Plan Review Details - Permit 06070539
Plan Review Stops For Permit 06070539
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-26 Cont ID  
Sent By alange Date 2006-09-26 Time 10:13 Rev Time 0.33
Received By alange Date 2006-09-26 Time 10:13 Sent To  
Notes
2006-09-26 00:00:00ELEVATION CERTIFICATE RECEIVED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 16:30 Rev Time 0.00
Received By alange Date 2006-07-26 Time 16:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-09-17 Cont ID  
Sent By dpalmer Date 2006-09-17 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2006-09-17 Time 11:30 Sent To B
Notes
2006-09-17 00:00:00ELEVATION CERTIFICATE OK WITH
 ELECTRICAL, AS THIS IS ALSO NEEDS A
 BUILDING REVIEW, SENT TO BUILDING
 REVIEWER FOR FINAL VERIFICATION AND
 STAMPING.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 07:43 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 07:20 Sent To PC
Notes
2006-08-17 00:00:00ELEV CERTIFICATE REQUIRED BEFORE FINAL.
 MUST BE OF SLAB ELEVATION, MUST ALSO
 CONTAIN THE ORIGINAL SIGNATURE FROM THE
 PERSON SEALING THE ELEV CERTIFICATE.
 FS 472.025,

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-07 Cont ID  
Sent By dpalmer Date 2006-08-07 Time 20:20 Rev Time 0.00
Received By dpalmer Date 2006-08-07 Time 20:15 Sent To PC
Notes
2006-08-07 00:00:00***** UNSAT2ND REVIEW *****
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO NE VERIFIED ETC.
  
 1) NOTE: NO, PLEASE SEE SPECS UBMITTED
 DO NOT SEEM TO CONTAIN THE DISCONNECITNG
 MEANS AS REQUIRED. IF THIS UNIT IS ONE
 OF THE NEW ONES WHICH CONTAINS A BRKR
 FOR NORMAL SIDE AND AND ADDTIONAL BRKR
 FOR EM/GEN SIDE, PLEASE BE SURE SPECS
 CLEARLY SHOW THIS.
 PLEASE KNOW, MANY OF GENERAC'S ONLY
 DISCONNECT POWER FROM THE NORMAL SIDE.
 THE TOGGLE SWITCH LOCATED IN SOME DO NOT
 MEET CODE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY THE USE OF A SE
 RATED ATS. PLEASE SEE THE EXISTING MAIN
 FOR HOUSE IS STILL THE SERVICE MAIN.
 PLEASE SEE THAT THE ATS AS SPECIFIED
 DOES NOT DICONNECT POWER FROM GEN OR
 FEEDERS COMING FROM THE GEN AS REQUIRED
 PER 225.31-225.39.
  
 2) NOTE:NO, PLEASE SEE I COULD NOT
 LOCATE THE MIN CLEARENCE REQUIRED FOR
 THIS GEN IN THE SPECS. PLEASE KNOW, THIS
 OFFICE HAS OBTAINED LTR FROMGENERAC
 WHICH REQUIRES A MIN OF 5' FOR THIS TYOE
 OF GEN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE ALL THE SETBACKS
 AND DISTANCES AROUND GENERATOR.
 PLEASE SEE THAT THE SPECS PROVIDE
 INFORMATION ON MIN CLEARENCES.
 110.3, 90.7
  
 3) NOTE: OK.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 08:35 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 08:15 Sent To M
Notes
2006-07-21 00:00:00***** UNSAT *****
  
 1) NOTE: PLEASE CLARIFY THE USE OF A SE
 RATED ATS. PLEASE SEE THE EXISTING MAIN
 FOR HOUSE IS STILL THE SERVICE MAIN.
 PLEASE SEE THAT THE ATS AS SPECIFIED
 DOES NOT DICONNECT POWER FROM GEN OR
 FEEDERS COMING FROM THE GEN AS REQUIRED
 PER 225.31-225.39.
  
 2) NOTE: PLEASE PROVIDE ALL THE SETBACKS
 AND DISTANCES AROUND GENERATOR.
 PLEASE SEE THAT THE SPECS PROVIDE
 INFORMATION ON MIN CLEARENCES.
 110.3, 90.7
  
 3) NOTE: PLEASE KNOW, LOCATION OF JOB IS
 IN A FLOOD ZONE AND NEEDS TO SPECIFY THE
 MIN HEIGHT OF THE SLAB 6" ABOVE BFE BASE
 FLOOD ELEVATION.
 PLEASE ALSO KNOW, A "FLOOD ELEVATION
 CERTIFICATE" WILL ALSO BE REQUIRED
 BEFORE FINAL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-26 Cont ID  
Sent By mperson Date 2006-07-26 Time 15:16 Rev Time 0.15
Received By mperson Date 2006-07-26 Time 15:16 Sent To B
Notes
2006-07-26 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-09 Cont ID  
Sent By adarroug Date 2006-09-09 Time 19:04 Rev Time 0.00
Received By adarroug Date 2006-09-09 Time 19:04 Sent To E
Notes
2006-09-09 00:00:00TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 13:58 Sent To E
Notes
2006-08-15 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 11:55 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 11:54 Sent To E
Notes
2006-08-03 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-18 Cont ID  
Sent By adarroug Date 2006-07-18 Time 11:38 Rev Time 0.00
Received By adarroug Date 2006-07-18 Time 11:38 Sent To E
Notes
2006-07-18 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 16:30 Rev Time 0.00
Received By alange Date 2006-07-12 Time 16:52 Sent To  
Notes
2006-07-12 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-08-17 Cont ID  
Sent By dpalmer Date 2006-08-17 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2006-08-17 Time 07:47 Sent To  
Notes
2006-08-17 00:00:00NAT GAS GEN, HAS BEEN MOVED PER
 MANUFACTURES MIN CLEARENCE REQUIREMENTS.
 ALSO 10FT FROM ANY OPENINGS INTO
 DWELLING.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By tgordon Date 2006-07-21 Time 11:07 Rev Time 0.15
Received By tgordon Date 2006-07-21 Time 11:07 Sent To P
Notes
2006-07-21 00:00:00*** DENIED ***
 1) SEE ELECTRICAL REVIEW, PLEASE
 CORRECT.
 2) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-16 Cont ID  
Sent By mmclean Date 2006-07-16 Time 13:48 Rev Time 0.00
Received By mmclean Date 2006-07-16 Time 13:48 Sent To I
Notes
2006-07-16 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6FT FROM SIDE PROPERTY LINE.