Plan Review Details - Permit 06070722
Plan Review Stops For Permit 06070722
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-05-11 Cont ID  
Sent By mjacobs Date 2007-05-11 Time 15:09 Rev Time 0.00
Received By mjacobs Date 2007-05-11 Time 14:39 Sent To  
Notes
2007-05-11 15:09:27BUILDING PLAN REVIEW
 PERMIT: 06070722
 ADD: 2800 N. FLAGLER DR #412
 CONT: R.W.MORRELL
 TEL: (561)714-8216
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 4TH
 ACTION: PASS. HOWEVER,
  
 1)DUE TO THE FACT THAT THE ELECTRICAL REVIEWER HAS
 DENIED THE PLANS,AND A REVISED SET WILL BE REQUIRED, I
 WILL NOT APPROVED THIS SET AT THIS TIME. NOTE THE
 ELECTRICAL REVIEWER HAS RETAIN ONE OF THE SETS FOR OUR
 RECORD. SUBMIT TWO REVISED SETS OF DRAWINGS WITH THE
 CORRECT INFORMATION FOR THE ELECTRIC PORTION OF THE
 PROJECT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-20 Cont ID  
Sent By mjacobs Date 2006-12-20 Time 07:04 Rev Time 0.00
Received By mjacobs Date 2006-12-20 Time 06:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-27 Cont ID  
Sent By alange Date 2006-09-27 Time 16:30 Rev Time 0.50
Received By alange Date 2006-09-27 Time 16:30 Sent To  
Notes
2006-09-27 00:00:00DENIED
  
 1.A STATE PRODUCT APPROVAL FOR A SH
 701 WAS SUBMITTED WITH A CERTIFICATE OF
 AUTHORIZATION FOR A SH 700.
 SELECT THE DESIRED WINDOW TO BE USED AND
 SUBMIT A STATE PRODUCT APPROVAL WITH THE
 APPROPRIATE NOA.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 09:00 Rev Time 0.50
Received By alange Date 2006-07-26 Time 09:00 Sent To  
Notes
2006-07-26 00:00:00DENIED
  
 NOA'S FOR PGT SH WINDOW AND MULLIONS ARE
 EXPIRED.SUBMIT NEW UPDATED NOA'S WITH
 THE APPROPRIATE STATE PRODUCT APPROVAL.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-05-01 Cont ID  
Sent By dpalmer Date 2007-05-01 Time 12:07 Rev Time 0.00
Received By dpalmer Date 2007-05-01 Time 10:53 Sent To  
Notes
2007-05-01 12:08:16*** UNSAT 4TH REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
 AS MANY ITEMS ON PLANS HAVE BEEN REVISED FROM THE LAST
 SET OF REVIEWED PLANS THERE ARE SEVERAL NEW COMMENTS
 WHICH ARE BASED ON THE REVISIONS MADE TO PLANS WHICH
 ARE NOT THE SAME AS PREVIOUSLY SUBMITTED PLANS. PLEASE
 SEE SOME OF THE COMMENTS ARE THE SAME FROM PREVIOUS
 REVIEW. RECORD AS SHOWN.
  
  
 1) NOTE: PLEASE SEE SOME CIRCUITS ARE MISSING FROM
 PLANS AND SOME OF THE CIRCUITING ON PLANS DOES NOT
 COORDINATE WITH THE PANEL SCHEDULE SUBMITTED. PLEASE
 SEE SOME OF THE CIRCUITS ON PANEL SCHEDULE ARE
 REPEATED.
 PLEASE SEE THAT THE USE OF GEN LTS ETC MAY NOT BE USED.
 ROOMS AND AREAS ARE TO BE SPECIFIC. PLEASE SEE THE
 FOLLOWING TEXT WHICH IS EXTRACTED FROM THE CODE.
 ** CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.**
 PLEASE SEE THAT THIS CIRCUITING SHALL CORRELATE WITH
 THE SUBMITTED PANEL SCHEDULE. 408.4, 310.16
  
  
 2) NOTE:PLEASE SEE MISSING REQUIRED DEDICATED
 CIRCUITS FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM
 CIRCUITS PER 210.52B1, 210.11C1, 220.16
 THIS IS THE SAME COMMENT AS TWO SMALL APPLIANCE
 CIRCUITS ARE SHOWN HOWEVER ONLY ONE IN THE KITCHEN AND
 ONE IN THE DINING ROOM. THE KITCHEN REQUIRES TWO
 CIRCUITS AT A MINIMUM. PLEASE SEE THE DINING AREA IS
 PERMITTED TO BE ON ONE OR *MORE* OF THE SMALL APPLIANCE
 CIRCUITS.( IF MORE THAN TWO, THEN 1500VA WOULD BE
 SHOULD FOR EACH ONE OVER THE TWO MINIMUM)
  
 3) NOTE: PLEASE SEE THE MISSING EQUIPMENT GROUNDING
 CONDUCTOR FROM THE NEW J-BOX TO THE NEW PANEL. PLEASE
 ALSO NOT ON PLANS, THAT IF THE EXISTING CONDUIT FROM
 THE EXISTING METER AND MAIN DOES NOT CONTAIN AN
 EQUIPMENT GROUNDING CONDUCTOR, ONE WILL BE REQUIRED TO
 BE INSTALLED OR WORDS TO THAT EFFECT. PLEASE KNOW IF
 THE EXISTING CONDUIT GROUNDING IN THE STRUCTURE IS
 RIGID AND NOT EMT, THEN AN EXISTING PATH TO THIS J-BOX
 MAY BE ADEQUATE.
 250.24, 250.110, 250.122.
  
 4) NOTE: PLEASE CORRELATE THE ITEMS/CIRCUITS SHOWN ON
 LOAD CALCULATIONS WITH THE CIRCUITS AS SHOWN ON PANEL
 SCHEDULE.
 PLEASE SEE PANEL SCHEDULE IS MISSING THE LAUNDRY
 CIRCUIT AS SHOWN ON THE LOAD CALCULATIONS.
 PLEASE SEE THE LOAD FOR THE WATER HEATER IS SHOWN AS
 3KW ON LOAD CALCULATIONS AND THE LOAD ON THE PANEL
 SCHEDULE IS SHOWN AS 4.5 KW. PLEASE SEE THE NEXT
 COMMENT FOR WATER HEATER.
  
 5) NOTE: PLEASE SEE THE LOAD ON THE PANEL SCHEDULE AND
 LOAD CALCULATIONS BOTH WHICH ARE SHOWN AS 3KW AND 4.5KW
 EXCEED THAT OF THE CONDUCTORS, RATING OF THE BREAKER
 AND IS ONLY SHOWN AS 120V?
 PLEASE SEE 422.13 AS THE MINIMUM SIZING FOR THIS
 CIRCUIT MUST BE DONE AT 125% INCLUDING LOAD, OCP AND
 CONDUCTOR SIZES.
 PLEASE COORDINATE THE ACTUAL WATER HEATER SIZE AND GO
 FROM THERE.
  
 6) NOTE: PLEASE SEE MISSING RECEPT(S) TO BE LOCATED PER
 210.52 (SEE BEDROOM WALL)
  
 7) NOTE:THIS IS THE SAME NOTE: IF THESE ARE 110V,
 BATTERY BACK UP DEVICES WHICH ACTUALLY DETECT AND SOUND
 AN ALARM, THEN THESE ARE * SMOKE ALARMS*
 ** PREVIOUS NOTE **
 PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS 110V W/
 BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD WHICH
 MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72 DEFINITIONS AS
 A SMOKE DETECTOR IS IN FACT A DEVICE WHICH ONLY DETECTS
 AND IS PART OF A FIRE ALARM SYSTEM. IF THIS DEVICE IS
 INDEED A DEVICE WHICH DETECTS AND SOUNDS, THEN THIS
 DEVICE SHOULD BE SHOWN AND NOTED AS "SA" AS A SMOKE
 ALARM DEVICE.
 R313 2004 FBC, NFPA-72 2002 11.5, 11.8
 PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA
 THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND
 SHALL BE INDICATED AS SUCH.
  
 8) NOTE: SAME NOTE, PLEASE SEE ONLY ONE CIRCUIT IS
 BEING NOTED AS BEING AFCI PROTECTED WHEN THE SMOKE
 DEVICES ALSO REQUIRE PROTECTION.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN FOR
 RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI
 PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS.
 PLEASE LIST CIRCUITS ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM?
  
