Plan Review Details - Permit 06070094
Plan Review Stops For Permit 06070094
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By alange Date 2006-11-02 Time 15:22 Rev Time 0.00
Received By alange Date 2006-11-02 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-20 Cont ID  
Sent By alange Date 2006-07-20 Time 10:35 Rev Time 0.50
Received By alange Date 2006-07-20 Time 09:54 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-11-01 Cont ID  
Sent By dpalmer Date 2006-11-01 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2006-10-31 Time 07:07 Sent To I
Notes
2006-11-01 07:14:30OK, STAMPED ELEC SHEETS. SENT BACK TO INCOMING.
2006-10-31 17:55:37REMOVED FROM INCOMING, IN ELEC FOR REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 18:25 Sent To  
Notes
2006-07-15 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE CLARIFY THE ROOM IN
 WHICH THE NEW VAV PANEL IS BEING
 INSTALLED. PLEASE KNOW AND NOTE ON PLANS
 THAT THIS RM SHALL BE AN ELEC/MECH RM
 ONLY CONTAINING NO STORAGE.
 110.26,240.24,408.7 ETC.
 SIGNAGE REQUIRED ON DOOR STATING " NO
 STORAGE" OR WORDS TO THE EFFECT.
 MIN 1" ON CONTRASTING BACKGROUND.
  
 2) NOTE: PLEASE SPECIFY THE CURRENT NEC
 ( NFPA-70) OF 2002. PLANS NOTE THE
 LATEST EDITION, HOWEVER THE LATEST NEC
 (2005 ) HAS NOT BEEN ADOPTED AS OF YET.
  
 3) NOTE: PLEASE SEE TITLE BLOCKS OF
 SHEET SHOULD CORRELATE AS A-SHEETS
 MENTIONS THE GOVERNMENTAL BUILDING, YET
 E-SHEETS MENTIONS THE ADMINISTRATIVE
 OFFICE COMPLEX WHICH IS NOT THE SAME.
 PLEASE KNOW, PER THE PERMIT APPLICATION,
 WORK IS APPLIED FOR UNDER 301 N OLIVE
 WHICH SHOULD BE REFLECTED ON PLANS,
 WHICH IS THE GOV. CENTER.
  
 4) NOTE: NOTE ON PLANS MENTIONS ROUTING
 OF NEW CONDUIT AND MENTIONS NEW PANEL
 NEAR STAIRWELL, PLEASE KNOW, THE FEEDERS
 AND CONDUIT MAY NOT BE RUN IN STAIRWAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By mwennerg Date 2006-11-02 Time 13:40 Rev Time 0.00
Received By mwennerg Date 2006-11-02 Time 13:40 Sent To  
Notes
2006-11-02 13:44:30***APPROVED***
  
 1) DUCT SMOKE DETECTORS SHALL INITIATE A GENERAL FIRE
 ALARM IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
 2) FIRE AND SMOKE DETECTOR INSTALLATIONS SHALL BE
 TESTED FOR CLOSURE IN ACCORDANCE WITH UL 555.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722 OR 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By mwennerg Date 2006-07-18 Time 10:22 Rev Time 0.00
Received By mwennerg Date 2006-07-18 Time 10:22 Sent To  
Notes
2006-07-18 00:00:00***PROVISO***
  
  
 1) IN ACCORDANCE WITH LOCAL REQUIREMENTS
 DUCT SMOKE DETECTOR INSTALLATIONS SHALL
 BE TIED TO THE FIRE ALARM SYSTEM, AND
 INITIATE A GENERAL FIRE ALARM WHEN
 ACTIVATED.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS
 ARE REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM REMODEL IF APPLICABLE.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-28 Cont ID  
Sent By adarroug Date 2006-10-28 Time 14:47 Rev Time 0.00
Received By adarroug Date 2006-10-28 Time 14:46 Sent To  
Notes
2006-11-02 09:33:07TO "BOB"#11
2006-10-28 14:47:19WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-20 Cont ID  
Sent By alange Date 2006-07-20 Time 10:35 Rev Time 0.00
Received By alange Date 2006-07-07 Time 13:54 Sent To  
Notes
2006-07-11 00:00:00TO "BOB"#14
2006-07-07 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By tgordon Date 2006-11-02 Time 15:48 Rev Time 0.45
Received By tgordon Date 2006-11-02 Time 15:48 Sent To  
Notes
2006-11-02 15:52:02*** PROVISO ***
 1) CONDENSATE DRAIN TO DISCHARGE AT THE ROOF DRAIN NOT
 ONTO THE ROOF, PER 2004 FBC/M 307.2.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-07-12 Cont ID  
Sent By tgordon Date 2006-07-12 Time 14:15 Rev Time 0.30
Received By tgordon Date 2006-07-12 Time 14:15 Sent To  
Notes
2006-07-12 00:00:00*** DENIED ***
 1) OPEN FLOOR DRAINS CAN NOT BE IN A
 MECHANICAL ROOM THAT IS AN OPEN PLENUM,
 PER 2004 FBC/P 901.2, FBC/M 601.3, AND
 ASHARE 8.4.1.11 .
  
 2) PLANS THAT HAVE AN ENGINEER'S SEAL ON
 THEM MUST ALSO HAVE THE ENGINEER'S
 PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER ON EACH SHEET, PER FAC
 61G15-23.002 .
  
 3) PLEASE HAVE JOB ADDRESS ADDED TO
 TITLE BLOCK, PER 2004 FBC 106.1.1 .
  
 4) PLEASE SHOW SIZE OF ALL RETURN AIR
 TRANSFER DUCTS, SEE NOTE #5 (A).
  
 5) BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.