Plan Review Stops For Permit 06070850 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-06-28 |
Time |
14:12 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-06-28 |
Time |
11:16 |
Sent To |
|
|
Notes |
2007-06-28 14:11:58 | WAITING FOR ENGINEER TO CHANGE THE ASCE CODE REFERENCE. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2007-02-26 |
Time |
06:47 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2007-02-26 |
Time |
05:52 |
Sent To |
|
|
Notes |
2007-02-26 07:41:56 | | | | | BUILDING PLAN REVIEW | | PERMIT:06070850 | | ADD:5200 N. FLAGLER DR. | | CONT: PALM BEACH AIR INC. | | TEL: (561)833-3030 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | W/ 2006 FBC REVISIONS | | * WEST PALM BEACH AMENDMENTS | | | | REVIEW 1ST | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2)FBC. 106.1 SUBMIT TWO COMPLETE SETS OF DRAWINGS. | | | | 3) 2004 FL. BLD CODE 1603.1.4 THE | | FOLLOWING INFORMATION RELATED TO WIND | | SHALL BE SHOWN ON THE CONSTRUCTION | | DRAWINGS, | | 1)- BASIC WIND SPEED, MPH | | 2)- WIND IMPORTANCE FACTOR, & BUILDING | | CATEGORY | | 3)- WIND EXPOSURE | | 4)- INTERNAL PRESSURE COEFFICIENT, | | 5)- COMPONENTS & CLADDING, THE DESIGN | | WIND PRESSURES IN TERMS OF PSF. | | | | 4)THIS IS A FLOOD ZONE AREA (A-5), THE SLAB SHALL BE | | AT LEAST SIX INCHES ABOVE THE BASE FLOOD ELEVATION(7 | | FT.) | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-10-16 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-10-16 |
Time |
15:48 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-10-16 |
Time |
15:48 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-08-10 |
Time |
11:18 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-08-10 |
Time |
11:03 |
Sent To |
|
|
Notes |
2006-08-10 00:00:00 | DENIED | | | | 1.PROPERTY IS IN FLOOD ZONE "A".SHOW | | SLAB AT A MINIMUM OF 6" ABOVE THE BASE | | FLOOD ELEVATION OF 7FT NGVD. | | AN ELEVATION CERTIFICATE IS REQUIRED AT | | FINAL INSPECTION. | | | | 2.SHOW METHOD OF GENERATOR ATTACHMENT | | TO SLAB. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2007-06-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-06-21 |
Time |
20:54 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-06-21 |
Time |
20:04 |
Sent To |
|
|
Notes |
2007-06-21 20:55:33 | *** NOTES REDLINED *** | | | | 1) NOTE: ELECTRICAL PERMIT FOR *GEN-ELEC* IS STILL | | REQUIRED AS APPLICATION IS ONLY FOR GENERATOR | | INSTALLATION. | | THE LICENSED ELECTRICAL CONTRACTOR MAY REFERENCE THIS | | PLAN FOR TURN-AROUND ELECTRICAL PERMIT. | | | | 2) NOTE: PLEASE BE SURE TO VERIFY COMPLIANCE WITH HOUSE | | BILL 7121 FOR NEW AND EXISTING RESIDENTIAL HIGH-RISE | | BUILDINGS. | | THIS WILL GO THROUGH THE STATE ELEVATOR INSPECTOR. | | | | | | ** IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPARTMENT | | CITY OF WEST PALM BEACH. | | 561-805-6717 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-02-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-25 |
Time |
10:17 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-25 |
Time |
09:13 |
Sent To |
|
|
Notes |
