Plan Review Details - Permit 06070497
Plan Review Stops For Permit 06070497
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By mjacobs Date 2006-11-02 Time 15:43 Rev Time 0.00
Received By mjacobs Date 2006-11-02 Time 12:47 Sent To PC
Notes
2006-11-02 15:40:03 
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 4)1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING.
 STRUCTURAL MEMBERS AND SYSTEMS AND COMPONENTS AND
 CLADDING IN A BUILDING OR STRUCTURE SHALL BE ANCHORED
 TO RESIST WIND-INDUCED OVERTURNING, UPLIFT AND SLIDING
 AND TO PROVIDE CONTINUOUS LOAD PATHS FOR THESE FORCES
 TO THE FOUNDATION. WHERE A PORTION OF THE RESISTANCE TO
 THESE FORCES IS PROVIDED BY DEAD LOAD, THE DEAD LOAD,
 INCLUDING THE WEIGHT OF SOILS AND FOUNDATIONS, SHALL BE
 TAKEN AS THE MINIMUM DEAD LOAD LIKELY TO BE IN PLACE
 DURING A DESIGN WIND EVENT. WHERE THE ALTERNATE BASIC
 LOAD COMBINATIONS OF SECTION 1605.3.2 ARE USED, ONLY
 TWO-THIRDS OF THE MINIMUM DEAD LOAD LIKELY TO BE IN
 PLACE DURING A DESIGN WIND EVENT SHALL BE USED. NOTE:
 AN ENGINEER OR ARCHITECT WHO IS REGISTERED WITH THE
 STATE WILL HAVE TO PROVIDE THIS INFORMATION ON THE
 DRAWINGS. SEE F.A.C. 61G15-23.002 - 471.025 F.S. AND
 SEC. 106 F.B.C.
  
 5) THE SLAB DETAIL IS STILL MISSING FROM THE DRAWINGS.
 THE SCALE NOTED ON THEDRAWINGS IS INCORRECT. INDICATE
 THE CORRECT SCALE FOR THE DRAWINGS 106.1.3 FBC*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By mjacobs Date 2006-08-01 Time 09:06 Rev Time 0.00
Received By mjacobs Date 2006-08-01 Time 08:18 Sent To  
Notes
2006-08-01 00:00:00 
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) WPB AMEND:106.1.3 . QUALITY OF
 BUILDING PLANS. BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICIAL
 MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
 3) THE FLOOD ZONE IN THE AREA IS "AE"
 ZONE. PROVIDE THE ELEVATION CERTIFICATE
 INDICATING THAT THE GENERATOR AND ALL
 OTHER EQUIPMENT WILL BE AT LEAST SIX
 INCHES ABOVE THE BASE FLOOD ELEVATION.
  
 4) SUBMIT TWO COPIES OF THE DETAILS FOR
 SLAB AND/OR TIEDOWN CONNECTIONS.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-30 Cont ID  
Sent By dpalmer Date 2006-09-30 Time 16:25 Rev Time 0.00
Received By dpalmer Date 2006-09-30 Time 15:27 Sent To  
Notes
2006-09-30 00:00:00******** UNSAT 2ND REVIEW ************
  
  
 ** PLEASE SEE MOST COMMENTS FROM
 PREVIOUS REVIEW STILL NEED TO BE
 ADDRESSED.
  
  
 1) NOTE: NO, PLEASE SEE ONE NEW RISER IS
 DONE NOW WHICH DOES NOT CORRELATE WITH
 PREVIOUS PLANS. PLEASE ALSO SEE THAT THE
 PLANS. RISER IS NOT COMPLETE WITH ALL
 INFORMATION AS PREVIOUSLY REQUESTED. ALL
 CONDUCTORS, ETC.
  
 ** PREVIOUS REIVEW NOTE **
 PLEASE SUBMIT COMPLETED PLANS
 WHICH ARE DONE WITH DRAFTMAN'S QUALITY
 WITH MIN SCALE AS REQUIRED.
 PLEASE SEE NO ELECTRICAL RISER DIAGRAM
 WAS SUBMITTED FOR REVIEW.
 DRAWING SUBMITTED DOES NOT SHOW OR
 INCLUDE CONDUCTORS, CONDUITS, MAINS, ALL
 SIZES, DISCONNECTING MEANS REQUIRED,
 ATS.MTS, GROUNDING, ETC ETC.
 PLEASE SEE FBC 106.1.2, 106.1.3 AND
 SUBMIT COMPLETE PLANS.
 PLEASE ALSO SEE NEC 2002,
 250,225.31-225.39, 230.72, 702, 215.5
 240.4,310.16 ETC
  
 2) NOTE:NO, PLEASE SEE A MIN SLAB
 DETAIL IS STILL NOT CLEAR OR IN PACKAGE.
 THE ELEVATION CERTIFICATE WILL BE
 REVIEWED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE BLDG REVIEW
 COMMENTS FOR MISSING SLAB DETAIL.
 PLEASE ALSO SEE LOCATION APPEARS TO BE
 IN A FLOOD ZONE "A".PLEASE BE SURE
 ELEVATION OF GENERATOR IS A MIN OF 6"
 ABOVE BFE.
 PLEASE BE SURE SITE/SURVEY AND NEW PLANS
 DETAIL THIS.
  
 3) NOTE: NO, PLEASE KNOW, THIS VALUE IS
 TO INCLUDE ALL EQUIPMENT, AND LABOUR AS
 PREVIOUSLY STATED. PLEASE KNOW, BASED ON
 THE DRAWING AND PLANS SUBMITTED AND THE
 FAIR MARKET VALUE BASED ON THE CODE, ONE
 WILL BE ASSESSED IF ONE IS NOT ADJUSTED.
 VALUE WILL BE ASSESSED BASED ON
 MARSHALL'S & SWIFT GUIDE AS ADOPTED BY
 THE FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR PROJECT
 AND SCOPE OF WORK IS REQUIRED TO INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE VLAUE IS WAY LOW.PLEASE BE
 SURE TO ADJUST VALUE BEFORE RESUBMITTING
 PLANS ONCE ALL REVIEWS ARE DONE. PLEASE
 KNOW, A VALUE BASED ON THE MARSHALL'S
 /SWIFT GUIDE ADOPTED INTO THE FBC MAY BE
 USED TO ASSESS A VALUE.
  
 4) NOTE NO, ONLY ONE COVER SHEET FOR THE
 GENERATOR WAS SUBMITTED. ATS? MTS? ETC.
 90.7, 110.3, FBC 106.1.2.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR ALL EQUIPMENT.
 PLEASE SEE MISSING SPEC FOR THE MTS/ATS.
  
 5) NOTE: NO, ALL PLANS/DESIGNS DONE BY
 THE CONTRACTOR. (DOES NOT INLCUDE
 MANUFACTURE SHEETS).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS/
 DESIGN. THIS IS REQUIRED FOR ALL SHEETS.
 PLEASE SEE FBC106.1.2 OR PLEASE SEE FS
 481,471 IF PLANS ARE DONE BY AN
 ARCHITECT OR ENGINEER.
  
 **** NEW NOTE **
  
 6) NOTE: PLEASE SEE GENERATOR AS
 SUBMITTED IS NOT LARGE ENOUGH FOR LOADS
 AS INDICATED.
 PLEASE SEE RISER SHOWING 200A PANEL AND
 PLANS SHOWING 400A'S??
 PLEASE SEE ALL ABOVE NOTES AND SUBMIT
 PLANS FOR CODE COMPLIANCE BASED ON THE
 2002 NEC, 2002 NFPA-110 FOR SIZING,
 LOADS ETC.
  
 7) NOTE; PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS FOR CODE COMPLIANCE 3 OR
 MORE TIMES.
 PLEASE BE SURE TO ADDRESS ALL COMMENTS.
  
