Plan Review Details - Permit 06070850
Plan Review Stops For Permit 06070850
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By mjacobs Date 2007-06-28 Time 14:12 Rev Time 0.00
Received By mjacobs Date 2007-06-28 Time 11:16 Sent To  
Notes
2007-06-28 14:11:58WAITING FOR ENGINEER TO CHANGE THE ASCE CODE REFERENCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-02-26 Cont ID  
Sent By mjacobs Date 2007-02-26 Time 06:47 Rev Time 0.00
Received By mjacobs Date 2007-02-26 Time 05:52 Sent To  
Notes
2007-02-26 07:41:56 
  
 BUILDING PLAN REVIEW
 PERMIT:06070850
 ADD:5200 N. FLAGLER DR.
 CONT: PALM BEACH AIR INC.
 TEL: (561)833-3030
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)FBC. 106.1 SUBMIT TWO COMPLETE SETS OF DRAWINGS.
  
 3) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)THIS IS A FLOOD ZONE AREA (A-5), THE SLAB SHALL BE
 AT LEAST SIX INCHES ABOVE THE BASE FLOOD ELEVATION(7
 FT.)
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-16 Cont ID  
Sent By alange Date 2006-10-16 Time 15:48 Rev Time 0.00
Received By alange Date 2006-10-16 Time 15:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 11:18 Rev Time 0.00
Received By alange Date 2006-08-10 Time 11:03 Sent To  
Notes
2006-08-10 00:00:00DENIED
  
 1.PROPERTY IS IN FLOOD ZONE "A".SHOW
 SLAB AT A MINIMUM OF 6" ABOVE THE BASE
 FLOOD ELEVATION OF 7FT NGVD.
 AN ELEVATION CERTIFICATE IS REQUIRED AT
 FINAL INSPECTION.
  
 2.SHOW METHOD OF GENERATOR ATTACHMENT
 TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2007-06-21 Cont ID  
Sent By dpalmer Date 2007-06-21 Time 20:54 Rev Time 0.00
Received By dpalmer Date 2007-06-21 Time 20:04 Sent To  
Notes
2007-06-21 20:55:33*** NOTES REDLINED ***
  
 1) NOTE: ELECTRICAL PERMIT FOR *GEN-ELEC* IS STILL
 REQUIRED AS APPLICATION IS ONLY FOR GENERATOR
 INSTALLATION.
 THE LICENSED ELECTRICAL CONTRACTOR MAY REFERENCE THIS
 PLAN FOR TURN-AROUND ELECTRICAL PERMIT.
  
 2) NOTE: PLEASE BE SURE TO VERIFY COMPLIANCE WITH HOUSE
 BILL 7121 FOR NEW AND EXISTING RESIDENTIAL HIGH-RISE
 BUILDINGS.
 THIS WILL GO THROUGH THE STATE ELEVATOR INSPECTOR.
  
  
 ** IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH.
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-02-25 Cont ID  
Sent By dpalmer Date 2007-02-25 Time 10:17 Rev Time 0.00
Received By dpalmer Date 2007-02-25 Time 09:13 Sent To  
Notes
2007-02-25 10:20:27*** UNSAT 2NDREVIEW ***
  
  
 ** THE *RESUB* FEE WAS NOT PAID WHEN PLANS WERE
 RESUBMITTED WHICH IS REQUIRED. PLANS WILL NOT BE
 RELEASED UNTIL FEE IS PAID.
  
 ** ONE COPY OF PLANS AND COPY OF PERMIT APPLICATION
 WILL BE RETAINED BY THIS OFFICE.
  
  
 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST
 ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE
 PERMIT WAS APPLIED FOR BEFORE THE CODES CHNAGES OF
 DECEMBER 8TH, 2006.
 2004 FBC.
 2002 NFPA-70 (NEC).
 2002 NFPA-72
 2003 NFPA-101
 2002 NFPA-110
 ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE
 REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR
 REVIEWER(S).
 PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH
 REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD
 BE REVISED ACCORDINGLY.
  
