Plan Review Details - Permit 06070132
Plan Review Stops For Permit 06070132
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-07-17 Cont ID  
Sent By lursu Date 2006-07-17 Time 14:30 Rev Time 0.00
Received By lursu Date 2006-07-17 Time 14:28 Sent To  
Notes
2006-07-18 00:00:00WARRANTY DEED WAS SUBMITTED;OWNER INFO
 UPDATED
2006-07-17 00:00:00UPDATED SITE ADDRESS FOR THE UNIT 204
 .PROOF OF OWNERSHIP IS REQUIRED PRIOR OF
 RELEASING THE PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-28 Cont ID  
Sent By alange Date 2006-09-28 Time 08:39 Rev Time 0.00
Received By alange Date 2006-09-28 Time 08:39 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-25 Cont ID  
Sent By alange Date 2006-07-25 Time 16:22 Rev Time 0.00
Received By alange Date 2006-07-25 Time 16:22 Sent To  
Notes
2006-07-25 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 3.SHOW EXISTING WALL ON EAST SIDE AS A
 ONE HOUR RATED WALL.
  
 4.SHOW SALES/ SERVICE COUNTER
 COMPLYING WITH FBC 11-7.2
  
 5.SHOW 18" MINIMUM CLEARANCE ON
 LATCHED SIDE OF DOOR PER FBC 11 FIG 25
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-01-10 Cont ID  
Sent By dpalmer Date 2007-01-10 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2007-01-10 Time 11:38 Sent To  
Notes
2007-01-10 12:09:56** UNSAT ***
  
 1) NOTE: PLEASE SEE PLANS ARE NOW INCLUDING A NEW TANK
 LESS WATER HEATER WHICH HAS CREATED NEW COMMENTS.
 PLEASE SEE THIS CIRCUIT IS BEING SHOWN AS A SINGLE POLE
 20AMP CIRCUIT, HOWEVER THE LOAD ON THIS CIRCUIT IS
 SHOWN AS 3300VA. PLEASE SEE THAT THIS EXCEEDS THE
 MAXIMUM RATING ON THIS 20AMP SINGLE POLE CIRCUIT.
 PLEASE VERIFY THE SIZE OF THE CIRCUIT AND THE LOAD AND
 CORRELATE.
 310.16, 240.4, 408.4, 220 ETC.
  
 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE UNIT BEING INSTALLED. PLEASE KNOW THIS
 DOCUMENTATION MUST CONTAIN THE INFORMATION AND
 LISTING(S) FROM A NRTL. NATIONALLY RECOGNIZED TESTING
 LABORATORY.
 110.3, 90.7
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-28 Cont ID  
Sent By dpalmer Date 2006-09-28 Time 18:16 Rev Time 0.00
Received By dpalmer Date 2006-09-28 Time 18:03 Sent To PC
Notes
2006-09-28 00:00:00ARCH REDLINED LC'S FOR SW'S AS "S""T".
 OK, AND INITIALED PER ARCH AND DVP.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-18 Cont ID  
Sent By dpalmer Date 2006-09-18 Time 18:34 Rev Time 0.00
Received By dpalmer Date 2006-09-18 Time 17:42 Sent To  
Notes
2006-09-18 00:00:00*** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM THE
 PREVIOUS REVIEW AND ONE NEW COMMENT DUE
 TO CHANGE IN RISER.
 PLEASE SEE NOTES BELOEW ARE BEING TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WIHT NEW
 BEING ADDED TO THE BOTTOM OF REVIEW.
  
  
 1) NOTE: NO, PLEASE SEE RESPONSE LETTER
 MENTIONS THAT SHEET "A-1" WAS REVISED,
 HOWEVER THESE COULD NOT BE LOCATED ON
 A-1. PLEASE EITHER REVISE ON A-1 OR
 ELECTRICAL SHEETS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE FOLLOWING
 CURRENT CODES IN EFFECT. PLEASE KNOW THE
 LATEST EDITION OF THE NEC IS NOT YET
 ADOPTED BY THE STATE OF FL.
 PLEASE LIST THE 2002 NFPA-70 (NEC), 2002
 NFPA-72 AND FBC 2004.
  
 2) NOTE: NO, NOT ENTIRELY. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 AS NOTED
 ON PREVIOUS REVIEW. PLEASE SEE ALL ROOMS
 AND OFFICES CONTAINING FLR TO CEILING
 HEIGHT PARTITIONS, SHALL CONTAIN
 SEPARATE CONTROLS FROM THE NORMAL TIMED
 SCHEDULING. PLEASE SEE CONTROLS SHOULD
 BE NOTED AND OVER RIDES TIMES (MAX)
 SAHLL BE STATED FOR THE DEVICE TYPE
 SHOWN.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN
 A BUILDING GREATER THAN 5K SQ FT, IT
 WILL REQUIRE LIGHTING CONTROLS BY ONE
 METHOD AS MENTIONED. PLEASE EACH ROOM
 SHALL ALSO CONTAIN EITHER SOME TYPE OF
 OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE
 KNOWIF TIMER TYPE DEVICE IS USED, A
 MAX OF 4HR OF OVER RIDE, AND FOR
 OCCUPANCY SENSOR TYPE PERMITS A MAX OF
 30 MINS OF OVER RIDE. PLEASE SEE
 13-415.1.ABC.1.2, .1.3.
  
