Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-12-27 Cont ID  
Sent By mjacobs Date 2006-12-27 Time 08:55 Rev Time 0.00
Received By mjacobs Date 2006-12-27 Time 07:42 Sent To PC
Notes
2006-12-27 08:55:52BUILDING PLAN REVIEW
 PERMIT:06070099
 ADD:1612 N. TAMARIND AVE.
 CONT: HOOVER CANVAS PRODUCTS CO.
 TEL: (561)844-4444
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST.
 ACTION: DENIED
  
 1)AWNINGS SHALL BE DESIGNED SO THAT FABRIC OR
 MEMBRANE COVER CAN BE QUICKLY AND EASILY REMOVED PER
 3105.4.2.1 TIGHTLY WRAPED OR WOVEN CORDS ARE ACCEPTABLE
 WHEN 2 COPIES OF A DETAILED INSTRUCTION GUIDEFOR
 REMOVAL ARE INCLUDED IN THE SUBMITTAL.
 IN ADDITION 2 COPIES OF A NOTORIZED LETTER OF INTENT TO
 REMOVE AT 75 MPH ARE REQUIRED.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-12-06 Cont ID  
Sent By adarroug Date 2006-12-06 Time 10:36 Rev Time 0.00
Received By adarroug Date 2006-12-06 Time 10:36 Sent To B
Notes
2006-12-06 10:36:58TO "MISC" BOX#2

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-12-27 Time   Rev Time 0.00
Received By adarroug Date 2006-11-20 Time 16:02 Sent To  
Notes
2006-11-20 16:03:04TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status F Date 2006-12-03 Cont ID  
Sent By mmclean Date 2006-12-03 Time 23:38 Rev Time 0.00
Received By mmclean Date 2006-12-03 Time 23:38 Sent To I
Notes
2006-12-03 23:40:42DENIED.
 1. PLEASE PROVIDE A FULL COPY OF CURRENT SURVEY,
 SHOWING THE COMPLETE PROPERTY WITH DIMENSION AND
 PROPOSED WORK.
 2. AWNINGS SHALL NOT PROJECT NO MORE THAN 4FT INTOA
 SETBACK SEC 94-305(5).
 3. SURVEYS SUBMITTED IS PARTIAL AND IS INSUFFICIENT FOR
 A COMPLETE REVIEW.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720


Account Summary | Usage Policy | Privacy Policy