2007-02-25 10:20:27 | *** UNSAT 2NDREVIEW *** | | | | | | ** THE *RESUB* FEE WAS NOT PAID WHEN PLANS WERE | | RESUBMITTED WHICH IS REQUIRED. PLANS WILL NOT BE | | RELEASED UNTIL FEE IS PAID. | | | | ** ONE COPY OF PLANS AND COPY OF PERMIT APPLICATION | | WILL BE RETAINED BY THIS OFFICE. | | | | | | 1) NOTE: PLEASE BE SURE ALL PLANS REFLECT THE LATEST | | ADOPTED CODES PER THE STATE OF FLORIDA. PLEASE SEE THE | | PERMIT WAS APPLIED FOR BEFORE THE CODES CHNAGES OF | | DECEMBER 8TH, 2006. | | 2004 FBC. | | 2002 NFPA-70 (NEC). | | 2002 NFPA-72 | | 2003 NFPA-101 | | 2002 NFPA-110 | | ** THESE CODES ARE REQUIRED AT A MINIMUM FOR THIS TRADE | | REVIEWER; OTHERS MAY BE REQUIRED PER OTHER TRADES OR | | REVIEWER(S). | | PLEASE SEE THERE ARE MANY AREAS ON THE PLANS WHICH | | REFERENCE OLDER CODES FROM PREVIOUS CODES, THESE SHOULD | | BE REVISED ACCORDINGLY. | | | | 2) NOTE: PLEASE SEE GAS REVIEW NOTES, AS NO | | MANUFACTURES/SPECS CUTS SHEETS WERE SUBMITTED FOR TANK | | AS PROPOSED. | | GAS PERMIT IS APPLIED FOR AT THIS TIME AND PLANS | | INDICATE UNDER SEPARATE PERMIT? | | PLEASE SEE GAS REVIEW NOTES. | | | | 3) NOTE: PLEASE SEE MANUFACTURES SPECS/CUT SHEETS WHICH | | REFLECT A 700AMP BREAKER FEEDING A 600A PANEL WHERE | | PLANS CALL FOR A 600AMP BREAKER AT THIS SAME LOCATION | | FOR THE GENERATOR? PLEASE CORRELATE AND ADJUST AS | | NEEDED. | | | | 4) NOTE: PLEASE SEE NOTE #3 ABOVE WITH RESPECT TO | | CONDUCTOR SIZES IF INDEED THE BREAKER IS 700AMPS? | | 310.16, 240.4 | | | | 5) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS TO PLACE | | NEW CIRCUITS INTO PANEL *EM* WHICH ARE NOT LEGALLY | | REQUIRED OR EMERGENCY SYSTEMS REQUIRED CIRCUITS. PLEASE | | SEE THE NEC 700 AND 701 AS 702 TYPE CIRCUITS MAY NOT BE | | IN SAME EQUIPMENT. | | PLEASE DO NOT INDICATE SYSTEMS OTHER THAN MENTIONED | | ABOVE UNLESS INSTALLING ANOTHER 702 SYSTEM WHICH WILL | | REQUIRE A SEPARATE ATS AND LOAD SHEDDING, PANEL | | SCHEDULE, LOADS ETC. | | PLEASE SEE THE LOAD SUMMARY ON PLANS DOES NOT INCLUDE | | ANY OF THESE LOADS MENTIONED IN NOTES. | | PLEASE SUBMIT A COMPLETE PANEL SCHEDULE FOR THE | | EXISTING EM PANEL. | | 310.16, 240.4, 215.5, 701.6, 700.6, 702.6, 408.4, ETC | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION. | | PLEASE ALSO SEE CHAPTER 6 OF NFPA-110 2002. | | | | 6) NOTE: PLEASE SEE AS STATED IN PREVIOUS REVIEW; | | PLEASE SUBMIT ALL PLANS INTO COMPLETE SETS FOR REVIEW | | AND STAMPING. PLEASE DO NOT SUBMIT LOOSE SHEETS. PLEASE | | BE SURE TO REMOVE ANY OLD/VOIDED SHEETS FROM SHEETS. | | | | 7) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE FLOOD | | ELEVATION AS REQUIRED PER CHAPTER 7 OF NFPA-110. PLEASE | | STATE IF THIS ELEVATION IS THAT FROM TEH SLOSH CHARTS | | BASED ON A CAT 4 HURRICANE OR THAT OF THE LEVELS BASED | | ON THE " 100 YR STORM LEVEL". | | 7.2.3* | | | | 8) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE | | SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND | | MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT | | IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED | | BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT | | GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS | | NOTED ABOVE. | | AS THE SCOPE OF WORK HAS ONCE AGAIN INCREASED THE VALUE | | HAS NOT BEEN