 3) NOTE: OK.
  
 4) NOTE: NO, THE COMMENT WAS ADDRESSED ,
 HOWEVER THE CONDUCTORS WERE REVISED.
 PLEASE SEE NEC 310.16, AS #4'S ARE ONLY
 RATED FOR 85A'S, AND WHEN THE CONDUCTOR
 SIZE DOES NOT CORRELATE TO THE STANDARD
 OCP DEVICE, THE CODES DOES PERMIT YOU TO
 GO TO THE NEXT SIZE UP, HOWEVER PLEASE
 SEE 240.6 AS THE NEXT SIZE OCP IS 90A'S
 AND THE RISER SHOWS 100A OCP ON THESE
 FEEDERS.
 PLEASE SEE 310.16 AND ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFYTHE CONDUCTORS
 SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND
 3-3#0, IT IS BEING TAKEN THIS IS A
 MISPRINT AND THE SYMBOLS ARE MEANING
 3/0?S. PLEASE SEE REDLINED PLANS FOR
 LOCATIONS AND ADJUST.
 310.16.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: OK, CAHNGED TO 100A.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By dpalmer Date 2006-07-24 Time 09:09 Rev Time 0.00
Received By dpalmer Date 2006-07-24 Time 07:32 Sent To  
Notes
2006-07-24 00:00:00** UNSAT **
  
 1) NOTE: PLEASE SPECIFY THE FOLLOWING
 CURRENT CODES IN EFFECT. PLEASE KNOW THE
 LATEST EDITION OF THE NEC IS NOT YET
 ADOPTED BY THE STATE OF FL.
 PLEASE LIST THE 2002 NFPA-70 (NEC), 2002
 NFPA-72 AND FBC 2004.
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN
 A BUILDING GREATER THAN 5K SQ FT, IT
 WILL REQUIRE LIGHTING CONTROLS BY ONE
 METHOD AS MENTIONED. PLEASE EACH ROOM
 SHALL ALSO CONTAIN EITHER SOME TYPE OF
 OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE
 KNOWIF TIMER TYPE DEVICE IS USED, A
 MAX OF 4HR OF OVER RIDE, AND FOR
 OCCUPANCY SENSOR TYPE PERMITS A MAX OF
 30 MINS OF OVER RIDE. PLEASE SEE
 13-415.1.ABC.1.2, .1.3.
  
 3) NOTE: PLEASE SEE MISSING THE PRINTED
 NAME AND PRINTED LICENSE NUMBER OF SAID
 ARCHITECT ON TITLE BLOCKS AS REQUIRED
 PER FAC 61G1-16.004.
 THIS IS REQUIRED FOR ALL TRADES AND FOR
 ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE CLARIFYTHE CONDUCTORS
 SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND
 3-3#0, IT IS BEING TAKEN THIS IS A
 MISPRINT AND THE SYMBOLS ARE MEANING
 3/0?S. PLEASE SEE REDLINED PLANS FOR
 LOCATIONS AND ADJUST.
 310.16.
  
 5) NOTE: PLEASE SEE 700.12E AS THE
 EM/EXT LTS ARE REQUIRED TO BE CIRCUITED
 AHEAD OFSWITCHING ON THE LOCAL
 LIGHTING BRANCH CIRCUIT IN THE SAME
 AREAS.
  
 6) NOTE: PLEASE CLARIFY SPECIAL
 EQUIPMENT LOAD OF 7500 VAON LOAD
 CALCULATIONS AS THIS DOES NOT SEEM TO
 CORRELATE WITH AMPERAGES ON PANEL
 SCHEDULES.
 PLEASE ALSO LIST THIS EQUIPMENT; SOME
 NOTED FOR FUTURE HOWEVER PLEASE KNOW
 EQUIPMENT MAY AFFECT INSTALLATION
 REQUIREMENTS.
 PLEASE ALSO SEE THAT WHEN THE NUMBER OF
 RECEPTS ARE KNOW THE AMOUNT FIGURED FOR
 LOAD CALCULATIONS SHALL BE 180VA PER
 RECEPT.
 PLEASE ALSO SEE PLANS APPEAR TO SHOW A
 REFRIGIERATOR CIRCUITED TO OTHER GENERAL
 RECEPT CIRCUIT? PLEASE VERIFY THE AMOUNT
 OF VA ON THIS APPLIANCE AND PROVIDE A
 DEDICATED CIRCUIT IF OVER 750VA.
 220.3,220.10,220.11,220.13 ETC.
 106.1.2 FBC ADMIN SECT.
  
