Plan Review Details - Permit 06070733
Plan Review Stops For Permit 06070733
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By jgomez Date 2006-08-08 Time 15:38 Rev Time 1.00
Received By jgomez Date 2006-08-08 Time 12:41 Sent To PC
Notes
2006-08-08 00:00:00PERMIT UNDER 'H'.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By jgomez Date 2006-07-17 Time 14:53 Rev Time 0.50
Received By jgomez Date 2006-07-17 Time 14:53 Sent To  
Notes
2006-07-17 00:00:00BUILDING REVIEW CHECKLIST:
 1- ENGINEER IS REFERING TO NOA
 02-1023.05. CORRECT NOA THAT WAS
 SUBMITTED TO OBTAIN THE FLORIDA PRODUCT
 APPROVAL IS NOA 02-0212.07. ENGINEER TO
 CORRECT HIS CALCULATIONS AND REFER TO
 THE CORRECT NOA.
  
 2- ENGINEER TO REVIEW NOA 02-0212.07 AND
 PROVIDE THE REQUIRED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS. THIS SYSTEM
 IS COMPLETELY DIFFERENT THAN ONE FOR
 WHICH CALCULATIONS WERE DONE. SEE PAGE 7
 OF THE NOA.
  
 3- PERMIT APPLICATION SPECIFIES THAT
 ROOF HAS "NO SLOPE PONDING WATER SPEC".
 ROOFS FOR RE-ROOFING PERMITS NEED NOT TO
 HAVE THE REQUIRED SLOPE OF 1/4 PER FOOT
 RULE, BUT ROOF MUST PROVIDEPOSITIVE
 ROOF DRAINAGE. SEE SECTION 1510.1 FBC
 2004.
  
 4- LAST PAGE OF ENGINEER REPORT IS
 LISTING ALL ZONES AS ZONE 1. WHEN DOING
 CALCULATIONS FOR CORRECT NOA (SEE ITEMS
 1 AND 2 ABOVE) MAKE SURE CORRECT ROOF
 ZONES ARE LISTED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-07-13 Cont ID  
Sent By ptjomsto Date 2006-07-13 Time 13:32 Rev Time 0.00
Received By ptjomsto Date 2006-07-13 Time 13:32 Sent To  
Notes
2006-07-13 00:00:00HISTORIC APPROVED BY JUDGE