ADJUSTED, PLEASE DO SO OR A VALUE WILL BE | | ASSESSED USING THE FBC AND MARSHALL'S & SWIFT GUIDES. | | | | 9) NOTE: THE TIME FOR FUEL CONSUMPTION SHALL BE PLACED | | ON PLANS BASED ON THE "ON-SITE" FUEL. | | THIS WAS NOTED ON PREVIOUS REVIEW. | | | | ** PLEASE KNOW BASED ON THE ELECTRICAL RISER SUBMITTED | | OF THE EXISTING ELECTRICAL SERVICE, THERE ARE SEVERAL | | ITEMS WHICH ARE NOT COMPLIANT FOR THE CURRENT CODES AND | | CODES FOR AT LEAST THE LAST 20 YEARS, THIS REVIEWER IS | | NOT RESPONSIBLE FOR THE EXISTING ELECTRICAL SERVICE AND | | HOW EQUIPMENT IS FED. NO SCOPE OF WORK IS BEING APPLIED | | FOR TO UPDATE OR DO WORK WITH THE EXISTING SERVICE AS | | SHOWN. | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-10-14 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-14 |
Time |
19:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-14 |
Time |
19:02 |
Sent To |
|
|
Notes |
2006-10-14 19:38:24 | *** UNSAT2ND REVIEW *** | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW AND SOME | | NEW NOTES FOR PLANS SUBMITTED WHICH NOW INDICATE ITEMS | | NEEDED ON PREVIOUS REVIEW. | | | | 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES SPECS/CUT | | SHEETS FOR ALL NEW EQUIPMENT WHICH WILL BE INSTALLED. | | PLEASE ALSO KNOW SOME COMMENTS BELOW WILL REQUIRE OTHER | | SPECS (TANK). | | | | 2) NOTE: PLEASE SEE 700.12B3 AND 701.11B3 AS ON SITE | | FUEL IS REQUIRED FOR THE MINIMUM AMOUNT OF TIME | | REQUIRED FOR BOTH EM AND LEGALLY REQUIRED."PRIME MOVERS | | SHALL NOT BE SOLELY DEPENDENT ON A PUBLIC UTILITY GAS | | SYSTEM FOR THEIR FUEL SUPPLY OR MUNICIPAL WATER SUPPLY | | FOR THEIR COOLING SYSTEMS. MEANS SHALL BE PROVIDED FOR | | AUTOMATICALLY TRANSFERRING FROM ONE FUEL SUPPLY TO | | ANOTHER WHERE DUAL FUEL SUPPLIES ARE USED." | | | | 3) NOTE: PLEASE SEE NFPA-20 2003 9.6.2.2 THE FUEL | | SUPPLY CAPACITY SHALL BE SUFFICIENT TO PROVIDE 8 HOURS | | OF FIRE PUMP OPERATION AT 100 PERCENT OF THE RATED PUMP | | CAPACITY IN ADDITION TO THE SUPPLY REQUIRED FOR OTHER | | DEMANDS. | | THIS IS REQUIRED FOR "ONSITE" FUEL. | | | | 4) NOTE: PLEASE SEEE NFPA-110 7.2.3*, THIS UNIT IS | | LOCATED IN A "FLOOD ZONE A, (SEE BLDG REVIEW ALSO). | | PLEASE PROVIDE COMPLETE ELEVATION FOR THIS TO MEET THE | | MIN LEVELS FOR EITHER ONE OF THE FOLLOWING. 100YR STORM | | ELEVATION OR BASED ON A CAT 4 STORM FROM THE "SLOSH" | | PREDICTION CHARTS. | | | | 5) NOTE: PLEASE SEE PLUMB REVIEW COMMENTS FOR TYPE OF | | MATERIALS REQUIRED FOR GAS LINE PER 7.9.3.1GALVANIZED | | FUEL LINES SHALL NOT BE USED. | | | | 6) NOTE: PLEASE SEE WE ARE UNABLE TO VERIFY THE AIC | | RATING FOR EQUIPMENT AT THIS TIME DUE TO GEN SPEC NOT | | SUBMITTED. | | PLEASE SEE 110.9, 240.12 FOR DETAIL ON SELECTIVE | | COORDINATION. PLEASE ALSO INDICATE LET THROUGH AND THE | | EXSITING RATING FOR THE EM PANEL MAIN. | | | | 7) NOTE: PLEASE SEE FBC 108.3 AS THE VALUE FOR COMPLETE | | SCOPE OF WORK ON PLANS SHALL INLCUDE ALL LABOUR AND | | MATERIALS FOR ALL SUBS AND EQUIPMENT, EVEN IF EQUIPMENT | | IS OWNER SUPPLIED. PLEASE KNOW A VALUE MAY BE ASSED | | BASED ON FAIR MARKET VALUE BASED ON MARSHALL'S & SWIFT | | GUIDE AS ADOPTED BY THE FBC ADMINSTRATIVE SECTION AS | | NOTED ABOVE. | | | | | | *** PLEASE KNOW AS SOME INFORMATION IS NOT YET | | SUBMITTED, THERE MAY BE FUTURE COMMENTS. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-08-02 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-02 |
Time |
19:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-08-02 |
Time |
19:26 |
Sent To |
|
|
Notes |
2006-08-02 00:00:00 | ************ UNSAT *********** | | | | 1) NOTE: PLEASE SEE PLANS SUBMITTED AR | | PHOTO-COPIES OF SIGNEDAND SEALED | | PLANS. | | PLEASE SEE FS 471.025, FAC 61G15-23.002 | | | | 2) NOTE: PLEASE SEE PLANS NOTE THAT THE | | GEN IS NOT REQUIRED FOR LIFE SAFETY: | | PLEASE PROVIDE INFORMATION FOR WHAT IS | | PROVIDING BACK UP FOR EM SYSTEMS. | | CAN NOT VERIFY CODE COMPLIANCE ITEMS AT | | THIS TIME FOR THIS. | | IS THIS BUIDLING A HIGH-RISE? | | PLEASE SEE 700.12B3 | | PLEASE SEE 701.11B3 | | PLEASE SEE THAT NO PANEL SCHEDULES, | | INTENDED LOADS ETC WERE SUBMITTED OR | | SHOWN FOR THIS NEW GENERATOR. | | | | 3) NOTE: PLEASE PROVIDE AN ELECTRICAL | | DIAGRAM TO VERIFY CONDUCTORS, FEEDERS, | | CONDUITS, OCP ETC ETC. | | PLEASE SEE NO INFORMATION OR ELECTRICAL | | PLANS WERE SUBMITTED SHOWING HOW THIS | | UNIT IS BEING WIRED IN WITH THE EXISTING | | SERVICE. | | PLEASE PROVIDE OCP ON GENERATOR ETC. | | PLEASE PROVIDE AIC RATINGS ETC | | PLEASE SEE NEC 2002. | | THERE ARE TOO MANY CODE ARTICLES TO | | REFERENCE TO COMPLETE PLANS. | | FBC 106.1.2 | | | | 4) NOTE: PLEASE SUBMIT ALL MANUFACTURES | | SPECS/CUT SHEETS FOR NEW GEN, WP | | ENCLOUSURE (IF NOT PART OF GEN) ETC. | | 106.1.2, NEC 90.8, 110.3 ETC | | | | ** PLEASE KNOW, PLANS AND SUBMITTED | | PACKAGE IS NOT COMPLETE AT THIS TIME AND | | THERE MAY BE FURTHER COMMENTS ONCE PLANS | | ARE COMPLETE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-06-28 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-06-28 |
Time |
10:33 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-06-28 |
Time |
10:33 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-03-08 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2007-03-08 |
Time |
14:29 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2007-03-08 |
Time |
14:29 |
Sent To |
|
|
Notes |
2007-03-08 14:32:05 | ***DENIED*** | | | | PLEASE NOTE THAT COMMENTS FROM LAST FIRE REVIEW HAVE | | NOT BEEN ADDRESSED. | | | | 1) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR | | EMERGENCY STANDBY AND POWER SYSTEMS. PLEASE ILLUSTRATE | | ON PLANS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW(561) 805-6722 | | FIRE PREVENTION(561) 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-11-06 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-11-06 |
Time |
13:29 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-11-06 |
Time |
13:29 |
Sent To |
|
|
Notes |
2006-11-06 13:39:35 | ***DENIED*** | | | | 1) PLEASE SUBMIT MANUFACTURER SPEC SHEETS FOR GENERATOR | | AND ASSOCIATED EQUIPMENT. | | | | 2) WORK SHALL COMPLY WITH NFPA 110, STANDARD FOR | | EMERGENCY AND STANDBY POWER SYSTEMS. PLEASE ACKNOWLEDGE | | OR SHOW ON PLANS. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW (561) 805-6722 OR 804-4756 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-08-31 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-08-31 |
