Plan Review Details - Permit 06070109
Plan Review Stops For Permit 06070109
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2007-09-04 Cont ID  
Sent By lmartine Date 2007-09-04 Time 13:15 Rev Time 0.00
Received By lmartine Date 2007-09-04 Time 13:15 Sent To  
Notes
2007-09-04 13:17:59REVISION FOR STEEL COLUMNS AND DOOR PRODUCT APPROVALS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-02 Cont ID  
Sent By lmartine Date 2007-03-02 Time 15:33 Rev Time 0.00
Received By lmartine Date 2007-03-02 Time 15:33 Sent To  
Notes
2007-03-02 15:34:37 
 REVISION OK, SUBMIT PRODUCT APPROVAL FOR 10' DOORS.
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-07 Cont ID  
Sent By alange Date 2006-11-07 Time 13:59 Rev Time 0.00
Received By alange Date 2006-11-07 Time 13:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-27 Cont ID  
Sent By alange Date 2006-09-27 Time 10:20 Rev Time 1.50
Received By alange Date 2006-09-26 Time 16:07 Sent To  
Notes
2006-09-27 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 5.PGT 701 MISSING STATE PRODUCT
 APPROVAL.
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 10.SHOW FIREPLACE CONSTRUCTION
 DETAILS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By alange Date 2006-07-17 Time 09:18 Rev Time 3.50
Received By alange Date 2006-07-17 Time 09:18 Sent To  
Notes
2006-07-17 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 4. SIGN OWNER/AGENT ON ENERGY CALCS PER
 2004 FBC.
  
 5.PRODUCT APPROVALS REQUIRED FOR
 LINTELS.PGT 701 MISSING STATE PRODUCT
 APPROVAL.
  
 6.ALL PRODUCT APPROVALS SUBMITTED WITH
 QUALITY ASSURANCE SHALL HAVE THE
 FOLLOWING STATE APPROVAL ATTACHED.
  
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A STATE PRODUCT APPROVAL
 SHEETS THAT LISTS THE PRODUCT IDENTITY
 NUMBER FROM THE STATE. IF THE PRODUCT
 DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT
 AN APPLICATION FOR LOCAL PRODUCT
 APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 7.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 8.R401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED
 POINT OF COLLECTION SO AS TO NOT CREATE
 A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE AWAY FROM FOUNDATION
 WALLS SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET.
  
 9.SHOW GUARD RAIL DETAILS COMPLYING
 WITH R-312.1 AND R-312.2.
  
 10.SHOW FIRE PLACE CONSTRUCTION
 DETAILS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2008-03-13 Cont ID  
Sent By btrobaug Date 2008-03-13 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2008-03-13 Time 14:40 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2008-03-10 Cont ID  
Sent By btrobaug Date 2008-03-10 Time 13:14 Rev Time 0.00
Received By btrobaug Date 2008-03-10 Time 13:11 Sent To PC
Notes
2008-03-10 13:14:11 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 1} HAND DRAWN CHANGES TO THE PLAN ARE NOT ACCEPTABLE
 FOR RECORD RETENTION OR CLARITY IN THE FIELD. 106.1.3
 FBC AS AMENDED.PLANS ARE REQUIRED TO BE DRAFTSMAN
 QUALITY
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2006-11-20 Cont ID  
Sent By dpalmer Date 2006-11-20 Time 17:31 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 16:26 Sent To PC
Notes
2006-11-20 17:32:47**
  
 ALL MAINS GROUPED AND NO MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS INSIDE THE BUILDING.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2006-10-29 Cont ID  
Sent By dpalmer Date 2006-10-29 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2006-10-29 Time 11:34 Sent To B
Notes
2006-10-29 13:06:08**** UNSAT 3RD REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
 COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND THEN NEW COMMENTS
 ARE ADDED TO BOTTOM.
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK
  
 5) NOTE: OK.
  
 6) NOTE OK.
  
 7) NOTE:NO, OK, PLEASE SEE NEW NOTES FOR A REVISED
 RISER WHICH HAS NOW CHANGED A THIRD TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2 **
 OK, HOWEVER SEE NEW NOTES A
 COMPLETELY NEW RISER WAS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFTER DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK, STAIRS REMOVED.
  
 12) NOTE: OK, STAIRS REMOVED.
  
 13) NOTE:NO, SAME NOTE, PLEASE SEE PANEL SCHEDULE(S).
 IE: EXAMPLE: MASTER BDRM LT., KITCHEN LT'S, BERM #2
 RECEPTS, HALLWAY LT'S ETC
 IT IS KNOWN THAT DURING CONSTRUCTION THESE CIRCUITS AND
 LOCATIONS WILL CHANGE HOWEVER A MIN SCHEDULE FOR BRANCH
 CIRCUITS ARE REQUIRED AT THIS TIME.
  
 ** PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE SPECIFIC ROOMS
 AND AREAS ARE NOT LISTED ON PLANS.
  
 ** PREVIOUS REVIEW NOTEREVIEW #1**
 PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: OK, HOWEVER SEE NEW NOTE FOR OCP FOR STEAM
 UNIT.
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: OK. HOWEVER SEE MINOR NEW NOTE FOR STEAM UNIT
 OCP.
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:OK.
  
 21) NOTE: OK.
  
 22) NOTE:OK.
  
 23) NOTE: OK.
  
 24) NOTE: OK, PLEASE BE SURE ANY REVISED
 PLANS ARE ALSO SIGNED, ETC.
  
 25) NOTE:OK, PLEASE DO THE SAME AS NOTED ON BOTH
 PREVIOUS REVIEW.
  
 ** PREVIOUS REVIEW NOTE #2.
 OK, PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
 ***** NEW NOTES 2ND REVIEW ******
  
 26 ) NOTE: OK, HOWEVER SEE NEW NOTES FROM THIRD REVIEW
 PERTAINING TO REVISED SERVICE RISER.
  
 ** PREVIOUS REVIEW NOTE , REVIEW #2 **
 PLEASE SEE RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED.
 PLEASE SEE PLANS DO NOT SHOW THE
 LOCATION OF THIS NEW 400A MAIN. PLEASE
 SEE ALL MCB'S ARE BEING SHOWN AS BEING
 TAPPED FROM THIS ONE MAIN. PLEASE VERIFY
 TAPPED CONDUCTORS RULE W/ 240.21
 DEPENDING ON WHERE MAIN IS LOCATED.
 (VERIFY THE LUGS AVAILABLE FOR THREE
 CONDUCTORS, ONLY NOTED)
  
 27) NOTE: OK.
  
 28) NOTE: OK, MAIN NOW REMOVED?
  
 29) NOTE: OK, HOWEVER SEE NOTE FOR MIN SIZE ON NEW
 NOTES FOR GEC.
  
 30) NOTE: OK.
  
 31) NOTE:OK, SEE NEW NOTES.
  
  
 ** NEW NOTES 3RD REVIEW ***
  
  
 32) NOTE: PLEASE SEE SERVICE HAS NOW BEEN COMPLETELY
 REVISED REMOVING THE 400A MAIN DISCONNECT AND PROVIDING
 "TAPPED" CONDUCTORS FROM A NEW 480K-7 METER CAN. PLEASE
 SEE 310.15B6 CAN NO LONGER BE USED FOR THE SEC'S AS
 RISER SHOWN NO LONGER CAN USE EXCEPTION.
 310.15B6(HANDBOOK) 230.42A, 240.4 , 310.16 ETC. PLEASE
 SEE THE SEC'S IF BEING PROVIDED TO A FPL HAND-HOLE
 SHALL BE BASED ON THE 500A SERVICE BEING PROVIDED.
 PLEASE ALSO SEE TAPS(LUGS FOR 3CONDUCTORS ARE AVAILABLE
 FOR THE K-7, HOWEVER PLEASE VERIFY HOWCONDUCTORS ARE
 GOING TO BE INSTALLED AND THE LENGTH OF THE SEC'S FROM
 THE METER UNTIL THEY TERMINATE IN THE OCP DEVICE.
 PLEASE SEE 230.70 AS THE LENGTH INTO A BUILDING SHALL
 BE LIMITED TO THE NEAREST POINT OF ENTRANCE INTO A
 BLDG. THEPREVIOUS RISER SHOWED A MAIN WHICH WAS OK,
 AS LONG AS THE TAPPED CONDUCTORS MET 240.21, 408.16 AND
 THE LUGS WERE AVAILABLE FOR THE 400A MAIN DISCONNECT AS
 PREVIOUSLY NOTED AND THERE WERE "EQUIPMENT GROUNDING
 CONDUCTORS TO EACH PANEL WHICH WERE MISSING ON PREVIOUS
 RISER.(90.7,250.24B,250.122)
 PLEASE SEE AS SHOWN THE LENGTH OF SEC'S INTO THE
 DWELLING IS NOT PERMITTED TO BE MORE THAN 8FT (TOTAL
 LENGTH) OF UNPROTECTED CONDUCTOR 230.70, 90.4.
  
 ** PLEASE SEE THE PANEL "B" IS SHOWN WITH A 150A MCB
 WITH 3/0'S? THIS ISOK, HOWEVER ONLY NOTED. **PLEASE
 SEE THE FOLLOWWING COMMENTS AS THE SIZE OF THE SEC'S
 AND SERVICE ALSO AFFECTS THE GEC.
  
 33) NOTE: PLEASE PROVIDE COMPLETE NEUTRAL LOAD
 CALCULATIONS FOR THE NEUTRAL LOAD AS THE SEC NEUTRAL IS
 NOW BEING SHOWN 4 TIMES SMALLER THAN THE OTHER PHASE
 SEC'S, OR ADJUST THE SEC FOR THE NEUTRAL FOR FULL
 SIZE.220.22, 310.16
  
 34) NOTE: PLEASE SEE BASED ON NEW NOTES FROM THIRD
 REVIEW AND NOT KNOWING HOW LARGE WILL BE OR IF RISER
 WILL BE REVISED, PLEASE SEE 250.66 AS THE GEC IS
 REQUIRED TO BE SIZED FOR THE SEC'S. PLEASE SEE 310.16,
 AS THIS WOULD BE REFLECTED TO A 2/0 MIN.
 THIS IS NOTED AT THIS TIME BASED ON RISER AS SHOWN.
  
 35) NOTE: PLEASE SEE OCP AS NOTED ON SPECS FOR STEAM
 UNIT, INDICATES 35A OCP TO BE USED, HOWEVER PANEL
 SCHEDULE/CALCS INDICATE 40A. THIS IS AN ITEM WHICH
 COULD HAVE BEEN REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER CORRECTIONS AT THIS TIME. PLEASE ADJUST.
  
 36) NOTE: PLEASE SEE THE NOTICE OF COMMENCMENT
 SUBMITTED IS LONGER VALID AND WILL BE REQUIRED TO BE
 RE-RECORDED. PLEASE SEE FS 713.13(2) . IF WORK HAS NOT
 COMMENCES WITHIN 90DAYS OF RECORDING NOC, THE NOC IS NO
 LONGER VALID AND SHALL BECOME VOID. THIS ONLY NEEDS TO
 BE RE-RECORDED AND IS ONLY REQUIRED WHEN PICKING UP
 PERMIT.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-23 Cont ID  
Sent By dpalmer Date 2006-08-23 Time 12:13 Rev Time 0.00
Received By dpalmer Date 2006-08-23 Time 07:51 Sent To P
Notes
2006-08-23 00:00:00**** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM
 PREVIOUS REVIEW AND SOME NEW COMMENTS
 DUE TO CHANGES IN PLANS.
 COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND THEN NEW COMMENTS
 ARE ADDED TO BOTTOM.
  
  
 ***** UNSAT *****
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 COMMENTS AND SOME ITEMS NOT COMPLETE AT
 THIS TIME, THERE MAY BE COMMENTS OTHER
 THAN BELOW ON THE NEXT REVIEW.
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: NO, PLEASE SEE SOME ITEMS WERE
 ADDED AND SOME WERE CORRECTED, HOWEVER
 PLEASE SEE LOAD CALCULATIONS. PLEASE
 KNOW, THE LARGER OF THE TWO LOADS OF AN
 A/C CU AND AHU SHOULD BE FIGURED INTO
 THE LOAD CALCULATIONS. PLEASE SEE CU'S
 WITH LOADS LESS THAN HEAT BEING SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE PLANS, PANEL
 SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS
 THAN IN PANEL SCHEDULES OR LOAD CALCS.
 PLEASE SEE ONLY ONE CU IS SHOWN ON
 PLANS, PLEASE SEE 3- AHU'S??
 106.1.2, 440.11 ETC
  
 5) NOTE: OK.
  
 6) NOTE OK.
  
 7) NOTE: OK, HOWEVER SEE NEW NOTES A
 COMPLETELY NEW RISER WAS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFTER DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: OK, HOWEVER SEE NOTE PERTAINING
 TO A/C LOADS.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK, STAIRS REMOVED.
  
 12) NOTE: OK, STAIRS REMOVED.
  
 13) NOTE: NO, PLEASE SEE SPECIFIC ROOMS
 AND AREAS ARE NOT LISTED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: NO, PLANS ONLY PROVIDE NOTES
 FOR WHERE THESE ARE GOING TO BE. NO
 DISCONNECTS, CLEARANCES, ACCESS IS BEING
 SHOWN. PLEASE SEE CODES BELOW AS
 CLEARANCES ETC CAN NOT BE VERIFIED.
 PLEASE SEE 240.24D ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE ALL EQUIPMENT
 ON PLANS FOR STEAM UNITS, ELEVATOR
 EQUIPMENT, DISCONNECTS, LT'S, GFI ETC.
 UNABLE TO REVIEW LOCATIONS FOR CODE
 COMPLIANCE AT THIS TIME.
 110.26,240.4.240.24 ETC
  
 15) NOTE: OK.
  
 16) NOTE: OK.
  
 17) NOTE: NO, THESE COULD NOT BE LOCATED
 ON PLANS OR SUBMITTED IN PACKAGES.
 NEED TO VERIFY MIN CLEARANCES ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT MANUFACTURES
 SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT
 AND FOR STEAM UNIT EQUIPMENT. ALL SHALL
 INDICATE A LISTING FROM A NRTL.
 110.3, 106.1.2*
  
 18) NOTE: OK.
  
 19) NOTE: OK.
  
 20) NOTE:NO, PLEASE SEE A DINING RM
 CIRCUIT WAS ADDED ON PANEL SCHEDULE
 WHICH IS OK, HOWEVER IF THIS IS A
 DEDICATED CIRCUIT, THEN PLEASE SEE
 210.11C1, 220.16 FOR MIN VA TO BE
 FIGURED FOR THIS CIRCUIT.
 7-SM APPL CIRCUITS ARE LISTED ON PANEL
 SCHEDULE AND 7- SHOWN IN LOAD CALCS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 210.52B1,
 210.11C1,220.16, DINING RM CIRCUIT SHALL
 BE INDICATED AS NOTED.
  
 21) NOTE: OK.
  
 22) NOTE:NO, PLEASE SEE DISCONNECT FOR
 CU OUTSIDE NOW, HAS BEEN MOVED BEHIND
 UNIT. THIS WAS SHOWN W/ CORRECT
 CLEARANCES ON PREVIOUS PLANS.
 PLEASE CLARIFY THE DISC'S FOR AHU'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 110.26 FOR MIN
 CLEARANCES FOR AHU'S AND DISCONNECTS.
  
 23) NOTE: OK.
  