 2) NOTE: PLEASE SEE GAS REVIEW NOTES, AS NO
 MANUFACTURES/SPECS CUTS SHEETS WERE SUBMITTED FOR TANK
 AS PROPOSED.
 GAS PERMIT IS APPLIED FOR AT THIS TIME AND PLANS
 INDICATE UNDER SEPARATE PERMIT?
 PLEASE SEE GAS REVIEW NOTES.
  
 3) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH
 REFLECT A 700AMP BREAKER FEEDING A 600A PANEL WHERE
 PLANS CALL FOR A 600AMP BREAKER AT THIS SAME LOCATION
 FOR THE GENERATOR? PLEASE CORRELATE AND ADJUST AS
 NEEDED.
  
 4) NOTE: PLEASE SEE NOTE #3 ABOVE WITH RESPECT TO
 CONDUCTOR SIZES IF INDEED THE BREAKER IS 700AMPS?
 310.16, 240.4
  
 5) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS TO PLACE
 NEW CIRCUITS INTO PANEL *EM* WHICH ARE NOT LEGALLY
 REQUIRED OR EMERGENCY SYSTEMS REQUIRED CIRCUITS. PLEASE
 SEE THE NEC 700 AND 701 AS 702 TYPE CIRCUITS MAY NOT BE
 IN SAME EQUIPMENT.
 PLEASE DO NOT INDICATE SYSTEMS OTHER THAN MENTIONED
 ABOVE UNLESS INSTALLING ANOTHER 702 SYSTEM WHICH WILL
 REQUIRE A SEPARATE ATS AND LOAD SHEDDING, PANEL
 SCHEDULE, LOADS ETC.
 PLEASE SEE THE LOAD SUMMARY ON PLANS DOES NOT INCLUDE
 ANY OF THESE LOADS MENTIONED IN NOTES.
 PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR THE
 EXISTING EM PANEL.
 310.16, 240.4, 215.5, 701.6, 700.6, 702.6, 408.4, ETC
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION.
 PLEASE ALSO SEE CHAPTER 6 OF NFPA-110 2002.
  
 6) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEW;
 PLEASE SUBMIT ALL PLANS INTO COMPLETE SETS FOR REVIEW
 AND STAMPING. PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE
 BE SURE TO REMOVE ANY OLD/VOIDED SHEETS FROM SHEETS.
  
 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE FLOOD
 ELEVATION AS REQUIRED PER CHAPTER 7 OF NFPA-110. PLEASE
 STATE IF THIS ELEVATION IS THAT FROM TEH SLOSH CHARTS
 BASED ON A CAT 4 HURRICANE OR THAT OF THE LEVELS BASED
 ON THE " 100 YR STORM LEVEL".
 7.2.3*
  
 8) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE
 SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND
 MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED
 BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT
 GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS
 NOTED ABOVE.
 AS THE SCOPE OF WORK HAS ONCE AGAIN INCREASED THE VALUE
 HAS NOT BEEN ADJUSTED, PLEASE DO SO OR A VALUE WILL BE
 ASSESSED USING THE FBC AND MARSHALL'S & SWIFT GUIDES.
  
 9) NOTE: THE TIME FOR FUEL CONSUMPTION SHALL BE PLACED
 ON PLANS BASED ON THE "ON-SITE" FUEL.
 THIS WAS NOTED ON PREVIOUS REVIEW.
  
 ** PLEASE KNOW BASED ON THE ELECTRICAL RISER SUBMITTED
 OF THE EXISTING ELECTRICAL SERVICE, THERE ARE SEVERAL
 ITEMS WHICH ARE NOT COMPLIANT FOR THE CURRENT CODES AND
 CODES FOR AT LEAST THE LAST 20 YEARS, THIS REVIEWER IS
 NOT RESPONSIBLE FOR THE EXISTING ELECTRICAL SERVICE AND
 HOW EQUIPMENT IS FED. NO SCOPE OF WORK IS BEING APPLIED
 FOR TO UPDATE OR DO WORK WITH THE EXISTING SERVICE AS
 SHOWN.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-10-14 Cont ID  
Sent By dpalmer Date 2006-10-14 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2006-10-14 Time 19:02 Sent To  
Notes
2006-10-14 19:38:24*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME
 NEW NOTES FOR PLANS SUBMITTED WHICH NOW INDICATE ITEMS
 NEEDED ON PREVIOUS REVIEW.
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT
 SHEETS FOR ALL NEW EQUIPMENT WHICH WILL BE INSTALLED.
 PLEASE ALSO KNOW SOME COMMENTS BELOW WILL REQUIRE OTHER
 SPECS (TANK).
  
 2) NOTE: PLEASE SEE 700.12B3 AND 701.11B3 AS ON SITE
 FUEL IS REQUIRED FOR THE MINIMUM AMOUNT OF TIME
 REQUIRED FOR BOTH EM AND LEGALLY REQUIRED."PRIME MOVERS
 SHALL NOT BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS
 SYSTEM FOR THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY
 FOR THEIR COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR
 AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO
 ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED."
  
 3) NOTE: PLEASE SEE NFPA-20 2003 9.6.2.2 THE FUEL
 SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS
 OF FIRE PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP
 CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER
 DEMANDS.
 THIS IS REQUIRED FOR "ONSITE" FUEL.
  
 4) NOTE: PLEASE SEEE NFPA-110 7.2.3*, THIS UNIT IS
 LOCATED IN A "FLOOD ZONE A, (SEE BLDG REVIEW ALSO).
 PLEASE PROVIDE COMPLETE ELEVATION FOR THIS TO MEET THE
 MIN LEVELS FOR EITHER ONE OF THE FOLLOWING. 100YR STORM
 ELEVATION OR BASED ON A CAT 4 STORM FROM THE "SLOSH"
 PREDICTION CHARTS.
  
 5) NOTE: PLEASE SEE PLUMB REVIEW COMMENTS FOR TYPE OF
 MATERIALS REQUIRED FOR GAS LINE PER 7.9.3.1GALVANIZED
 FUEL LINES SHALL NOT BE USED.
  
 6) NOTE: PLEASE SEE WE ARE UNABLE TO VERIFY THE AIC
 RATING FOR EQUIPMENT AT THIS TIME DUE TO GEN SPEC NOT
 SUBMITTED.
 PLEASE SEE 110.9, 240.12 FOR DETAIL ON SELECTIVE
 COORDINATION. PLEASE ALSO INDICATE LET THROUGH AND THE
 EXSITING RATING FOR THE EM PANEL MAIN.
  
 7) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE
 SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND
 MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT
 IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED
 BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT
 GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS
 NOTED ABOVE.
  
  
 *** PLEASE KNOW AS SOME INFORMATION IS NOT YET
 SUBMITTED, THERE MAY BE FUTURE COMMENTS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-08-02 Cont ID  
Sent By dpalmer Date 2006-08-02 Time 19:44 Rev Time 0.00
Received By dpalmer Date 2006-08-02 Time 19:26 Sent To  
Notes
2006-08-02 00:00:00************ UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED AR
 PHOTO-COPIES OF SIGNEDAND SEALED
 PLANS.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE PLANS NOTE THAT THE
 GEN IS NOT REQUIRED FOR LIFE SAFETY:
 PLEASE PROVIDE INFORMATION FOR WHAT IS
 PROVIDING BACK UP FOR EM SYSTEMS.
 CAN NOT VERIFY CODE COMPLIANCE ITEMS AT
 THIS TIME FOR THIS.
 IS THIS BUIDLING A HIGH-RISE?
 PLEASE SEE 700.12B3
 PLEASE SEE 701.11B3
 PLEASE SEE THAT NO PANEL SCHEDULES,
 INTENDED LOADS ETC WERE SUBMITTED OR
 SHOWN FOR THIS NEW GENERATOR.
  
 3) NOTE: PLEASE PROVIDE AN ELECTRICAL
 DIAGRAM TO VERIFY CONDUCTORS, FEEDERS,
 CONDUITS, OCP ETC ETC.
 PLEASE SEE NO INFORMATION OR ELECTRICAL
 PLANS WERE SUBMITTED SHOWING HOW THIS
 UNIT IS BEING WIRED IN WITH THE EXISTING
 SERVICE.
 PLEASE PROVIDE OCP ON GENERATOR ETC.
 PLEASE PROVIDE AIC RATINGS ETC
 PLEASE SEE NEC 2002.
 THERE ARE TOO MANY CODE ARTICLES TO
 REFERENCE TO COMPLETE PLANS.
 FBC 106.1.2
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR NEW GEN, WP
 ENCLOUSURE (IF NOT PART OF GEN) ETC.
 106.1.2, NEC 90.8, 110.3 ETC
  
 ** PLEASE KNOW, PLANS AND SUBMITTED
 PACKAGE IS NOT COMPLETE AT THIS TIME AND
 THERE MAY BE FURTHER COMMENTS ONCE PLANS
 ARE COMPLETE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-06-28 Cont ID  
Sent By mwennerg Date 2007-06-28 Time 10:33 Rev Time 0.00
Received By mwennerg Date 2007-06-28 Time 10:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-03-08 Cont ID  
Sent By mwennerg Date 2007-03-08 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2007-03-08 Time 14:29 Sent To  
Notes
2007-03-08 14:32:05***DENIED***
  
 PLEASE NOTE THAT COMMENTS FROM LAST FIRE REVIEW HAVE
 NOT BEEN ADDRESSED.
  
 1) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY STANDBY AND POWER SYSTEMS. PLEASE ILLUSTRATE
 ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW(561) 805-6722
 FIRE PREVENTION(561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-06 Cont ID  
Sent By mwennerg Date 2006-11-06 Time 13:29 Rev Time 0.00
Received By mwennerg Date 2006-11-06 Time 13:29 Sent To  
Notes
2006-11-06 13:39:35***DENIED***
  
 1) PLEASE SUBMIT MANUFACTURER SPEC SHEETS FOR GENERATOR
 AND ASSOCIATED EQUIPMENT.
  
 2) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR
 EMERGENCY AND STANDBY POWER SYSTEMS. PLEASE ACKNOWLEDGE
 OR SHOW ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 13:44 Rev Time 0.00
Received By mwennerg Date 2006-08-31 Time 13:44 Sent To  
Notes
2006-08-31 00:00:00***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING FS AND FAC REQUIREMENTS.
  
 2) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 EQUIPMENT.
  
 3) PLEASE SHOW LOCATION OF GENERATOR AS
 IT APPLIES TO BUILDING OPENINGS AND GIVE
 DIMENSIONS.
  
 4) WORK SHALL COMPLY WITH APPLICABLE
 BUILDING CODES AND NFPA 110, STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-07-13 Cont ID  
Sent By kstevens Date 2007-07-13 Time 07:08 Rev Time 0.00
Received By kstevens Date 2007-07-11 Time 17:30 Sent To  
Notes
2007-07-13 07:10:27PLANS APPROVED AT THIS TIME, BUT THE APPLICATION IS NOW
 A DUPLICATE AND DOES NOT HAVE THE SUBS SIGNED ON. SINCE
 THE PERMIT NUMBERS HAVE BEEN GENERATED, THE SUBS SHALL
 SIGN ON THE NEW DUPLICATE APPLICATION PRIOR TO ISSUING
 THE GEN-COM PERMIT.
  
 7-13-7 SUBS SIGNED ON PERMIT TO BE ISSUED

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-03-07 Cont ID  
Sent By kstevens Date 2007-03-07 Time 17:41 Rev Time 0.00
Received By kstevens Date 2007-03-07 Time 17:41 Sent To  
Notes
2007-03-07 18:08:29DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 FROM PREVIOUS REVIEWS
  
 A. OK
 B. OK
  
 C.THE FOLLOWING INFORMATION IS
 REQUIRED FOR REVIEW FOR GAS PERMIT:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. N/A
 7. OK
 8.N/A
 9. OK
  
 ************NEW COMMENTS*************
  
 A. NEW PLANS WITH NEW INFORMATION REQUIRE NEW COMMENTS.
 NOW LP-GAS ALSO INDICATED ON PLANS.
  
 1B. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. - THE LENGTHS OF PIPE SHOWN ON THE
 ISOMETRIC DO NOT REFLECT THE LENGTHS OF PIPE AS SCALED
 ON THE 1/8" SCALE FLOOR PLAN.SCALE INDICATES THE
 TOTAL DEVELOPED LENGTH ON THE NATURAL GAS SYSTEM TO BE
 APPROX. 131'. PLEASE CLARIFY. SECTION 106.1.1.-- SHOW
 THE SHUT OFF VALVE UPSTREAM OF THE REGULATORS. SECTION
 409.4. A DRIP/SEDIMENT TRAP IS REQUIRED DOWNSTREAM OF
 THE EQUIPMENT SHUT OFF VALVE. SECTIONS 408.2 & 408.4.
  