 9) NOTE:PLEASE SEE 210.4 AS THE DISHWASHER AND
 DISPOSAL ARE NOW BEING SHOWN ON THE SAME DEVICE, YET ON
 TWO DIFFERENT CIRCUITS? PLEASE SEE THE SECTION ABOVE AS
 IF BOTH ARE ON THE SAME DEVICE/YOKE, THEN THIS WOULD BE
 REQUIRED TO BE A 2-POLE BREAKER. PLEASE REVISE PANEL.
  
 10) NOTE: PLEASE SEE THE NEW BATH CIRCUIT WHICH IS
 NOTED ON PANEL SCHEDULE INDICATES A LOAD OF 5KW. PLEASE
 CLARIFY HOW THIS IS POSSIBLE?
 PLEASE ALSO SEE THIS SAME BATH CIRCUIT IS BEING NOTED
 AND SHOWN FEEDING THE LIVING ROOM RECEPTACLES WHICH IS
 NOT PERMITTED.
 PLEASE SEE 210.52D, 210.11C3 AS BATH GFI MAY NOT FEED
 OTHER AREAS, ONLY THE BATH.
  
 11) NOTE: PLEASE SEE THE OCCUPANCY IS NOTED AS
 *ANCILLARY/MAIL ROOM*?
 THE R-2 APPEARS TO BE CORRECT HOWEVER NOT SURE WHERE A
 MAIL ROOM COMES INTO AFFECT.?
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-12-17 Cont ID  
Sent By dpalmer Date 2006-12-17 Time 11:24 Rev Time 0.00
Received By dpalmer Date 2006-12-17 Time 10:53 Sent To  
Notes
2006-12-17 11:24:21*** UNSAT 3RD REVIEW***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH
 STILL NEEDS TO BE CLARIFIED OR ADDRESSED.
 THIS IS ACTUALLY THEFIRST SET OF PLANS BEING
 SUBMITTED FOR REVIEW UNDER THE THE NEW DESIGNER OF
 RECORD AS SHOWN.
  
 ** PLEASE SEE PREVIOUS REVIEWS WHICH REQUESTED PLANS
 FOR REVIEW FOR SCOPE OF WORK BEING PERFORMED. PLEASE
 SEE THE COMMENTS BELOW ARE BASED ON THE PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE PLANS MISSING CIRCUITING AS
 PREVIOUSLY REQUESTED. PLEASE SEE THAT THIS CIRCUITING
 SHALL CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 408.4, 310.16
  
 2) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED CIRCUITS
 FOR SMALL APPLIANCE CIRCUITS AND DINING ROOM CIRCUITS
 PER 210.52B1, 210.11C1, 220.16
  
 3) NOTE: PLEASE SEE EXISTING PANEL IS BEING SHOWN
 LOCATED SO THAT THE MINIMUM CLEARANCE IS NOT MET IN
 110.26. PLEASE SEE NOTE ON PLANS MENTIONS THIS IS
 EXEMPT DUE TO INSPECTOR AND IS "GRANDFATHERED" PLEASE
 KNOW MINIMUM CLEARANCES IN THE CODE HAVE GONE BACK
 FURTHER THAN WHEN THIS BUILDING WAS CONSTRUCTED AND A
 LIFE SAFETY CODE HAZARD IS NOT "GRANDFATHERED" AS
 STATED ON PLANS. PLEASE KNOW THIS LICENSED PLANS
 EXAMINER WILL NOT MAKE ANY EXCEPTION TO THIS. PLEASE
 SEE 110.26, PLEASE RELOCATE AND MEET CODE OR PROVIDE
 DOCUMENTATION TO THE INSPECTOR WHICH WILL BE REQUIRED
 TO BE THE CHIEF ELECTRICAL INSPECTOR AND THE BUILDING
 OFFICIAL FOR ANY EXCEPTIONS.
 THIS REVIEWER WILL RELEASE PROJECT AT THAT TIME IF THIS
 EXCEPTION IS GRANTED AND NEW LICENSED PLANS EXAMINER/
 INSPECTOR OR BUILDING OFFICAL WILL TAKE OVER REVIEWING
 AND SIGNING OFF OF CODE COMPLIANCE.
  
 4) NOTE: PLEASE SEE MISSING COUNTER SPACE GFI LOCATIONS
 AS REQUIRED PER 210.52C1
  
 5) NOTE: PLEASE SEE MISSING RECEPTS TO BE LOCATED PER
 210.52
  
 6) NOTE: PLEASE SEE THE SMOKE DEVICE IS BEING NOTED AS
 110V W/ BATTERY BACK UP AND PLANS INDICATE UNIT AS A SD
 WHICH MEANS SMOKE DETECTOR. PLEASE SEE NFPA-72
 DEFINITIONS AS A SMOKE DETECTOR IS IN FACT A DEVICE
 WHICH ONLY DETECTS AND IS PART OF A FIRE ALARM SYSTEM.
 IF THIS DEVICE IS INDEED A DEVICE WHICH DETECTS AND
 SOUNDS, THEN THIS DEVICE SHOULD BE SHOWN AND NOTED AS
 "SA" AS A SMOKE ALARM DEVICE.
 PLEASE KNOW THIS WAS PROVIDED TO THIS OFFICE FROM NFPA
 THAT NOTATION OF SD AND SA IS CLEARLY DIFFERENT AND
 SHALL BE INDICATED AS SUCH.
  
 7) NOTE: PLEASE SEE ARC FAULT PROTECTION IS BEING SHOWN
 FOR RECEPTS ONLY WHERE THE 2002 NEC REQUIRES AFCI
 PROTECTION FOR ALL BRANCH CIRCUITING IN SLEEPING ROOMS.
 PLEASE LIST CIRCUITS ON PANEL SCHEDULE.
 PANEL SCHEDULE SHOWS AFCI FOR BATH ROOM?
  
 8) NOTE: PLEASE SEE PLANS REFER TO A 2004 NEC. PLEASE
 KNOW AS THIS PROJECT CAME IN BEFORE THE CODE CHANGE
 THIS SHOULD BE SHOWN AS THE 2002.
 ** PLEASE KNOW THE NEXT CODE FOR THE NEC AFTER THE 2002
 WILL BE THE 2005 NEC WHICH WAS ADOPTED ON 12/8/06. THIS
 PROJECT IS UNDER THE 2002.
  
 9) NOTE: PLEASE SEE NOTICE OF COMMENCMENT STILL BEING
 SUBMITTED HAS EXPIRED AND HAS BECOME VOID . PLEASE SEE
 FLORIDA STATUTES 713.13(2). WHEN WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING SUCH NOTICE OF
 COMMENCEMENT, THE NOC SHALL BEOMCE VOID. THIS WAS
 RECORDED IN JULY OF 06, A NEW RECORDED NOC WIL BE
 REQUIRED BEFORE PICKIGN UP PERMIT.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-14 Cont ID  
Sent By dpalmer Date 2006-09-14 Time 13:04 Rev Time 0.00
Received By dpalmer Date 2006-09-14 Time 12:56 Sent To  
Notes
2006-09-14 00:00:00**** UNSAT2ND REVIEW *****
  
  
 ** PLEASE SEE COMMENTS FROM PREVIOUS
 REVIEW.
 AS REQUESTED ON PREVIOUS REVIEW , PLANS
 CAN NOT BE DONE BY A DRAFTING/ DESIGN
 CO.
 NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW.
  
  
 1) NOTE: NO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ARCHITECTURAL
 PLANS DONE BY AN ARCHITECT PER FS
 481.229.
 PLEASE SHOW CODE COMPLIANCE FOR ALL
 ELECTRCAIL IN SCOPE OF WORK. PLEASE ALSO
 SEE NFPA-72 11.5.1.1,11.8.3 FOR REQUIRED
 SD'S. R313
 PLEASE SHOW ALL ELECTRICAL DEVICES AS
 REQUIRED ALONG WTIH CIRCUITING ON PLANS.
 PLEASE CORRELATE WITH PANEL SCHEDULE (S)
 TO BE SUBMITTED. PLEASE SHOW ALL
 REQUIRED DEDICATED CIRCUITS.
  
 ** PLEASE SEE NFPA-70 2002
 210.52,210.11C1,C2,C3, 210.52C1-5,
 210.52D, 220.16, 220.31, 215.5, 240.24,
 408.16, 110.26, 210.70, 240.4,310.16 ETC
 ETC.
  
  
  
 ****NEW NOTE **
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B).
 THIS IS A NOTICE GIVEN AT THIS TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 20:00 Sent To  
Notes
2006-07-23 00:00:00**** UNSAT *****
  
 1) NOTE: PLEASE SUBMIT ARCHITECTURAL
 PLANS DONE BY AN ARCHITECT PER FS
 481.229.
 PLEASE SHOW CODE COMPLIANCE FOR ALL
 ELECTRCAIL IN SCOPE OF WORK. PLEASE ALSO
 SEE NFPA-72 11.5.1.1,11.8.3 FOR REQUIRED
 SD'S. R313
 PLEASE SHOW ALL ELECTRICLA DEVICES AS
 REQUIRED ALONG WTIH CIRCUITING ON PLANS.
 PLEASE CORRELATE WITH PANEL SCHEDULE (S)
 TO BE SUBMITTED. PLEASE SHOW ALL
 REQUIRED DEDICATED CIRCUITS.
  
 ** PLEASE SEE NFPA-70 2002
 210.52,210.11C1,C2,C3, 210.52C1-5,
 210.52D, 220.16, 220.31, 215.5, 240.24,
 408.16, 110.26, 210.70, 240.4,310.16 ETC
 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2007-05-16 Cont ID  
Sent By mwennerg Date 2007-05-16 Time 15:03 Rev Time 0.00
Received By mwennerg Date 2007-05-16 Time 15:03 Sent To  
Notes
2007-05-16 15:08:07***PROVISO***
  
 1) PLEASE NOTE THAT PLANS WERE PREVIOUSLY APPROVED AND
 STAMPED BY FIRE REVIEW. SEE ELECTRICAL COMMENTS
 REGARDING DETECTION DEVICES AND MAKE CORRECTION. PLANS
 WILL BE STAMPED WHEN RETURNED WITH APPROPRIATE
 CORRECTIONS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-22 Cont ID  
Sent By mwennerg Date 2006-12-22 Time 13:08 Rev Time 0.00
Received By mwennerg Date 2006-12-22 Time 13:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-03 Cont ID  
Sent By mawillia Date 2006-08-03 Time 10:34 Rev Time 0.00
Received By mawillia Date 2006-08-03 Time 10:34 Sent To  
Notes
2006-08-03 00:00:00***APPROVED W/PROVISO ***
  
 1.) CONSTRUCTION, ALTERATIONS, AND
 DEMOLITION TO COMPLY WITH NFPA 241.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-04-30 Cont ID  
Sent By adarroug Date 2007-04-30 Time 11:34 Rev Time 0.00
Received By adarroug Date 2007-04-30 Time 11:34 Sent To  
Notes
2007-04-30 11:34:13TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-30 Cont ID  
Sent By adarroug Date 2006-11-30 Time 16:38 Rev Time 0.00
Received By adarroug Date 2006-11-30 Time 16:38 Sent To  
Notes
2006-12-14 16:30:52TO "BOB"#9
2006-11-30 16:38:36WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-12 Cont ID  
Sent By adarroug Date 2006-09-12 Time 10:38 Rev Time 0.00
Received By adarroug Date 2006-09-12 Time 10:38 Sent To  
Notes
2006-09-13 00:00:00TO "BOB"#3
2006-09-12 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-03 Cont ID  
Sent By mawillia Date 2006-08-03 Time 10:35 Rev Time 0.00
Received By mawillia Date 2006-07-14 Time 16:04 Sent To  
Notes
2006-07-20 00:00:00TO "BOB"#9
2006-07-14 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-12-19 Cont ID  
Sent By tgordon Date 2006-12-19 Time 15:48 Rev Time 0.20
Received By tgordon Date 2006-12-19 Time 15:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-20 Cont ID  
Sent By tgordon Date 2006-07-20 Time 12:18 Rev Time 0.20
Received By tgordon Date 2006-07-20 Time 12:18 Sent To  
Notes
2006-07-20 00:00:00REPLACE EXISTING AIR HANDLER AND REPLACE
 6 FEET OF DUCT.