Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-08-08 Cont ID  
Sent By lursu Date 2006-08-08 Time 15:24 Rev Time 0.00
Received By lursu Date 2006-08-08 Time 15:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-07-14 Cont ID  
Sent By mjacobs Date 2007-07-14 Time 09:26 Rev Time 0.00
Received By mjacobs Date 2007-07-14 Time 09:04 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-05-29 Cont ID  
Sent By mjacobs Date 2007-05-29 Time 13:03 Rev Time 0.00
Received By mjacobs Date 2007-05-29 Time 12:51 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-09 Cont ID  
Sent By mjacobs Date 2006-08-09 Time 15:56 Rev Time 0.00
Received By mjacobs Date 2006-08-09 Time 15:56 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-08-01 Cont ID  
Sent By mjacobs Date 2006-08-01 Time 07:26 Rev Time 0.00
Received By mjacobs Date 2006-08-01 Time 06:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-08-02 Cont ID  
Sent By dpalmer Date 2007-08-02 Time 17:42 Rev Time 0.00
Received By dpalmer Date 2007-08-02 Time 17:24 Sent To PC
Notes
2007-08-02 17:43:25REVISED PLANS FOR FINAL.
 REVISED ENGINEER OF RECORD.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-07-16 Cont ID  
Sent By dpalmer Date 2007-07-16 Time 17:38 Rev Time 0.00
Received By dpalmer Date 2007-07-16 Time 17:30 Sent To PC
Notes
2007-07-16 17:38:51**** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES TWO
 SMALL APPLIANCE CIRCUITS ALONG WITH DINING ROOM AND
 EACH AT 1500VA YET THE LOAD CALCULATIONS DO NOT
 CORRELATE WITH THIS.
 PLEASE SEE 210.52B1, 210.11C1, AND 220.16
  
 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR
 CORRECTIONS; PLEASE CORRECT THE DESIGNATION OF THE
 SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE
 ALARMS AND NOT SMOKE DETECTORS PER NFPA-72
 DEFINITIONS.
 PLEASE SEE BOTH SMOKE DEVICES ARE SHOWN INSIDE THE
 BEDROOM/SLEEPING ROOM. PLEASE SEE NFPA-72 11.5.1.1.1
 WHICH REQUIRES THESE INSIDE AND OUTSIDE ROOM.
  
 3) NOTE: PLEASE CLARIFY THE *EXISTING* BATH GFI CIRCUIT
 WITH 1500AV LOAD?
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-05-14 Cont ID  
Sent By dpalmer Date 2007-05-14 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2007-05-14 Time 09:28 Sent To  
Notes
2007-05-14 09:29:39** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE: PLEASE SEE 210.4 AS THE DISHWASHER AND
 DISPOSAL SEEM TO BE FEEDING THE SAME YOKE WHICH WOULD
 REQUIRE 2-POLE BREAKER.THE BOTH ARE CURRENTLY BEING
 SHOWN AS SINGLE POLE BREAKERS>
 PLEASE ADJUST BREAKER(S) OR PLANS FOR THE DEVICES.
  
 2) NOTE: PLEASE SEE THE PLANS ARE MISSING THE OUTLET
 FOR RANGE/OVEN.
 FBC 106.1.2
  
 3) NOTE: PLEASE CORRELATE THE LOAD CALCULATIONS WITH
 THE ITEMS ON THE PANEL SCHEDULES. PLEASE SEE THERE ARE
 MANY ITEMS ON CALCS WHICH ARE NOT ON PANEL SCHEDULE?
 NEC 220, 408.4, 310.16, 240.4.
 FBC 106.3.5.4
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-12-30 Cont ID  
Sent By dpalmer Date 2006-12-30 Time 16:03 Rev Time 0.00
Received By dpalmer Date 2006-12-30 Time 15:49 Sent To PC
Notes
2006-12-30 16:03:42REDLINED PLANS.COUNTER SPACE IS BEING SHOWN IN FRONT
 OF THE NEW PANEL WHICH IS NOT PERMITTED PER 110.26

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-12-03 Cont ID  
Sent By dpalmer Date 2006-12-03 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2006-12-03 Time 17:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 19:41 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 19:41 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-05-29 Cont ID  
Sent By mawillia Date 2007-05-29 Time 10:16 Rev Time 0.00
Received By mawillia Date 2007-05-29 Time 09:59 Sent To  
Notes
2007-05-29 10:15:40*****PROVISO*****
  
 ALL PLAN REVIEWS COMMENTS ARE TO BE SATISFIED BEFORE
 SHEET E1 IS STAMPED.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 13:28 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 13:28 Sent To AD
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-07-31 Cont ID  
Sent By adarroug Date 2007-07-31 Time 15:49 Rev Time 0.00
Received By adarroug Date 2007-07-31 Time 15:49 Sent To E
Notes
2007-07-31 15:49:30TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 11:49 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 11:48 Sent To E
Notes
2007-07-12 11:49:10TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-07-12 Cont ID  
Sent By adarroug Date 2007-07-12 Time 10:44 Rev Time 0.00
Received By adarroug Date 2007-07-12 Time 10:44 Sent To B
Notes
2007-07-12 10:44:45TO "MJACOBS" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-05-11 Cont ID  
Sent By adarroug Date 2007-05-11 Time 15:53 Rev Time 0.00
Received By adarroug Date 2007-05-11 Time 15:53 Sent To  
Notes
2007-05-11 15:53:24TO "BOB"#16

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 10:28 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 10:28 Sent To E
Notes
2006-12-26 10:28:41TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-17 Cont ID  
Sent By adarroug Date 2006-11-17 Time 15:51 Rev Time 0.00
Received By adarroug Date 2006-11-17 Time 15:51 Sent To E
Notes
2006-11-17 15:51:20TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-08-09 Time   Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 17:46 Sent To  
Notes
2006-08-03 00:00:00BOB #6
2006-07-20 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 14:04 Rev Time  
Received By pschmitz Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-08-05 Cont ID  
Sent By pschmitz Date 2006-08-05 Time 14:04 Rev Time 0.00
Received By pschmitz Date 2006-08-05 Time 14:04 Sent To  
Notes
2006-08-05 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 PROVISO
  
 1) REPLACE EX FIXTURES ONLY
  
 2) REVISION REQUIRED.
  
 END OF COMMENTS, QUESTIONS 561-805-6692