Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-19 Cont ID  
Sent By dpalmer Date 2006-07-19 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2006-07-19 Time 20:20 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 20:38 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 20:32 Sent To PC
Notes
2006-07-18 00:00:00** UNSAT **
  
 1) NOTE: PLEASE BE SURE TO PRINT NAME
 AND SIGN RISER AND LOAD CALCUALTIONS.
 FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-18 Time   Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 15:10 Sent To  
Notes
2006-07-18 00:00:00TO "E" BOX