2006-09-30 00:00:00 | ******** UNSAT 2ND REVIEW ************ |
| |
| |
| ** PLEASE SEE MOST COMMENTS FROM |
| PREVIOUS REVIEW STILL NEED TO BE |
| ADDRESSED. |
| |
| |
| 1) NOTE: NO, PLEASE SEE ONE NEW RISER IS |
| DONE NOW WHICH DOES NOT CORRELATE WITH |
| PREVIOUS PLANS. PLEASE ALSO SEE THAT THE |
| PLANS. RISER IS NOT COMPLETE WITH ALL |
| INFORMATION AS PREVIOUSLY REQUESTED. ALL |
| CONDUCTORS, ETC. |
| |
| ** PREVIOUS REIVEW NOTE ** |
| PLEASE SUBMIT COMPLETED PLANS |
| WHICH ARE DONE WITH DRAFTMAN'S QUALITY |
| WITH MIN SCALE AS REQUIRED. |
| PLEASE SEE NO ELECTRICAL RISER DIAGRAM |
| WAS SUBMITTED FOR REVIEW. |
| DRAWING SUBMITTED DOES NOT SHOW OR |
| INCLUDE CONDUCTORS, CONDUITS, MAINS, ALL |
| SIZES, DISCONNECTING MEANS REQUIRED, |
| ATS.MTS, GROUNDING, ETC ETC. |
| PLEASE SEE FBC 106.1.2, 106.1.3 AND |
| SUBMIT COMPLETE PLANS. |
| PLEASE ALSO SEE NEC 2002, |
| 250,225.31-225.39, 230.72, 702, 215.5 |
| 240.4,310.16 ETC |
| |
| 2) NOTE:NO, PLEASE SEE A MIN SLAB |
| DETAIL IS STILL NOT CLEAR OR IN PACKAGE. |
| THE ELEVATION CERTIFICATE WILL BE |
| REVIEWED. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE BLDG REVIEW |
| COMMENTS FOR MISSING SLAB DETAIL. |
| PLEASE ALSO SEE LOCATION APPEARS TO BE |
| IN A FLOOD ZONE "A".PLEASE BE SURE |
| ELEVATION OF GENERATOR IS A MIN OF 6" |
| ABOVE BFE. |
| PLEASE BE SURE SITE/SURVEY AND NEW PLANS |
| DETAIL THIS. |
| |
| 3) NOTE: NO, PLEASE KNOW, THIS VALUE IS |
| TO INCLUDE ALL EQUIPMENT, AND LABOUR AS |
| PREVIOUSLY STATED. PLEASE KNOW, BASED ON |
| THE DRAWING AND PLANS SUBMITTED AND THE |
| FAIR MARKET VALUE BASED ON THE CODE, ONE |
| WILL BE ASSESSED IF ONE IS NOT ADJUSTED. |
| VALUE WILL BE ASSESSED BASED ON |
| MARSHALL'S & SWIFT GUIDE AS ADOPTED BY |
| THE FBC. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE VALUE FOR PROJECT |
| AND SCOPE OF WORK IS REQUIRED TO INCLUDE |
| ALL LABOR AND MATERIALS EVEN IF ANY |
| EQUIPMENT IS OWNER SUPPLIED. |
| FBC 108.3 |
| PLEASE SEE VLAUE IS WAY LOW.PLEASE BE |
| SURE TO ADJUST VALUE BEFORE RESUBMITTING |
| PLANS ONCE ALL REVIEWS ARE DONE. PLEASE |
| KNOW, A VALUE BASED ON THE MARSHALL'S |
| /SWIFT GUIDE ADOPTED INTO THE FBC MAY BE |
| USED TO ASSESS A VALUE. |
| |
| 4) NOTE NO, ONLY ONE COVER SHEET FOR THE |
| GENERATOR WAS SUBMITTED. ATS? MTS? ETC. |
| 90.7, 110.3, FBC 106.1.2. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SUBMIT ALL MANUFACTURE |
| SPECS/CUT SHEETS FOR ALL EQUIPMENT. |
| PLEASE SEE MISSING SPEC FOR THE MTS/ATS. |
| |
| 5) NOTE: NO, ALL PLANS/DESIGNS DONE BY |
| THE CONTRACTOR. (DOES NOT INLCUDE |
| MANUFACTURE SHEETS). |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT ALL PLANS SHALL |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR PLANS/ |
| DESIGN. THIS IS REQUIRED FOR ALL SHEETS. |
| PLEASE SEE FBC106.1.2 OR PLEASE SEE FS |
| 481,471 IF PLANS ARE DONE BY AN |
| ARCHITECT OR ENGINEER. |
| |
| **** NEW NOTE ** |
| |
| 6) NOTE: PLEASE SEE GENERATOR AS |
| SUBMITTED IS NOT LARGE ENOUGH FOR LOADS |
| AS INDICATED. |
| PLEASE SEE RISER SHOWING 200A PANEL AND |
| PLANS SHOWING 400A'S?? |
| PLEASE SEE ALL ABOVE NOTES AND SUBMIT |
| PLANS FOR CODE COMPLIANCE BASED ON THE |
| 2002 NEC, 2002 NFPA-110 FOR SIZING, |
| LOADS ETC. |
| |
| 7) NOTE; PLEASE SEE FS 553.80(2)(B) WITH |
| RESPECT TO DESIGN PROFESSIONALS AND |
| REPEAT COMMENTS FOR CODE COMPLIANCE 3 OR |
| MORE TIMES. |
| PLEASE BE SURE TO ADDRESS ALL COMMENTS. |
| |
| 8) NOTE: PLEASE SEE NOTICE OF |
| COMMENCMENT SUBMITTED IS NOT RECORDED AS |
| REQUIRED PER FS 713.13(2). |
| PLEASE KNOW, THIS WILL BE REQUIRED |
| BEFORE PICKING UP PERMIT. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |