OF GAS, (LP OR NATURAL) (PLEASE
 INDICATE GAS TYPE ON ISOMETRIC.)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (NOTE: ADDRESS INDICATES
 EXISTING GAS, PLEASE SEE ATTACHED PERMIT
 INFORMATION FOR REFERENCE, THE BTU LOAD
 OF THE EXISTING SYSTEM PLUS THE BTU LOAD
 OF THE GENERATOR NEED TO BE INDICATED ON
 THE ISOMETRIC OR INDICATE METER FOR
 GENERATOR ONLY ON ISOMETRIC.)
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(PLEASE
 INDICATE THIS ON THE ISOMETRIC)
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (PLEASE INDICATE THIS ON THE ISOMETRIC.)
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE:
 NEED MANUFACTURE SHEETS OF THE 2LB TO
 11" WC MP REGULATOR)
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE ATTACHED ISOMETRIC GAS
 RISER DIAGRAM FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 18:36 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 18:36 Sent To G
Notes
2006-08-11 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-24 Cont ID  
Sent By mperson Date 2006-07-24 Time 14:52 Rev Time 0.00
Received By mperson Date 2006-07-20 Time 15:18 Sent To  
Notes
2006-07-20 00:00:00TO "G" BOX