 24) NOTE: OK, PLEASE BE SURE ANY REVISED
 PLANS ARE ALSO SIGNED, ETC.
  
 25) NOTE: OK, PLEASE BE SURE TO DO THE
 SAME WHEN RESUBMITTING.
  
 ** PREVIOUS REVIEW NOTE **
 ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEAS BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
 ***** NEW NOTES ******
  
 26 ) NOTE: PLEASE SEE RISER DIAGRAM HAS
 NOW BEEN COMPLETELY REVISED.
 PLEASE SEE PLANS DO NOT SHOW THE
 LOCATION OF THIS NEW 400A MAIN. PLEASE
 SEE ALL MCB'S ARE BEING SHOWN AS BEING
 TAPPED FROM THIS ONE MAIN. PLEASE VERIFY
 TAPPED CONDUCTORS RULE W/ 240.21
 DEPENDING ON WHERE MAIN IS LOCATED.
 (VERIFY THE LUGS AVAILABLE FOR THREE
 CONDUCTORS, ONLY NOTED)
  
 27) NOTE: PLEASE SEE ITEMS WHICH ARE NOW
 HAND WRITTEN ON RISER AND PLANS WHICH IS
 NOT PERMITTED. THESE ITEMS SHOULD BE
 PRINTED WHEN PLANS ARE RE-PRINTED.
 FBC ADMIN SECT 106.1
  
 28) NOTE: PLEASE SEE NOW THAT RISER HAS
 BEEN REVISED, PLEASE SEE MISSING
 "EQUIPMENT GROUNDING CONDUCTORS" FROM
 THE MAIN TO THE SUB-PANELS.
 PLEASE SEE 250.24B, 250.110, AND TABLES
 IN 250.122 FOR SIZING.
  
 29) NOTE: PLEASE SEE MISSING CONNECTIONS
 FOR GROUNDING ELECTRODE SYSTEM TO BE
 COLD WATER PIPE (IF METAL), NEW FOOTER
 STEEL AND ANY OTHER SYSTEMS BEING
 PROVIDED. PLEASE SHOW ON RISER.
 250.50
 THIS WAS NOT IN PREVIOUS REVIEW NOTES
  
 30) NOTE: PLEASE SEE POOL PUMP AND POOL
 HEATER SHOULD BE NOTED AS (FUTURE) SINCE
 THESE ARE NOT SHOWN ON PLANS AND POOL IS
 NOT PERMITTED AT THIS TIME.
  
 31) NOTE: PLEASE SEEFS 553.80(2)(B)
 WITH RESPECT TO REPEAT COMMENTS.
 THIS IS ONLY A NOTICE.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-08 Cont ID  
Sent By dpalmer Date 2006-07-08 Time 15:58 Rev Time 0.00
Received By dpalmer Date 2006-07-08 Time 15:27 Sent To Z
Notes
2006-07-08 00:00:00 
 ***** UNSAT *****
  
 ** PLEASE KNOW, DUE TO THE EXTENT OF
 COMMENTS AND SOME ITEMS NOT COMPLETE AT
 THIS TIME, THERE MAY BE COMMENTS OTHER
 THAN BELOW ON THE NEXT REVIEW.
  
  
 1) NOTE: PLEASE SEE 210.52 FOR RECEPT
 SPACING. PLEASE SEE MANY LOCATIONS ON
 PLANS.2',6',12' RULE.
  
 2) NOTE: PLEASE SEE MISSING RECEPTS FOR
 KITCHEN ISLAND, FOR ALL ELECTRICAL
 APPLIANCES, COUNTERSPACE ETC. PLEASE
 COMPLETE.
 PLEASE SEE 210.52C1-5, 210.8A6, FBC
 ADMIN SECT 106.1.2
  