Time |
13:44 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-08-31 |
Time |
13:44 |
Sent To |
|
|
Notes |
2006-08-31 00:00:00 | ***DENIED*** | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | REGARDING FS AND FAC REQUIREMENTS. | | | | 2) PLEASE SUBMIT MANUFACTURER SPEC | | SHEETS FOR GENERATOR AND ASSOCIATED | | EQUIPMENT. | | | | 3) PLEASE SHOW LOCATION OF GENERATOR AS | | IT APPLIES TO BUILDING OPENINGS AND GIVE | | DIMENSIONS. | | | | 4) WORK SHALL COMPLY WITH APPLICABLE | | BUILDING CODES AND NFPA 110, STANDARD | | FOR EMERGENCY AND STANDBY POWER SYSTEMS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2007-07-13 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-07-13 |
Time |
07:08 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-07-11 |
Time |
17:30 |
Sent To |
|
|
Notes |
2007-07-13 07:10:27 | PLANS APPROVED AT THIS TIME, BUT THE APPLICATION IS NOW | | A DUPLICATE AND DOES NOT HAVE THE SUBS SIGNED ON. SINCE | | THE PERMIT NUMBERS HAVE BEEN GENERATED, THE SUBS SHALL | | SIGN ON THE NEW DUPLICATE APPLICATION PRIOR TO ISSUING | | THE GEN-COM PERMIT. | | | | 7-13-7 SUBS SIGNED ON PERMIT TO BE ISSUED |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-03-07 |
Time |
17:41 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-03-07 |
Time |
17:41 |
Sent To |
|
|
Notes |
2007-03-07 18:08:29 | DENIED | | REFERNCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | FROM PREVIOUS REVIEWS | | | | A. OK | | B. OK | | | | C.THE FOLLOWING INFORMATION IS | | REQUIRED FOR REVIEW FOR GAS PERMIT: | | | | 1. OK | | 2. OK | | 3. OK | | 4. OK | | 5. OK | | 6. N/A | | 7. OK | | 8.N/A | | 9. OK | | | | ************NEW COMMENTS************* | | | | A. NEW PLANS WITH NEW INFORMATION REQUIRE NEW COMMENTS. | | NOW LP-GAS ALSO INDICATED ON PLANS. | | | | 1B. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. - THE LENGTHS OF PIPE SHOWN ON THE | | ISOMETRIC DO NOT REFLECT THE LENGTHS OF PIPE AS SCALED | | ON THE 1/8" SCALE FLOOR PLAN.SCALE INDICATES THE | | TOTAL DEVELOPED LENGTH ON THE NATURAL GAS SYSTEM TO BE | | APPROX. 131'. PLEASE CLARIFY. SECTION 106.1.1.-- SHOW | | THE SHUT OFF VALVE UPSTREAM OF THE REGULATORS. SECTION | | 409.4. A DRIP/SEDIMENT TRAP IS REQUIRED DOWNSTREAM OF | | THE EQUIPMENT SHUT OFF VALVE. SECTIONS 408.2 & 408.4. | | | | 2B. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). - AS INDICATED IN COMMENT | | 1B. THE TOTAL DEVELOPED LENGTH APPEARS TO BE ABOUT | | 131'. PLEASE VERIFY. SECTION 106.1.1. | | | | 3B. SUBMIT THE MANUF. SPECIFICATION SHEETS FOR THE | | SECOND STAGE REGULATORS FOR THE NATURAL GAS AND LP GAS | | SYSTEMS. THE REGULATORS SHALL BE LISTED AND INDICATE | | THE MODEL NUMBER FOR EACH REGULATOR ON MANUF. | | SPECIFICATION SHEETS. SECTION 410.2((2)(3). | | | | 4B. SUBMIT THE MANUF. SPECIFICATIONS FOR THE "AUTOMATIC | | TRANSFER SOLENOID SWITCH" INDICATED ON THE STANDBY | | GENERATOR MECHANICAL PLAN. THIS SOLENOID TRANSFER | | SWITCH SHALL BE LISTED FOR BOTH NATURAL GAS AND LP GAS | | AND SHALL INDICATE INSTALLATION INSTRUCTIONS. SECTION | | 106.1.2. | | | | 5B. SHOW THE PIPE SIZE OF THE EXISTING NATURAL GAS LINE | | FROM THE NATURAL GAS METER TO THE POINT OF CONNECTION | | OF THE NEW PE PIPE. ALSO INDICATE THE MATERIAL OF THAT | | EXISTING PIPE. SECTION 106.1.2 AND TABLES 402.4. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
F |
Date |
2006-10-30 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-10-30 |
Time |
08:17 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-10-30 |
Time |
08:17 |
Sent To |
|
|
Notes |
2006-10-30 08:42:45 | DENIED | | REFERNCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | A. OK | | B. OK | | | | C. SEPARATE GAS PERMIT REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR | | REVIEW FOR GAS PERMIT: | | | | 1. OK | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. ****RESPONSE | | NOTED, BUT GALVANIZED PIPE IS NOT APPROVED FOR | | UNDERGROUND PER SECTION 404.8. | | | | 3. OK | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | ****RESPONSE NOTED, BUT THE MAXIMUM LOAD ON THE 2" PIPE | | PER TABLE IS 1,300,000 BTU'S.1,717,000 BTU'S SHOWN. | | MINIMUM 2-1/2" PIPE REQUIRED. | | | | 5. OK | | 6. N/A | | 7. OK | | 8.N/A | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION INSTRUCTIONS SHALL BE | | SUBMITTED TO DETERMING THE DISTANCE FROM | | STRUCTURES/WALLS REQUIRED. | | ****NO RESPONSE NOTED, NOT ADDRESSED | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-08-10 |
Time |
07:01 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-08-10 |
Time |
07:00 |
Sent To |
|
|
Notes |
2006-08-10 00:00:00 | DENIED | | REFERNCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | | | A. PLANS SHALL BE SEALED PER SECTION | | 106.1. | | | | B. SUBMIT A SITE PLAN SHOWING ALL | | STRUCTURES, WALLS ETC. AJOINING THE | | GENERATOR. SECTION 106.1.2. | | | | C. SEPARATE GAS PERMIT REQUIRED. THE | | FOLLOWING INFORMATION IS REQUIRED FOR | | REVIEW FOR GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. N/A | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 8.N/A | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INSTALLATION INSTRUCTIONS SHALL BE | | SUBMITTED TO DETERMING THE DISTANCE FROM | | STRUCTURES/WALLS REQUIRED. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-06-06 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-06-06 |
Time |
11:31 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-06-06 |
Time |
11:31 |
Sent To |
|
|
Notes |
2007-06-21 14:29:04 | TO "COMM" BD#8 | 2007-06-06 11:32:52 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2007-02-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-08 |
Time |
16:18 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-08 |
Time |
16:18 |
Sent To |
|
|
Notes |
2007-02-20 09:25:49 | TO "COMM" BD#3 | 2007-02-08 16:18:39 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-26 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-26 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-26 |
Time |
16:00 |
Sent To |
|
|
Notes |
2006-10-12 13:58:43 | TO "COMM" BD#31 | 2006-09-26 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-31 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-08-31 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-07-17 |
Time |
08:49 |
Sent To |
|
|
Notes |
2006-08-01 00:00:00 | TO "COMM" BD#46 | 2006-07-17 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-06-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-06-25 |
Time |
13:44 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2007-06-25 |
Time |
13:44 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-02-21 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-02-21 |
Time |
09:38 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-02-21 |
Time |
09:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-10-17 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-10-17 |
Time |
11:02 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-10-17 |
Time |
11:02 |
Sent To |
|
|
Notes |
2006-10-17 11:02:58 | *** DENIED *** | | 1) PLEASE SEE OTHER REVIEW NOTES, MAKE | | CORRECTIONS AND RE-SUBMIT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-25 |
Time |
15:39 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2006-08-25 |
Time |
15:39 |
Sent To |
|
|
Notes |
2006-08-25 00:00:00 | *** DENIED *** | | 1) PLEASE SEE OTHER REVIEW NOTES, MAKE | | CORRECTIONS AND RE-SUBMIT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2007-02-22 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2007-02-22 |
Time |
16:57 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2007-02-22 |
Time |
16:57 |
Sent To |
|
|
Notes |
2007-02-26 14:56:28 | PROVISO: A WALL OR FENCE IN ACCORDANCE WITH THE | | REQUIREMENTS OF SECTION 94-444(B) SHALL BE PROVIDED | | UNDER A SEPARATE PERMIT. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-11-03 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2006-11-03 |
Time |
11:17 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2006-11-03 |
Time |
11:17 |
Sent To |
|
|
Notes |
2006-11-03 11:17:36 | PLEASE SUPPLY A SURVEY SHOWING THE LOCATION OF THE | | GENERATOR. RESPONSE NOTED, HOWEVER, WHAT WAS PROVIDED | | IS SITE PLAN, NOT A SURVEY. PLEASE ENSURE THAT ALL | | EASEMENTS ARE SHOWN ON THE SURVEY. | | | | THE GENERATOR SHALL BE SCREENED AND LANDSCAPED | | ACCORDING TO THE REQUIREMENTS OF SECTION 94-444(B) OF | | THE ZONING AND LAND DEVELOPMENT REGULATIONS. THE | | SCREENING SHALL CONSIST OF WALLS OR FENCING. THE | | LANDSCAPING SHALL CONSIST OF SHRUBS OR HEDGES PLANTED | | AT 2 FEET ON-CENTER. RESPONSE NOTED, HOWEVER, A FENCE | | OR WALL IN ADDITION TO THE LANDSCAPING IS REQUIRED. | | | | PLEASE CONTACT KELLY FREEMAN, PLANNER, WITH ANY | | QUESTIONS. (561) 822-1435 OR [email protected] |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-08-14 |
|
|
Cont ID |
|
Sent By |
kdfreema |
Date |
2006-08-14 |
Time |
11:53 |
Rev Time |
0.00 |
Received By |
kdfreema |
Date |
2006-08-14 |
Time |
11:53 |
Sent To |
|
|
Notes |
2006-08-14 00:00:00 | 1) PLEASE SUPPLY A SURVEY SHOWING THE | | LOCATION OF THE GENERATOR AS IT RELATES | | TO SURROUNDING PROPERTIES. | | | | 2) THE GENERATOR SHALL BE PROPERLY | | SCREENED AND LANDSCAPED. THE SCREENING | | SHALL CONSIST OF WALLS OR FENCING AND | | LANDSCAPING. THE LANDSCAPING SHALL | | CONSIST OF SHRUBS OR HEDGES PLANTED AT | | 24? ON CENTER. LANDSCAPE PLANS SHALL BE | | SIGNED AND SEALED BY A REGISTERED | | LANDSCAPE ARCHITECT. |
|
|