 7) NOTE: PLEASE CLARIFY RISER. IS THIS
 200A METER EXISTING FOR FUTURE USE AND
 NOW BEING USED OR IS THIS NEW? PLEASE
 LIST THE LOAD ON THE EXISTING SERVICE
 ALONG WITH THE NEW LOAD ADDED.
 220,220.35 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-14 Cont ID  
Sent By mawillia Date 2006-09-14 Time 14:33 Rev Time 0.00
Received By mawillia Date 2006-09-14 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-03 Cont ID  
Sent By mawillia Date 2006-08-03 Time 11:53 Rev Time 0.00
Received By mawillia Date 2006-08-03 Time 11:35 Sent To  
Notes
2006-08-03 00:00:00*** PROVISO ***
  
  
 1.) EXIT/EMERGENCY LIGHTING ACCEPTABLE
 PENDING ISSUES CORRECTED AS PER
 ELECTRICAL PLAN REVIEW.
  
 2.) EXPLAIN/SHOW A EVEN DISTRIBUTION (OR
 LACK THEREOF) OF SMOKE DETECTORS ON THE
 PLAN.
  
  
  
  
  
 LT. MICHAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-09 Cont ID  
Sent By adarroug Date 2007-01-09 Time 17:50 Rev Time 0.00
Received By adarroug Date 2007-01-09 Time 17:50 Sent To M
Notes
2007-01-09 17:50:41TO "M" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-29 Cont ID  
Sent By adarroug Date 2006-12-29 Time 11:15 Rev Time 0.00
Received By adarroug Date 2006-12-29 Time 11:15 Sent To  
Notes
2007-01-09 15:58:50TO "BOB"#11
2006-12-29 11:16:27WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-13 Cont ID  
Sent By adarroug Date 2006-09-13 Time 13:35 Rev Time 0.00
Received By adarroug Date 2006-09-13 Time 13:35 Sent To  
Notes
2006-09-13 00:00:00TO "BOB"#6

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-03 Cont ID  
Sent By mawillia Date 2006-08-03 Time 11:35 Rev Time 0.00
Received By mawillia Date 2006-07-14 Time 18:08 Sent To  
Notes
2006-07-20 00:00:00TO "BOB"#14
2006-07-14 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-01-10 Cont ID  
Sent By tgordon Date 2007-01-10 Time 09:30 Rev Time 0.30
Received By tgordon Date 2007-01-10 Time 09:30 Sent To  
Notes
2007-01-10 09:40:15MECHANICAL REVISION PG. A2 & AC1
 9" RETURN AIR TRANSFER DUCTS DUE TO LIMITED ROOM.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-15 Cont ID  
Sent By tgordon Date 2006-09-15 Time 12:11 Rev Time 0.25
Received By tgordon Date 2006-09-15 Time 12:11 Sent To  
Notes
2006-09-15 00:00:00RE-STAMP

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-20 Cont ID  
Sent By tgordon Date 2006-07-20 Time 16:20 Rev Time 0.40
Received By tgordon Date 2006-07-20 Time 16:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-01-12 Cont ID  
Sent By jleech Date 2007-01-12 Time 15:00 Rev Time 0.00
Received By jleech Date 2007-01-12 Time 15:00 Sent To  
Notes
2007-01-12 15:02:29REVISED P-1 SHEET. STUDER VENTS TO BE USED AND ON
 DEMAND WATER HEATER.OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-23 Cont ID  
Sent By jleech Date 2006-09-23 Time 13:08 Rev Time 0.00
Received By jleech Date 2006-09-23 Time 13:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-24 Cont ID  
Sent By jleech Date 2006-07-24 Time 07:33 Rev Time 0.00
Received By jleech Date 2006-07-24 Time 07:33 Sent To  
Notes
2006-07-24 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTES FOR
 DESIGN PROFESSIONAL INFORMATION MISSING
 FROM DRAWINGS.
 2.A DRINKING FOUNTAIN IS REQUIRED TO
 MEET MINIMUM PLUMBING FIXTURE
 REQUIRMENTS. SEE FBC-2004 PLUMBING TABLE
 403.1 (B).
 3.BREAK SINK SHALL COMPLY WITH BUILDING
 CODE CHAPTER 11 SECTIONS;
 11-4.24.3 KNEE CLEARANCE UNDER SINK.
 11-4.24.4 DEPTH OF SINK MAX. OF 6 1/2"
 11-4.24.5 CLEAR FLOOR SPACE UNDER SINK
 11-4.24.6 EXSPOSED PIPES TO BE RAPPED.
 11-4.24.7 FAUCET HANDLES.
 PLEASE SHOWCOMPLIANCE TO THESE
 SECTIONS ON KITCHENETTE DETAIL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695