Plan Review Details - Permit 06070197
Plan Review Stops For Permit 06070197
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2007-01-02 Cont ID  
Sent By swurafti Date 2007-01-02 Time 12:07 Rev Time 0.00
Received By swurafti Date 2007-01-02 Time 12:07 Sent To  
Notes
2007-01-02 12:11:06GAVE ADDRESS A PCN # AFTER PROOF OF UNITY TITLE FOR
 BOTH BAYS PER LILI & RBROWN

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2006-12-12 Cont ID  
Sent By lursu Date 2006-12-12 Time 09:07 Rev Time 0.00
Received By lursu Date 2006-12-12 Time 09:07 Sent To  
Notes
2006-12-12 09:07:30UNITY OF TITLE IS REQUIRED IF THE BAYS ARE COMBINED.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By lursu Date 2006-07-19 Time 11:43 Rev Time 0.00
Received By lursu Date 2006-07-19 Time 11:43 Sent To  
Notes
2006-07-19 00:00:00CREATE TEMPORARY PCN FOR THIS TWO BAYS
 231 & 232 UNDER THE ADDRESS OF 5403 N
 HAVERHILL RD.PCN =
 TEMP7442430208A31.PERMIT MUST BE
 ATTACHED TO THIS PCN.
2006-07-18 00:00:00NEEDS BAY #'S EXT?

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2006-12-13 Cont ID  
Sent By jwitmer Date 2006-12-13 Time 16:43 Rev Time 1.33
Received By jwitmer Date 2006-12-13 Time 16:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2006-11-02 Cont ID  
Sent By jwitmer Date 2006-11-02 Time 12:24 Rev Time 2.22
Received By jwitmer Date 2006-11-02 Time 12:24 Sent To PC
Notes
2006-11-02 12:35:41BUILDING PLAN REVIEW
 PERMIT: 06070197
 ADD: 5403 N HAVERHILL RD
 SUITE 31& 32
 CONT:PRIME MECHANICAL SERVICES
 TEL: (954)444-6823
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RD REVIEW
 ACTION: DENIED
  
 --- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 PLEASE TAKE TIME TO READ!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & "REMOVE ALL VOID SHEETS" & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)THIRDREQUEST, THIS REQUEST WASN'T
 EVEN LISTED ON THE RESPONSE SHEET,
 ADDITIONAL INFORMATION REQUIRED
 106.1.2*THERE IS NO INFORMATION AS HOW
 THE FREEZERS CEILING WILL BE FRAMED OR
 HOW IT WILL STAY IN PLACE? WILL IT BE
 ABLE TO TAKE ANY LOADING?
  
 2) 2ND REQUEST! THIS PROJECT IS A
 CONDOMINIUM REQUIRING A UNITY OF TITLE
 FOR THE 2 UNITS. SEE PLANNING & ZONING
 FOR THE REQUIRED PAPERWORK AND
 APPROVALS. TABLE 601 ISSUES.) THE PROPOSED BUILDING
 STRUCTURE
 TRANSGRESSES LEGAL BOUNDARY LINES
 BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'.A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE.
 SUBMIT A COPY OF THE RECORDED 'UNITY OF
 OF TITLE' DOCUMENT SO THAT FBC TABLE 601
 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED
 NOT APPLICABLE.
  
  
 3)!!!!!!!!!FEES DUE!!!!!!!!!!!!!!!!
 THIRDREQUEST, REVIEWS ARE NOT TO TAKE
 PLACE WHEN FEES ARE DUE!!!!!!!! FEES DUE
 TO ADDITION OF FIRE REVIEW
 10% OF PERMIT FEE. A "HOLD" IS PUT
 ON THIS PERMIT THAT THE PERMIT FEE IS TO BE
 PAYED IN FULLBEFORE THE PERMIT MAY
 BE RESUBMITTED. A 10% SURCHARGE WILL ALSO
 BE ASSESSED AND PAID BEFORE THE
 THIRD REVIEW MAY COMMENCE.
 FBC 108.1 PRESCRIBED FEES* 108.2*.
  
 4) EVALUATION IS LOW, IF THE CORRECT
 CONTRACT VALUE AND ASSOCIATED FEES ARE
 NOT UPDATED, FEES PAID BEFORE THE NEXT
 REVIEW WE WILL ASSESS THE CORRECT FEES
 AND FEES USING MARSHALL & SWIFT TO
 CALCULATE THE VALUES.
 108.1* ADMINISTRATIVE CODE.
  
 5)A NEW NOTICE OF COMMENCEMENT WILL BE REQUIRED,
 THE RECORDED NOTICE OF COMMENCEMENT DOESN'T INDICATE
 THE PRIME MECHANICAL CONTRACTOR.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
  
  
  
  
  
  
  
  
  
  
  
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-15 Cont ID  
Sent By jwitmer Date 2006-09-15 Time 07:30 Rev Time 0.55
Received By jwitmer Date 2006-09-15 Time 07:30 Sent To  
Notes
2006-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070197
 ADD: 5403 N HAVERHILL RD
 SUITE 31& 32
 CONT:PRIME MECHANICAL SERVICES
 TEL: (954)444-6823
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)SECOND REQUEST, THIS REQUEST WASN'T
 EVEN LISTED ON THE RESPONSE SHEET,
 ADDITIONAL INFORMATION REQUIRED
 106.1.2*THERE IS NO INFORMATION AS HOW
 THE FREEZERS CEILING WILL BE FRAMED OR
 HOW IT WILL STAY IN PLACE? WILL IT BE
 ABLE TO TAKE ANY LOADING?
  
 2) NEW COMMENT! THIS PROJECT IS A
 CONDOMINIUM REQUIRING A UNITY OF TITLE
 FOR THE 2 UNITS. SEE PLANNING & ZONING
 FOR THE REQUIRED PAPERWORK AND
 APPROVALS.
  
  
 3)!!!!!!!!!FEES DUE!!!!!!!!!!!!!!!!
 SECOND REQUEST, REVIEWS ARE NOT TO TAKE
 PLACE WHEN FEES ARE DUE!!!!!!!! FEES DUE
 TO ADDITION OF FIRE REVIEW
 10% OF PERMIT FEE.
  
 4) EVALUATION IS LOW, IF THE CORRECT
 CONTRACT VALUE AND ASSOCIATED FEES ARE
 NOT UPDATED, FEES PAID BEFORE THE NEXT
 REVIEW WE WILL ASSESS THE CORRECT FEES
 AND FEES USING MARSHALL & SWIFT TO
 CALCULATE THE VALUES.
 108.1* ADMINISTRATIVE CODE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-01 Cont ID  
Sent By jwitmer Date 2006-08-01 Time 12:02 Rev Time 1.55
Received By jwitmer Date 2006-08-01 Time 12:02 Sent To PC
Notes
2006-08-01 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070197
 ADD: 5403 N HAVERHILL RD UNIT 31/32
 CONT: PRIME MECHANICAL SERVICES
 TEL: (954)444-6823
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE LISTING REPORT
 WHICH PROVIDES THE DATA MEETING THE
 REQUIREMENTS OF 2603.4.1.2 COOLER AND
 FREEZER WALLS.
  
 2) PLEASE PROVIDE THE FIRE SPRINKLER
 PLANS AS REQUIRED BY 2603.4.1.2(4)BE
 PROTECTED BY AN AUTOMATIC SPRINKLER
 SYSTEM. WHERE THE COOLER OR FREEZER IS
 WITHIN A BUILDING, BOTH THE COOLER OR
 FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE
 SPRINKLERED. PROVIDE THE DETAILS HOW THE
 FIRE SPRINKLER HEADS WILL TRANSITION
 INTO THE FREEZER AND WALK IN COOLER.
  
 3) ADDITIONAL INFORMATION REQUIRED
 106.1.2*THERE IS NO INFORMATION AS HOW
 THE FREEZERS CEILING WILL BE FRAMED OR
 HOW IT WILL STAY IN PLACE? WILL IT BE
 ABLE TO TAKE ANY LOADING?
  
 4) FEES DUE TO ADDITION OF FIRE REVIEW
 10% OF PERMIT FEE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-06-28 Cont ID  
Sent By dpalmer Date 2007-06-28 Time 08:49 Rev Time 0.00
Received By dpalmer Date 2007-06-27 Time 20:12 Sent To  
Notes
2007-06-28 08:51:45 
 2007-06-28 08:51:45
 OK, STAMPED, LETTERS ON FILE.
2007-06-27 20:17:242007-06-27 20:17:24
 ON HOLD IN ELECTRICAL. CALLED KIM LIDDELL AND LEFT
 MESSAGE FOR LETTERS FROM THE DESIGNERS OF RECORD TAKING
 OVER PROJECT AND OWNER RELEASING PREVIOUS DESIGN TEAM.

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2007-04-04 Cont ID  
Sent By dpalmer Date 2007-04-04 Time 13:38 Rev Time 0.00
Received By dpalmer Date 2007-04-04 Time 13:38 Sent To PC
Notes
2007-04-04 13:47:59** UNSAT **
  
 1) NOTE: PLEASE SEE THAT ANY CHANGES TO LIGHTING ON
 PLANS MUST BE DONE BY THE ENGINEER OF RECORD.
 NO HAND-DRAWN CHANGES ARE PERMITTED.
 FS 471.025
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCK
 FOR THE ARCHITECTURAL FIRM AND PRINTED NAME AND LICENSE
 NUMBER FOR THE NEW ARCHITECT OF RECORD.
 PLEASE SEE FAC 61G1-16.004 AND FS 481.219.
 THIS COMMENT IS NOT FOR THE ENGINEERING FIRM.
  
 3) NOTE:PLEASE BE SURE THAT COMPLETE PLANS REVISING
 THE COMPLETED SETS OFPLANS FROM THE NEW DESIGN TEAM
 WILL BE REQUIRED TO BE SUBMITTED. MAY NOT HAVE SOME
 SHEETS FROM ONE DESIGN TEAM AND ONE SHEET OR OTHER
 SCOPE FROM ANOTHER DEISGN TEAM.
 FS 481/471
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-12-09 Cont ID  
Sent By dpalmer Date 2006-12-09 Time 17:12 Rev Time 0.00
Received By dpalmer Date 2006-12-09 Time 17:07 Sent To I
Notes
2006-12-09 17:13:17ELEC OK, STAMPED REVISEED SHEET.
 PLANS ROUTED BACK TO INCOMING.
2006-12-09 17:08:30PLANS REMOVED FROM INCOMING, PLANS WILL BE ROUTED BACK
 TO INCOMING WAITING FOR THE COMM BOB BOARD.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 20:58 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 20:48 Sent To  
Notes
2006-10-27 20:58:47*** UNSAT ****
  
  
 1) NOTE: PLEASE SEE ATTACHEDAND LOOSE SHEETS ATTACHED
 TO PLANS WHICH ARE DONE BY AN ENGINEER OR ARCHITECT IS
 NOTACCEPTABLE.
 PLEASE SEE SHEET E-3.01 HAS NOW BEEN VOIDED.
 PLEASE SEE PREVIOUS NOTES, OCCUPANCY SENSOR
 TYPE/AUTOMATIC DEVICES REQUIRED.
  
  
 ** PLEASE BE SURE THE VOIDED SHEETS ARE COMPLETELY
 REMOVED AND NEW SHEETS ARE INSERTED . DO NOT PLACE
 SHEETS IN SETS DONE BY CONTRACTOR AS THIS IS NOT UNDER
 THEIR SCOPE PERMITTED.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By dpalmer Date 2006-09-08 Time 18:32 Rev Time 0.00
Received By dpalmer Date 2006-09-08 Time 18:15 Sent To  
Notes
2006-09-08 00:00:00*** NOTES REDLINED ON PLANS ***
  
 1) NOTE: PLEASE SEE NFPA-101 7.9.2.2, IF
 AREA IN COOLER IS BEING LEFT IN TOTAL
 DARKNESS UPON THE TURNING OFF OF THE
 SWITHCES AS SHOWN, AN OCCUPANCY SENSOR
 OF SOME TYPE WILL BE REQUIRD INSIDE
 COOLER UNIT TO OVER RIDE LTS. THIS WILL
 ALLEAVIATE LEAVING AN OCCUPANT IN TOTAL
 DARKNESS FOR EGRESS IN THE EVENT THE
 SWITCHES BECOME ACCIDENTLY SWITCHED OFF.
 ** THE SIZE AND TRAVEL DISTANCE IN THIS
 COOLER IS SUBSTANTIAL AND WILL ALSO BE
 REQUIRED BY THE FIRE MARSHAL'S OFFICE.
  
 IF THERE ARE ANY QUESIONS, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 VALUE FOR SCOPE PF WORK IS STILL IN NEED
 OF ADJUSTMENT TO INCLUDE ALL
 ELECTRICAL,MECHANICAL EQUIPMENT AND NEW
 COOLER.
 THE ELECTRICAL STATUS SHALL REMAIN IN
 "F" STATUES UNTIL ADJUSTMENT IS MADE. IF
 ONE IS NOT ADJUSTED BY CONTRACTOR, ONE
 WILL BE ADJUSTED PER MARSHAL'S & SWIFT
 GUIDES AS ADOPTED BY THE FBC 108.3

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By dpalmer Date 2006-07-18 Time 20:14 Rev Time 0.00
Received By dpalmer Date 2006-07-18 Time 19:13 Sent To  
Notes
2006-07-18 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SEE THE LIGHTING LAYOUT
 WHICH WAS PROVIDED SEPARATELY NEEDS TO
 CONTAIN CIRCUITING, CONTROLS AND
 CORRELATE WITH THE SUBMITTED PANEL
 SCHEDULE ON PLANS. IN FACT THE
 ELECTRICLA LAYOUT SHOWN FOR COOLER
 SHOULD BE PROVIDED BY THE DESIGN
 PROFESSIONAL WHICH HAD DRAWN THE PLANS
 FOR THE INSTALLATION OF COOLER AND ALL
 OTHER ELECTRICAL WORK IN THIS SCOPE PF
 WORK FOR THIS PERMIT FOR SPACE.
 PLEASE KNOW, AS SCOPE OF WORK IS
 PERMITTED AND DONE UNDER THE SAME
 PERMIT. ONE DESIGN PROFESSIONAL SHOULD
 BE RESPOSIBLE FOR DESIGN AND
 CONNECTIONS, ETC ARE COMBINED.
 106.1.2 ADMIN SECT. PLEASE BE SURE TO
 SEE 700.12E FOR CIRCUITIGN OF EM/EXT LTS
 TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 ANY ONE AREA. PLEASE KNOW, FAILURE OF
 ONE OCP, CIRCUIT SHOULD NOT LEAVE IN ONE
 AREA IN TOTAL DARKNESS.
 LS 101 7.8, 7.9
  
 2) NOTE: PLEASE SEE RESPONSE LTR FROM
 ARCHITECT'S OFFICE MENTIONS THE 2000 LS
 CODE. PLEASE KNOW, WE ARE CURRENTLY
 UNDER THE 2003 101.
  
 3) NOTE: PLEASE SEE THAT THE SPECS ON EM
 LTS ARE OK, HOWEVERTHERE IS A QUESTION
 ON THE EM/EXT COMBO UNITWHERE THE
 LISTING FOR THIS FIXTURE PERMITS THE
 INSTALLATION IN THE COOLER/DAMP/POSSIBLE
 WET LOCATION.? COULD NOT LOCATE ANY
 INFORMATION ON SPECS SUBMITTED WHICH
 LENDS TO THIS?
 PLEASE ALSO SEE THE UNIT IS SHOWN AS A
 COMBO UNIT WHICH IS FINE, HOWEVER PLANS
 SHOULD INDICATE THIS.
 110.3, FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE KNOW, IF ALL OTHER
 ELECTRICAL MECHANICAL WORK IS INLCUDED
 IN THE PERMIT/SCOPE, THEN PLEASE KNOW,
 VALUATION FOR PERMIT SHALL INCLUDE ALL
 LABOR AND MATERIALS WHETHER OR NOT ANY
 OF THE EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
  
 THE EXTENSIVE RESPONSE LTR IS
 APPRECIATED FOR CLARIFICATION OF OTHER
 ITEMS.
  
 IF THERE ARE ANY QUESTIONS ON NOTE #1,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT THE ELECTRICAL PLANS, DESIGN ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2007-06-28 Cont ID  
Sent By mwennerg Date 2007-06-28 Time 10:15 Rev Time 0.00
Received By mwennerg Date 2007-06-28 Time 10:15 Sent To  
Notes
2007-06-28 10:16:23REVISION DATED 5/22/07

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2006-12-22 Cont ID  
Sent By mwennerg Date 2006-12-22 Time 12:55 Rev Time 0.00
Received By mwennerg Date 2006-12-22 Time 12:55 Sent To  
Notes
2006-12-22 12:56:04PLANS APPROVED AND STAMPED ON 9/19/06

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-10-30 Cont ID  
Sent By mawillia Date 2006-10-30 Time 09:33 Rev Time 0.00
Received By mawillia Date 2006-10-30 Time 09:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-19 Cont ID  
Sent By mwennerg Date 2006-09-19 Time 09:28 Rev Time 0.00
Received By mwennerg Date 2006-09-19 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-19 Cont ID  
Sent By mwennerg Date 2006-07-19 Time 15:05 Rev Time 0.00
Received By mwennerg Date 2006-07-19 Time 15:05 Sent To  
Notes
2006-07-19 00:00:00***PROVISO***
  
 1) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 2) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-06-25 Cont ID  
Sent By adarroug Date 2007-06-25 Time 12:47 Rev Time 0.00
Received By adarroug Date 2007-06-25 Time 12:47 Sent To  
Notes
2007-06-26 11:19:15TO "BOB"#2
2007-06-25 12:48:09WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:32 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:32 Sent To E
Notes
2007-03-30 17:32:31TO DEWEY PALMER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-29 Cont ID  
Sent By spalmer Date 2006-11-29 Time 18:42 Rev Time 0.00
Received By spalmer Date 2006-11-29 Time 18:42 Sent To  
Notes
2006-12-12 17:38:35TO "BOB"#11
2006-11-29 18:42:23WAITING FOR "BOB" BOARD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-23 Cont ID  
Sent By adarroug Date 2006-10-23 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-10-23 Time 11:31 Sent To  
Notes
2006-10-27 15:45:28TO "BOB"#18
2006-10-23 11:32:05WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-06 Cont ID  
Sent By adarroug Date 2006-09-06 Time 16:34 Rev Time 0.00
Received By adarroug Date 2006-09-06 Time 16:34 Sent To  
Notes
2006-09-08 00:00:00TO "BOB"#15
2006-09-06 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-01 Cont ID  
Sent By jwitmer Date 2006-08-01 Time 12:37 Rev Time 0.00
Received By jwitmer Date 2006-07-10 Time 09:46 Sent To  
Notes
2006-07-13 00:00:00TO "BOB"#8
2006-07-10 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-06-29 Cont ID  
Sent By tgordon Date 2007-06-29 Time 11:38 Rev Time 0.30
Received By tgordon Date 2007-06-29 Time 11:38 Sent To  
Notes
2007-06-29 11:39:26REVISION TO PLANS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-11 Cont ID  
Sent By tgordon Date 2006-09-11 Time 15:34 Rev Time 0.25
Received By tgordon Date 2006-09-11 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By tgordon Date 2006-07-14 Time 14:33 Rev Time 0.45
Received By tgordon Date 2006-07-14 Time 14:33 Sent To  
Notes
2006-07-14 00:00:00*** DENIED ***
 1) NOTICE OF COMMENCEMENT MUST HAVE THE
 FOLLOWING INFORMATION ADDED TO IT,
 *LEGAL DESCRIPTION OF PROPERTY,AND
 GENERAL DESCRIPTION OF IMPROVEMENTS.
 THEN REFILE WITH PALM BEACH COUNTY.
  
 2) SHOW ON MECHANICAL PLAN HOW CONDENSER
 UNITS ARE TO BE ANCHORED TO CONDENSER
 STANDS AND HOW MANY STRAPS PER COMDENSER
 UNIT. BE ADVISED TIE DOWN CABLES ARE NOT
 PERMITTED OVER THE TOP OF A CONDENSER
 UNIT.
  
 3) PLEASE ESTIMATE AMOUNT OF CONDENSATE
 WATER TO ENTER DRY WELL AND SIZE DRY
 WELL ACCORDINGLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 4 Status P Date 2007-07-02 Cont ID  
Sent By jleech Date 2007-07-02 Time 11:04 Rev Time 0.00
Received By jleech Date 2007-07-02 Time 11:04 Sent To  
Notes
2007-07-02 11:05:12CONDENSATE DRAINAGE ONLY

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-02 Cont ID  
Sent By jleech Date 2007-01-02 Time 14:55 Rev Time 0.00
Received By jleech Date 2007-01-02 Time 14:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 07:32 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 07:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By jleech Date 2006-07-18 Time 09:37 Rev Time 0.00
Received By jleech Date 2006-07-18 Time 09:32 Sent To  
Notes
2006-07-18 00:00:00CONDENSATE PIPING TO BE INCLUDED ON
 MASTER BUILDING PERMIT PLANS. NO
 PLUMBING REVIEW AT THIS TIME.
 JOHN LEECH
 805-6695