 2B. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). - AS INDICATED IN COMMENT
 1B. THE TOTAL DEVELOPED LENGTH APPEARS TO BE ABOUT
 131'. PLEASE VERIFY. SECTION 106.1.1.
  
 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE
 SECOND STAGE REGULATORS FOR THE NATURAL GAS AND LP GAS
 SYSTEMS. THE REGULATORS SHALL BE LISTED AND INDICATE
 THE MODEL NUMBER FOR EACH REGULATOR ON MANUF.
 SPECIFICATION SHEETS. SECTION 410.2((2)(3).
  
 4B. SUBMIT THE MANUF. SPECIFICATIONS FOR THE "AUTOMATIC
 TRANSFER SOLENOID SWITCH" INDICATED ON THE STANDBY
 GENERATOR MECHANICAL PLAN. THIS SOLENOID TRANSFER
 SWITCH SHALL BE LISTED FOR BOTH NATURAL GAS AND LP GAS
 AND SHALL INDICATE INSTALLATION INSTRUCTIONS. SECTION
 106.1.2.
  
 5B. SHOW THE PIPE SIZE OF THE EXISTING NATURAL GAS LINE
 FROM THE NATURAL GAS METER TO THE POINT OF CONNECTION
 OF THE NEW PE PIPE. ALSO INDICATE THE MATERIAL OF THAT
 EXISTING PIPE. SECTION 106.1.2 AND TABLES 402.4.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-10-30 Cont ID  
Sent By kstevens Date 2006-10-30 Time 08:17 Rev Time 0.00
Received By kstevens Date 2006-10-30 Time 08:17 Sent To  
Notes
2006-10-30 08:42:45DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. OK
 B. OK
  
 C. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 REVIEW FOR GAS PERMIT:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE
 NOTED, BUT GALVANIZED PIPE IS NOT APPROVED FOR
 UNDERGROUND PER SECTION 404.8.
  
 3. OK
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE MAXIMUM LOAD ON THE 2" PIPE
 PER TABLE IS 1,300,000 BTU'S.1,717,000 BTU'S SHOWN.
 MINIMUM 2-1/2" PIPE REQUIRED.
  
 5. OK
 6. N/A
 7. OK
 8.N/A
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTIONS SHALL BE
 SUBMITTED TO DETERMING THE DISTANCE FROM
 STRUCTURES/WALLS REQUIRED.
 ****NO RESPONSE NOTED, NOT ADDRESSED
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By kstevens Date 2006-08-10 Time 07:01 Rev Time 0.00
Received By kstevens Date 2006-08-10 Time 07:00 Sent To  
Notes
2006-08-10 00:00:00DENIED
 REFERNCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 A. PLANS SHALL BE SEALED PER SECTION
 106.1.
  
 B. SUBMIT A SITE PLAN SHOWING ALL
 STRUCTURES, WALLS ETC. AJOINING THE
 GENERATOR. SECTION 106.1.2.
  
 C. SEPARATE GAS PERMIT REQUIRED. THE
 FOLLOWING INFORMATION IS REQUIRED FOR
 REVIEW FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. N/A
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8.N/A
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION INSTRUCTIONS SHALL BE
 SUBMITTED TO DETERMING THE DISTANCE FROM
 STRUCTURES/WALLS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-06-06 Cont ID  
Sent By adarroug Date 2007-06-06 Time 11:31 Rev Time 0.00
Received By adarroug Date 2007-06-06 Time 11:31 Sent To  
Notes
2007-06-21 14:29:04TO "COMM" BD#8
2007-06-06 11:32:52WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 16:18 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 16:18 Sent To  
Notes
2007-02-20 09:25:49TO "COMM" BD#3
2007-02-08 16:18:39WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 16:00 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 16:00 Sent To  
Notes
2006-10-12 13:58:43TO "COMM" BD#31
2006-09-26 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-31 Cont ID  
Sent By mwennerg Date 2006-08-31 Time 13:58 Rev Time 0.00
Received By mwennerg Date 2006-07-17 Time 08:49 Sent To  
Notes
2006-08-01 00:00:00TO "COMM" BD#46
2006-07-17 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-06-25 Cont ID  
Sent By tgordon Date 2007-06-25 Time 13:44 Rev Time 0.20
Received By tgordon Date 2007-06-25 Time 13:44 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-21 Cont ID  
Sent By tgordon Date 2007-02-21 Time 09:38 Rev Time 0.30
Received By tgordon Date 2007-02-21 Time 09:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-17 Cont ID  
Sent By tgordon Date 2006-10-17 Time 11:02 Rev Time 0.30
Received By tgordon Date 2006-10-17 Time 11:02 Sent To  
Notes
2006-10-17 11:02:58*** DENIED ***
 1) PLEASE SEE OTHER REVIEW NOTES, MAKE
 CORRECTIONS AND RE-SUBMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 15:39 Rev Time 0.20
Received By tgordon Date 2006-08-25 Time 15:39 Sent To  
Notes
2006-08-25 00:00:00*** DENIED ***
 1) PLEASE SEE OTHER REVIEW NOTES, MAKE
 CORRECTIONS AND RE-SUBMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 3 Status P Date 2007-02-22 Cont ID  
Sent By kdfreema Date 2007-02-22 Time 16:57 Rev Time 0.00
Received By kdfreema Date 2007-02-22 Time 16:57 Sent To  
Notes
2007-02-26 14:56:28PROVISO: A WALL OR FENCE IN ACCORDANCE WITH THE
 REQUIREMENTS OF SECTION 94-444(B) SHALL BE PROVIDED
 UNDER A SEPARATE PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-03 Cont ID  
Sent By kdfreema Date 2006-11-03 Time 11:17 Rev Time 0.00
Received By kdfreema Date 2006-11-03 Time 11:17 Sent To  
Notes
2006-11-03 11:17:36PLEASE SUPPLY A SURVEY SHOWING THE LOCATION OF THE
 GENERATOR. RESPONSE NOTED, HOWEVER, WHAT WAS PROVIDED
 IS SITE PLAN, NOT A SURVEY. PLEASE ENSURE THAT ALL
 EASEMENTS ARE SHOWN ON THE SURVEY.
  
 THE GENERATOR SHALL BE SCREENED AND LANDSCAPED
 ACCORDING TO THE REQUIREMENTS OF SECTION 94-444(B) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS. THE
 SCREENING SHALL CONSIST OF WALLS OR FENCING. THE
 LANDSCAPING SHALL CONSIST OF SHRUBS OR HEDGES PLANTED
 AT 2 FEET ON-CENTER. RESPONSE NOTED, HOWEVER, A FENCE
 OR WALL IN ADDITION TO THE LANDSCAPING IS REQUIRED.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY
 QUESTIONS. (561) 822-1435 OR [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-14 Cont ID  
Sent By kdfreema Date 2006-08-14 Time 11:53 Rev Time 0.00
Received By kdfreema Date 2006-08-14 Time 11:53 Sent To  
Notes
2006-08-14 00:00:001) PLEASE SUPPLY A SURVEY SHOWING THE
 LOCATION OF THE GENERATOR AS IT RELATES
 TO SURROUNDING PROPERTIES.
  
 2) THE GENERATOR SHALL BE PROPERLY
 SCREENED AND LANDSCAPED. THE SCREENING
 SHALL CONSIST OF WALLS OR FENCING AND
 LANDSCAPING. THE LANDSCAPING SHALL
 CONSIST OF SHRUBS OR HEDGES PLANTED AT
 24? ON CENTER. LANDSCAPE PLANS SHALL BE
 SIGNED AND SEALED BY A REGISTERED
 LANDSCAPE ARCHITECT.