Plan Review Stops For Permit 06070082 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-10-02 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-10-02 |
Time |
17:00 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-09-28 |
Time |
15:42 |
Sent To |
|
|
Notes |
2006-10-02 00:00:00 | PLS ATTACH PERMIT TO THE CORRECT ADDRESS | | :1652 MERCER AVE | 2006-09-28 00:00:00 | APPL. AND RESUB FORMS READ 1652 MERCER | | AVE.COPY OF RESUB FORM SENT TO LILI |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-10-20 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-10-20 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-10-20 |
Time |
16:01 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-07-28 |
Time |
09:23 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-07-28 |
Time |
09:23 |
Sent To |
|
|
Notes |
2006-07-28 00:00:00 | DENIED | | | | ENGINEERING SUBMITTED FROM HILLMAN | | ENGINEERING SHALL BE SIGN AND SEALED. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-26 |
Time |
10:44 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-26 |
Time |
10:43 |
Sent To |
PC |
|
Notes |
2007-02-26 11:24:19 | MOVED ATS LOCATION,ATS CONTAINS A DISCONNECTING MEANS | | FOR BOTH NORMAL AND EMERGENCY SIDE. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-10-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-15 |
Time |
17:06 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-15 |
Time |
16:52 |
Sent To |
|
|
Notes |
2006-10-15 17:07:46 | BRKR AT GEN OK FOR MEANS OF DISCONNECT . MUST BE | | READILY ACCESSIBLE AND WITHIN SIGHT. OK PER CHIEF | | ELECTRICAL INSPECTOR. AS NEW CODE 2005 ALLOWS THIS |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-07-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-07-21 |
Time |
13:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-07-21 |
Time |
13:37 |
Sent To |
|
|
Notes |
2006-07-21 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE ADDRESS IS FOR | | "OKEECHOBEE RD" PLEASE KNOW, LEGALLY | | THERE IS NOT 'OLD " OKEECHOBEE IN THE | | CITY OF WEST PALM BEACH. | | PLEASE PLACE ADDRESS ON PLANS. | | 1259 OKEECHOBEE RD. | | | | 2) NOTE: PLEASE SEE RISER DIAGRAM SHOWN A | | SE RATED ATS , HOWEVER PLEASE SEE SPEC | | SUBMITTED ARE HIGH LIGHTED FOR A NON-SSE | | RATED ATS.? | | PLEASE CLARIFY. | | PLEASE ALSO CLARIFY OF THE EXISTING MAIN | | SHOWN ON RISER IS NEXT TO OR GROUPED IN | | CLOSE PROXIMITY TO NEW ATS/ SE RATED | | MAIN. | | 230.72,225.34 | | 110.3,90.7 | | | | 3) NOTE: PLEASE SEE AN "EQUIPMENT | | GROUNDING CONDUCTOR IS BEING SHOWN FROM | | METER TO THE FIRST MEANS OF DISCONNET, | | HOWEVER PER 250.6,250.24, ONLY AFTER THE | | FIRST MEANS OF DISCONNECT, DOES AN | | EQUIPMENT GROUNDING CONDUCTOR GET | | INSTALLED. | | | | 4) NOTE: PLEASE KNOW, AS PER INFORMATION | | OBTAINED BY THE OFFICE, THE MIN | | CLEARENCES FOR THESE TYPE OF GEN SHOULD | | BE 5' FROM ALL WALLS BLDGS ETC. PLEASE | | KNOW, IF INFORMATION IS NOT THE SAME | | PLEASE PROVIDE SPECIFIC DISTANCES | | REQUIRED BY MANUFACTURE. | | | | 5) NOTE: PLEASE VERIFY AIC RATINGS. | | 702.6,110.9 ETC. | | | | 6) NOTE: PLEASE SEE THAT SURVEY/ SITE | | PLAN SHALL NOT CONTAIN HANDWRITTEN, PEN | | OR PENCILED PLANS. | | PLEASE REPRINT AND COPY IF NEEDED. | | FBC 106.1.2,1.3 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-11-02 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-02 |
Time |
10:30 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-02 |
Time |
10:30 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-08-22 |
Time |
13:07 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-08-22 |
Time |
13:07 |
Sent To |
|
|
Notes |
2006-08-22 00:00:00 | **UNSAT** | | | | | | | | | | 1.) THE CORRECT ADDRESS OF THE PROPERTY | | WHERE THE SCOPE OF THE WORK TO BE DONE | | MUST BE ON THE APPLICATION/PERMIT. GIS | | AND WPBFR RECOGNIZE THIS BUILDING AS | | HAVING A MERCER AVENUE ADDRESS. | | | | | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 | | |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
N |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-22 |
Time |
16:19 |
Rev Time |
|
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
|
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2006-08-14 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2006-08-09 |
Time |
13:18 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2006-08-09 |
Time |
13:18 |
Sent To |
|
|
Notes |
2006-08-09 00:00:00 | NOT REQUIRED AT THIS TIME | | REFERENCE: FBC-2004 FUEL GAS | | | | A. SEPARATE GAS PERMIT REQUIRED. | | APPLICATION & INFORMATION FOR GAS PERMIT | | TO BE SUBMITTED WITH GAS APPLICATION. | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | GENERATOR SUBMITTAL SHEET INDICATES | | NATURAL GAS, BUT INFORMATION TO BE | | INDICATED ON GAS PERMIT APPLICATION | | INFORMATION. | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. NOT USED. | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | LOCATION, SIZE AND TERMINATION OF THE | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | SECS. 502 THRU 505. | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | INCLUDING THE INFORMATION FOR MINIMUM | | DISTANCE FROM WALLS, STRUCTURES ETC. PER | | MANUF. INSTALLATION INSTRUCTIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6721 | | E-MAIL [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-12-18 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-18 |
Time |
10:45 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-18 |
Time |
10:45 |
Sent To |
Z |
|
Notes |
2006-12-18 10:46:16 | TO "Z" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-28 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-28 |
Time |
15:42 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-28 |
Time |
15:42 |
Sent To |
|
|
Notes |
2006-10-13 15:03:42 | TO "COMM" BD#35 | 2006-09-28 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-08-22 |
Time |
13:06 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-07-06 |
Time |
15:11 |
Sent To |
|
|
Notes |
2006-07-19 00:00:00 | TO "COMM" BD#3 | 2006-07-06 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-08-22 |
Time |
16:21 |
Rev Time |
|
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
P |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-12-22 |
Time |
16:19 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-12-22 |
Time |
16:19 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-11-08 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-11-08 |
Time |
16:33 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-11-07 |
Time |
18:38 |
Sent To |
I |
|
Notes |
2006-11-13 16:34:56 | PLANNING AND ZONING: ***** FAILED ***** | | | | 1.PROVIDE RESPONSE TO COMMENTS IN WRITING. | | | | 2. THE ENLARGED DETAIL ON THE (8 1/2 X 11 SHEET) , | | PROVIDED SHOWS A PROPOSED FENCE TO FULFILL THE | | SCREENING REQUIREMENT FOR THE GENERATOR.HOWEVER, THE | | APPLICANT SHALL APPLY FOR A FENCE PERMIT PRIOR TO FINAL | | ZONING APPROVAL OF THIS GENERATOR PERMIT. | | | | NOTE:NO C.O. WILL BE GIVEN UNTILLANDSCAPE AND FENCE | | ARE IN PLACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT ME AT THE NUMBER BELOW. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1435 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-07-31 |
|
|
Cont ID |
|
Sent By |
lfranco |
Date |
2006-07-31 |
Time |
18:02 |
Rev Time |
0.00 |
Received By |
lfranco |
Date |
2006-07-31 |
Time |
18:02 |
Sent To |
I |
|
Notes |
2006-07-31 00:00:00 | PLANNING AND ZONING DEPARTMENT:FAILED | | | | 1.PROVIDE A BETTER DETAIL OF THE AREA | | WHERE THE GENERATOR IS PROPOSED, NOT AN ENLARGEMENT. | | THE SURVEY SHALL INCLUDE | | THE FOLLOWING: | | | | A. SCREENING AND ELEVATION OF | | WALL/HEDGES AROUND GENERATOR/ FUEL TANK, | | AND SETBACK DISTANCE FROM PROPERTY | | LINE. | | | | 2.PURSUANT TO SECTION 94-444(B) OPEN | | SPACE STANDARDS: | | (B) FUEL OR OIL OR PROPANE | | TANKS, GENERATORS SHALL NOT BE PERMITTED | | UNLESS APPROPRIATE SCREENING IS | | PROVIDED. SCREENING SHALL BE CONSTRUCTED | | OF BRICK, DECORATIVE CONCRETE, OTHER | | DECORATIVE MASONRY, OR COMPARABLY | | DURABLE WOOD AND STEEL. | | | | WALLS SHALL BE LANDSCAPED WITH SHRUBS | | AND HEDGES PLANTED AT TWO-FOOT | | INTERVALS.A FOUR-SIDED ENCLOSURE | | WITH MASONRY, OR COMPARABLY DURABLE WOOD | | AND STEEL, AN OBSCURING GATE IS REQUIRED | | AS A CONDITION FOR SITE PLAN APPROVAL. | | | | THE SCREENING SHALL ENCLOSE BOTH FUEL | | TANK INCLUDING ROOFTOP EXHAUST (TANK, IF APPLICABLE AND | | GENERATOR. | | | | 3.PURSUANT TO SECTION 94-305(B)(4) | | SETBACKS | | (B)(4) SETBACK ENCROACHMENT: | | MECHANICAL EQUIPMENT SHALL NOT PROJECT | | MORE THAN 4 FEET INTO A SETBACK. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT ME AT THE NUMBER BELOW. | | | | LINDA MIA FRANCO | | SENIOR PLANNER | | PLANNING AND ZONING DEPARTMENT | | TEL: (561) 822-1435 |
|
|