 3) NOTE: PLEASE KNOW, SD'S SHALL BE
 LOCATED WITH IN 3' OF THE PEAK ON A
 SLPOED CEILING AND SHALL BE WITHIN 12"
 OF THE HIGHEST POINT ON A FLAT CEILING.
 NFPA-72 11.8.3
 PLEASE ALSO SEE AREAS WHICH REQUIRE
 SD'S IN THE IMMEDIATE VICINITY OUTSIDE
 ALL SLEEPING RMS.
 11.5.1.1
  
 4) NOTE: PLEASE CORRELATE PLANS, PANEL
 SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS
 THAN IN PANEL SCHEDULES OR LOAD CALCS.
 PLEASE SEE ONLY ONE CU IS SHOWN ON
 PLANS, PLEASE SEE 3- AHU'S??
 106.1.2, 440.11 ETC
  
 5) NOTE: PLEASE SEE MISSING GFI RECEPT
 PER 210.6 FOR CU'S.
  
 6) NOTE PLEASE PROVIDE AIC RATINGS FOR
 MAIN(S). 110.9, ONLY SHOWN FOR SUB
 PANELS AND THE SERIES RATINGS.
  
 7) NOTE: PLEASE VERIFY THE SIZE OF MAIN
 AND METER, AS THE 320A OF METER AND THE
 LOADS CALCS AFETR DERATINGS, EXCEED
 THIS?
 PLEASE ADJUST AND INCREASE SIZE OF
 EQUIPMENT AS REQUIRED.
 230.70,240 ETC.
  
 8) NOTE: PLEASE CORRLEATE PLANS, PANELS,
 AND LOAD CALCS. PLEASE SEE PLANS
 INDICATE MORE THAN ONE WASHER AND DRYER.
 ADJUST AS REQUIRED.
 220.31, 215.5, 310.16, *106.1.2
  
 9) NOTE: PLEASE SEE LOADS SHOWN FOR
 WATER HEATER EXCEED BRANCH CIRCUIT
 RATING. 9KW? ON 30A BRKR?
 240.4,310.16, 240, 220 ETC
  
 10) NOTE: PLEASE SEE LOAD FOR STEAM UNIT
 EXCEEDS BRANCH CIRCUIT RATING FOR THE
 1-POLE 40A BRKR.
 240.4,310.16,240.,220 ETC
  
 11) NOTE: PLEASE PROVIDE AN ELEVATION OF
 ELECTRICAL SERVICE INCORPORATED WITH
 STAIRS ON OUTSIDE WALL.
 PLEASE SEE 110.26 AND MIN CLEARNECES
 REQUIRED BY FPL FOR LOCATION AS SHOWN.
  
 12) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL REQUIRED FOR OUTSIDE
 STAIRS AT LOWER LEVEL. (3-WAY). LS 101
 7.8, NEC 210.70
  
 13) NOTE: PLEASE SUBMIT AND COMPLETE THE
 PANEL SCHEDULES INDICATTING ALL
 CIRCUITS, WIRE SIZES, AND OCP FOR EACH.
 CIRCUITS SHALL BE SPECIFIC TO RMS AND
 AREAS.
 408.4, 240.4, 310.16 ETC.
 PLEASE SEE NOTES ABOVE AS MANY ITEMS ON
 PLANS, DO NOT MATCH.
  
 14) NOTE: PLEASE INDICATE ALL EQUIPMENT
 ON PLANS FOR STEAN UNITS, ELEVATOR
 EQUIPMENT, DISCONNECTS, LTS, GFI ETC.
 UNABLE TO REVIEW LOCATIONS FOR CODE
 COMPLIANCE AT THIS TIME.
 110.26,240.4.240.24 ETC
  
 15) NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 16) NOTE: PLEASE SEE ENERGY CALCS
 SHALLBE SIGNED , DATED AND SEALED.
 PLEASE SEE FBC CHAPTER 13
 FS 481.221, 471.023
  
 17) NOTE: PLEASE SUBMIT MANUFACTURES
 SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT
 AND FOR STEAM UNIT EQUIPMENT. ALL SHALL
 INDICATE A LISTING FROM A NRTL.
 110.3, 106.1.2*
  
 18) NOTE: PLEASE CLARIFY EXTERIOR LTS ON
 A 220V CIRCUIT??
 310.16, 220.,240.4 ETC
  
 19) NOTE: PLEASE INDICATE THE DEDICATED
 BATH(S) CIRCUIT(S0 PER 210.52D,210.11C3,
 MUST BE 20A AND #12.
  
 20) NOTE: PLEASE SEE 210.52B1,
 210.11C1,220.16, DINING RM CIRCUIT SHALL
 BE INDICATED AS NOTED.
  
 21) NOTE: PLEASE SEE PLANS NOTE ARC
 FAULT FOR WALL OUTLETS, THIS HAS CHANGED
 IN THE 2002 NEC, WHICH WENT INTO EFFECT
 7/1/2003.
 ALL OUTLETS" , IN BEDRMS SHALL BE
 PROTECTED. , LTS, RECEPTS, FANS, SD'S
 ETC.
 PLEASE LIST ALL THE ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. A NOT IS NOT
 SUFFICIENT.
 210.12B, 408.4
  
 22) NOTE: PLEASE SEE 110.26 FOR MIN
 CLEARENCES FOR AHU'S AND DISCONNECTS.
  
 23) NOTE: PLEASE SEE PLANS SHALL
 INDICATE THE 2002 NEC.
  
 24) NOTE: PLEASE SEE PLANS ARE NOT
 SIGNED, SEALED , OR DO NOT CONTAIN A
 TITLE BLOCK FOR PERSON RESPONSIBLE FOR
 PLASN AND DESIGN.
 PLEASE SEE THAT PLANS SHALL CLEARLY
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBEL FOR PLANS AND
 DESIGN. PLEASE SEE 106 FBC AND FS 481,
 471, 468 FOR PERSON PERMITTED TO DO
 SCOPE PF WORK AS SHOWN.
  
 25) NOTE: ** IMPORTANT**
 PLEASE KNOW, ONCE ALL REVIEWS ARE DONE
 AND BEFORE RESUBMITTING PLANS. PLEAS BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS FROM SETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONLY ONE COPY
 OF THE OLD/VOIDED REMOVED SHEETS SHOULD
 BE SUBMITTED FOR REFERENCE.
 PLEASE KNOW, THIS WILL HELP TO
 ALLEAVIATE ANY DELAYS INT THE PROCESSING
 OF PROJECT FOR PERMIT.
  
  
 *** PLEASE SEE NOTE AS FIRST MENTIONED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 11:37 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 11:37 Sent To E
Notes
2008-03-07 11:37:51TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2007-09-07 Cont ID  
Sent By adarroug Date 2007-09-07 Time 11:17 Rev Time 0.00
Received By adarroug Date 2007-09-07 Time 11:17 Sent To P
Notes
2007-09-07 11:18:09TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-08-03 Cont ID  
Sent By adarroug Date 2007-08-03 Time 09:08 Rev Time 0.00
Received By adarroug Date 2007-08-03 Time 09:08 Sent To B
Notes
2007-08-03 09:08:21TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-01-22 Cont ID  
Sent By adarroug Date 2007-01-22 Time 09:49 Rev Time 0.00
Received By adarroug Date 2007-01-22 Time 09:49 Sent To B
Notes
2007-01-22 09:49:42TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-10-27 Cont ID  
Sent By adarroug Date 2006-10-27 Time 09:00 Rev Time 0.00
Received By adarroug Date 2006-10-27 Time 09:00 Sent To E
Notes
2006-10-27 09:01:01TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 13:32 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 13:32 Sent To E
Notes
2006-08-22 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 13:12 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 13:12 Sent To Z
Notes
2006-08-15 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By alange Date 2006-07-17 Time 09:19 Rev Time 0.00
Received By alange Date 2006-07-07 Time 13:42 Sent To  
Notes
2006-07-07 00:00:00TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:08 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:08 Sent To P
Notes
2006-07-11 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2007-09-25 Cont ID  
Sent By jleech Date 2007-09-25 Time 09:00 Rev Time 0.00
Received By jleech Date 2007-09-25 Time 09:00 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-06 Cont ID  
Sent By jleech Date 2006-09-06 Time 09:22 Rev Time 0.00
Received By jleech Date 2006-09-06 Time 09:22 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By jleech Date 2006-07-12 Time 10:01 Rev Time 0.00
Received By jleech Date 2006-07-12 Time 10:01 Sent To B
Notes
2006-07-12 00:00:00DENIED;
 1.RISER DIAGRAM DOES NOT MATCH FLOOR
 PLAN. (NO BATHROOM NEXT TO KITCHEN)
 2.BOTH BIDETS ARE NOT VENTED. (TOILET
 FLUSHES PAST BIDET NO VENT)
 3.PLEASE SIZE TRUNK LINE ALL THE WAY TO
 KITCHEN.
 4. MASTER BATH FIRST FLOOR LAV STACK CAN
 NOT BE INSTALLED AS DRAWN. (DOOR BETWEEN
 LAVS)
 ONE SET OF PLANS MARKED IN RED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-05-06 Cont ID  
Sent By choops Date 2008-05-06 Time 16:00 Rev Time 0.00
Received By choops Date 2008-05-06 Time 16:00 Sent To PC
Notes
2008-05-06 16:07:20***APPROVED - LANDSCAPE PLAN SUBMITTAL***
  
 PROVISOS:
 1)PLANT MATERIALS USED PURSUANT TO THE PROVISIONS OF
 THIS SECTION SHALL BE EQUAL TO OR BETTER THAN FLORIDA
 DEPARTMENT OF AGRICULTURE NUMBER 1 NURSERY GRADE
 STANDARD.
  
 2)REQUIRED IRRIGATION SYSTEM SHALL BE INSTALLED IN
 BOTH THE YARD AND PARKWAY/SWALE AREA (IF APPLICABLE).
  
 3)BAMBOO TO BE INSTALLED AS SHOWN, 5 FEET FROM FRONT
 RIGHT-OF-WAY.

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-19 Cont ID  
Sent By mmclean Date 2006-08-19 Time 15:15 Rev Time 0.00
Received By mmclean Date 2006-08-19 Time 15:15 Sent To I
Notes
2006-08-19 00:00:00NOTE: THE PROPOSED A/C UNITS SHALL NOT
 BE CLOSER THAN 1FT ON THE EAST SIDE
 PROPERTY & 6FT ON THE WEST SIDE
 PROPERTY.
  
 NOTE: MUST PULL A SEPARATE PERMIT FOR
 ANY PROPOSED CBS WALL/FENCE/GATE WITH AN
 APPROVAL FROM THE CITY OF WEST PALM
 BEACH UTILITY DEPT.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-10 Cont ID  
Sent By mmclean Date 2006-07-10 Time 14:03 Rev Time 0.00
Received By mmclean Date 2006-07-10 Time 14:03 Sent To M
Notes
2006-07-10 00:00:00DENIED,
 1. THE PROPOSED STRUCTURE MUST MEET THE
 SIDE SETBACK OF 15FT TOTAL (THE LOCATION
 OF PROPOSED STAIRS AND WEST SIDE DOES
 NOT MEET THE 15FT TOTAL) SEC94-305 #9
 (OUTSIDE STAIRWAYS OVER 3FT IN HEIGHT
 ABOVE GRADE SHALL MEET ALL REQUIREMENTS
 OF THE MAIN STRUCTURE). (SITEPLANS DOES
 NOT GIVE ALL SETBACKS).
 2. MUST SHOW THE LOCATION OF THE
 PROPOSED A/C UNIT THE TWO COPY OF
 SURVEYS (SITEPLANS DOES NOT GIVE ALL
 SETBACKS).
 3. MUST PROVIDE DIMENSION OF THE
 PROPOSED DRIVEWAY (WIDTH) ON TWO COPY OF
 CURRENT SURVEYS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720