 8) NOTE: PLEASE SEE NOTICE OF
 COMMENCMENT SUBMITTED IS NOT RECORDED AS
 REQUIRED PER FS 713.13(2).
 PLEASE KNOW, THIS WILL BE REQUIRED
 BEFORE PICKING UP PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-30 Cont ID  
Sent By dpalmer Date 2006-07-30 Time 18:52 Rev Time 0.00
Received By dpalmer Date 2006-07-30 Time 18:36 Sent To  
Notes
2006-07-30 00:00:00******** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT COMPLETED PLANS
 WHICH ARE DONE WITH DRAFTMAN'S QUALITY
 WITH MIN SCALE AS REQUIRED.
 PLEASE SEE NO ELECTRICAL RISER DIAGRAM
 WAS SUBMITTED FOR REVIEW.
 DRAWING SUBMITTED DOES NOT SHOW OR
 INCLUDE CONDUCTORS, CONDUITS, MAINS, ALL
 SIZES, DISCONNECTING MEANS REQUIRED,
 ATS.MTS, GROUNDING, ETC ETC.
 PLEASE SEE FBC 106.1.2, 106.1.3 AND
 SUBMIT COMPLETE PLANS.
 PLEASE ALSO SEE NEC 2002,
 250,225.31-225.39, 230.72, 702, 215.5
 240.4,310.16 ETC
  
 2) NOTE:PLEASE SEE BLDG REVIEW
 COMMENTS FOR MISSING SLAB DETAIL.
 PLEASE ALSO SEE LOCATION APPEARS TO BE
 IN A FLOOD ZONE "A".PLEASE BE SURE
 ELEVATION OF GENERATOR IS A MIN OF 6"
 ABOVE BFE.
 PLEASE BE SURE SITE/SURVEY AND NEW PLANS
 DETAIL THIS.
  
 3) NOTE: PLEASE SEE VALUE FOR PROJECT
 AND SCOPE OF WORK IS REQUIRED TO INCLUDE
 ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
 PLEASE SEE VLAUE IS WAY LOW.PLEASE BE
 SURE TO ADJUST VALUE BEFORE RESUBMITTING
 PLANS ONCE ALL REVIEWS ARE DONE. PLEASE
 KNOW, A VALUE BASED ON THE MARSHALL'S
 /SWIFT GUIDE ADOPTED INTO THE FBC MAY BE
 USED TO ASSESS A VALUE.
  
 4) NOTE: PLEASE SUBMIT ALL MANUFACTURE
 SPECS/CUT SHEETS FOR ALL EQUIPMENT.
 PLEASE SEE MISSING SPEC FOR THE MTS/ATS.
  
 5) NOTE: PLEASE SEE THAT ALL PLANS SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS/
 DESIGN. THIS IS REQUIRED FOR ALL SHEETS.
 PLEASE SEE FBC106.1.2 OR PLEASE SEE FS
 481,471 IF PLANS ARE DONE BY AN
 ARCHITECT OR ENGINEER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-11-02 Cont ID  
Sent By mawillia Date 2006-11-02 Time 11:01 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 11:01 Sent To  
Notes
2006-11-02 11:09:05*****INCOMPLETE*****
  
  
  
  
 1.PLEASE ACKNOWLEDGE AS STATED IN PREVIOUS FIRE PLAN
 REVIEW,THAT WORK SHALL COMPLY WITH NFPA 110, STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS.
  
  
  
  
 ** TO EXPEDITE PLAN REVIEW, INCLUDE A RESPONSE LETTER
 INDICATING HOW EACH ITEM WAS ADDRESSED WHEN
 RESUBMITTING**
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 10:12 Rev Time 0.00
Received By mwennerg Date 2006-09-05 Time 10:12 Sent To  
Notes
2006-09-05 00:00:00***DENIED***
  
 1) PLEASE SUBMIT MANUFACTURER SPEC
 SHEETS FOR GENERATOR AND ASSOCIATED
 EQUIPMENT.
  
 2) WORK SHALL COMPLY WITH NFPA 110,
 STANDARD FOR EMERGENCY AND STANDBY POWER
 SYSTEMS.
  
