Plan Review Details - Permit 06070804
Plan Review Stops For Permit 06070804
Review Stop E ELECTRICAL
Rev No 2 Status N Date 2006-08-15 Cont ID  
Sent By dpalmer Date 2006-08-15 Time 08:39 Rev Time 0.00
Received By dpalmer Date 2006-08-15 Time 08:39 Sent To FIRE
Notes
2006-08-15 00:00:00FIRE PUMP ORIGINALLY ON APPLICATION
 CROSSED OUT. FA DEVICES ONLY, SENT TO
 FIRE

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-20 Cont ID  
Sent By dpalmer Date 2006-07-20 Time 12:52 Rev Time 0.00
Received By dpalmer Date 2006-07-20 Time 12:52 Sent To FIRE
Notes
2006-07-20 00:00:00********* UNSAT *********
  
 1) NOTE: PLEASE SEE NO INFORMATION WAS
 SUBMITTED OR ON PLANS FOR ANY NEW FIRE
 PUMP?
 PLEASE SEE PERMIT APPLICATION MENTIONS
 NEW FIRE PUMP?
 PLEASE SUBMIT RISER DIAGRAM SHOWING NEW
 FIRE PUMP, CONDUITS, CONDUCTORS , ETC
 PLEASE CALRIFY??
  
 2) NOTE: PLEASE SEE THAT ALL PLANS AND
 DESIGNS WHICH ARE NOT REQUIRED TO BE
 DONE BY AND ARCHITECT OR ENGINEER SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE DESIGN PROFESSIONAL TAKING
 RESPONSIBILTY OF SAID DESIGNS AND PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-18 Cont ID  
Sent By mawillia Date 2006-08-18 Time 16:17 Rev Time 0.00
Received By mawillia Date 2006-08-18 Time 15:38 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By mawillia Date 2006-08-01 Time 12:08 Rev Time 0.00
Received By mawillia Date 2006-08-01 Time 11:39 Sent To  
Notes
2006-08-01 00:00:00**DENIED**
  
 1. SINCE THERE APPEARS COOKING EQUIPMENT
 WILL BE USED, CLARIFY IF THE PROPOSED
 ALARM SYSTEM WILL BE TIED INTO THE HOOD/
 SUPPRESSION SYSTEM AS PER NFPA 96
  
 2. FIRE PUMP? IF A FIRE PUMP IS GOING TO
 BE INSTALLED AS PER YOUR APPLICATION,
 THIS NEEDS TO BE REFLECTED ON THE PLANS
 AS WELL AS ADDRESS THE ELECTRICAL PLAN
 REVIEW COMMENTS.
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-11 Cont ID  
Sent By mmiller Date 2006-08-11 Time 10:27 Rev Time 0.00
Received By mmiller Date 2006-08-11 Time 10:26 Sent To E
Notes
2006-08-11 00:00:00SENT TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By mawillia Date 2006-08-01 Time 12:32 Rev Time 0.00
Received By mawillia Date 2006-07-15 Time 09:50 Sent To  
Notes
2006-07-15 00:00:00TO "F" BOX