 3) PLEASE ILLUSTRATE ALL LOCATIONS OF
 GENERATOR AND EQUIPMENT RELATIVE TO
 BUILDING OPENINGS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2006-10-17 Cont ID  
Sent By kstevens Date 2006-10-17 Time 10:36 Rev Time 0.00
Received By kstevens Date 2006-10-17 Time 10:36 Sent To  
Notes
2006-10-17 10:37:10SEPARATE GAS PLANS AND PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By kstevens Date 2006-08-10 Time 06:06 Rev Time 0.00
Received By kstevens Date 2006-08-10 Time 06:06 Sent To  
Notes
2006-08-10 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED.
 APPLICATION SHALL BE SUBMITTED WITH
 GEN-COM PACKAGE. THE FOLLOWING
 INFORMATION IS REQUIRED FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, NATURAL IS INDICATED ON
 MANUF. SHEET, BUT SHALL BE INDICATED ON
 ISOMETRIC ALSO.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. N/A
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. THIS
 SHALL INCLUDE INSTALLATION INSTRUCTIONS
 TO DETERMINE MINIMUM DISTANCE FROM ALL
 STRUCTURES/WALLS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-15 Cont ID  
Sent By adarroug Date 2006-09-15 Time 13:21 Rev Time 0.00
Received By adarroug Date 2006-09-15 Time 13:21 Sent To  
Notes
2006-09-30 00:00:00TO COMM BOARD #33
2006-09-15 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-09-05 Cont ID  
Sent By mwennerg Date 2006-09-05 Time 10:17 Rev Time 0.00
Received By mwennerg Date 2006-07-12 Time 14:27 Sent To  
Notes
2006-07-28 00:00:00TO COMM BOARD #42
2006-07-12 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 06:57 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 06:54 Sent To  
Notes
2006-08-21 00:00:00NATURAL GAS GENERATOR / PLEASE NOTE,
 SITE PLANS SHOULD INDICATE CLEARANCES
 FROM PROPERTY LINES, BUILDINGS, FENCES,
 FRESH AIR INTAKES, WINDOWS, DOORS, ETC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-10-24 Cont ID  
Sent By mmclean Date 2006-10-24 Time 15:38 Rev Time 0.00
Received By mmclean Date 2006-10-24 Time 15:38 Sent To  
Notes
2006-10-24 17:02:13DENIED,
 1. THE SURVEY SUBMITTED SHOWS THE LOCATION OF THE
 PROPOSED GENERATOR LOCATED IN A PAVED AREA.
 2. PLEASE INDICATE IF THE LOCATION OF THE PROPOSED
 GENERATOR WILL BE TAKEN ANY REQUIRED PARKING SPACE.
 3. PLEASE PROVIDE COUNT OF THE APPROVED PARKING AND
 PROVIDE THE PLANS SHOWING THE LAYOUT OF PARKING.
  
 NOTE: GENERATOR MUST BE SCREENED.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By mmclean Date 2006-08-01 Time 17:05 Rev Time 0.00
Received By mmclean Date 2006-08-01 Time 17:05 Sent To I
Notes
2006-08-01 00:00:00DENIED,
 1. THE PROPOSED GENERATOR MUST BE SHOWN
 ON TWO COPY OF CURRENT SURVEY WITH
 SETBACKS.
 2. THE SURVEY PROVIDED IS NOT LEDGERBLE
 TO READ AND DOES NOT SHOW THE STRUCTURE
 ON THE PROPERTY WITH SETBACKS.
 3.SEC 94-444(B) - SCREENING SHALL BE
 CONSTRUCTED OF BRICK DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY AND
 WALLS SHALL BE LANDSCAPE WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.
 4. CITY OF WEST PALM - AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION: BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER
 ACCEPTABLE MEDIUM. THE BUILDING OFFICAL
 MAY ESTABLISH THROUGH DEPARTMENTAL
 POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROIVDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM.THIS POLICY MAY INCLUDE SUCH
 THINDS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
 NOTE:
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN