Plan Review Details - Permit 06070082
Plan Review Stops For Permit 06070082
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-10-02 Cont ID  
Sent By lursu Date 2006-10-02 Time 17:00 Rev Time 0.00
Received By lursu Date 2006-09-28 Time 15:42 Sent To  
Notes
2006-10-02 00:00:00PLS ATTACH PERMIT TO THE CORRECT ADDRESS
 :1652 MERCER AVE
2006-09-28 00:00:00APPL. AND RESUB FORMS READ 1652 MERCER
 AVE.COPY OF RESUB FORM SENT TO LILI

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-20 Cont ID  
Sent By alange Date 2006-10-20 Time 16:01 Rev Time 0.00
Received By alange Date 2006-10-20 Time 16:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-28 Cont ID  
Sent By alange Date 2006-07-28 Time 09:23 Rev Time 0.00
Received By alange Date 2006-07-28 Time 09:23 Sent To  
Notes
2006-07-28 00:00:00DENIED
  
 ENGINEERING SUBMITTED FROM HILLMAN
 ENGINEERING SHALL BE SIGN AND SEALED.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-26 Cont ID  
Sent By dpalmer Date 2007-02-26 Time 10:44 Rev Time 0.00
Received By dpalmer Date 2007-02-26 Time 10:43 Sent To PC
Notes
2007-02-26 11:24:19MOVED ATS LOCATION,ATS CONTAINS A DISCONNECTING MEANS
 FOR BOTH NORMAL AND EMERGENCY SIDE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-15 Cont ID  
Sent By dpalmer Date 2006-10-15 Time 17:06 Rev Time 0.00
Received By dpalmer Date 2006-10-15 Time 16:52 Sent To  
Notes
2006-10-15 17:07:46BRKR AT GEN OK FOR MEANS OF DISCONNECT . MUST BE
 READILY ACCESSIBLE AND WITHIN SIGHT. OK PER CHIEF
 ELECTRICAL INSPECTOR. AS NEW CODE 2005 ALLOWS THIS

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 13:58 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 13:37 Sent To  
Notes
2006-07-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE ADDRESS IS FOR
 "OKEECHOBEE RD" PLEASE KNOW, LEGALLY
 THERE IS NOT 'OLD " OKEECHOBEE IN THE
 CITY OF WEST PALM BEACH.
 PLEASE PLACE ADDRESS ON PLANS.
 1259 OKEECHOBEE RD.
  
 2) NOTE: PLEASE SEE RISER DIAGRAM SHOWN A
 SE RATED ATS , HOWEVER PLEASE SEE SPEC
 SUBMITTED ARE HIGH LIGHTED FOR A NON-SSE
 RATED ATS.?
 PLEASE CLARIFY.
 PLEASE ALSO CLARIFY OF THE EXISTING MAIN
 SHOWN ON RISER IS NEXT TO OR GROUPED IN
 CLOSE PROXIMITY TO NEW ATS/ SE RATED
 MAIN.
 230.72,225.34
 110.3,90.7
  
 3) NOTE: PLEASE SEE AN "EQUIPMENT
 GROUNDING CONDUCTOR IS BEING SHOWN FROM
 METER TO THE FIRST MEANS OF DISCONNET,
 HOWEVER PER 250.6,250.24, ONLY AFTER THE
 FIRST MEANS OF DISCONNECT, DOES AN
 EQUIPMENT GROUNDING CONDUCTOR GET
 INSTALLED.
  
 4) NOTE: PLEASE KNOW, AS PER INFORMATION
 OBTAINED BY THE OFFICE, THE MIN
 CLEARENCES FOR THESE TYPE OF GEN SHOULD
 BE 5' FROM ALL WALLS BLDGS ETC. PLEASE
 KNOW, IF INFORMATION IS NOT THE SAME
 PLEASE PROVIDE SPECIFIC DISTANCES
 REQUIRED BY MANUFACTURE.
  
 5) NOTE: PLEASE VERIFY AIC RATINGS.
 702.6,110.9 ETC.
  
 6) NOTE: PLEASE SEE THAT SURVEY/ SITE
 PLAN SHALL NOT CONTAIN HANDWRITTEN, PEN
 OR PENCILED PLANS.
 PLEASE REPRINT AND COPY IF NEEDED.
 FBC 106.1.2,1.3
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By mawillia Date 2006-11-02 Time 10:30 Rev Time 0.00
Received By mawillia Date 2006-11-02 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-22 Cont ID  
Sent By mawillia Date 2006-08-22 Time 13:07 Rev Time 0.00
Received By mawillia Date 2006-08-22 Time 13:07 Sent To  
Notes
2006-08-22 00:00:00**UNSAT**
  
  
  
  
 1.) THE CORRECT ADDRESS OF THE PROPERTY
 WHERE THE SCOPE OF THE WORK TO BE DONE
 MUST BE ON THE APPLICATION/PERMIT. GIS
 AND WPBFR RECOGNIZE THIS BUILDING AS
 HAVING A MERCER AVENUE ADDRESS.
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By dpalmer Date 2006-08-22 Time 16:19 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-08-14 Cont ID  
Sent By kstevens Date 2006-08-09 Time 13:18 Rev Time 0.00
Received By kstevens Date 2006-08-09 Time 13:18 Sent To  
Notes
2006-08-09 00:00:00NOT REQUIRED AT THIS TIME
 REFERENCE: FBC-2004 FUEL GAS
  
 A. SEPARATE GAS PERMIT REQUIRED.
 APPLICATION & INFORMATION FOR GAS PERMIT
 TO BE SUBMITTED WITH GAS APPLICATION.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
 GENERATOR SUBMITTAL SHEET INDICATES
 NATURAL GAS, BUT INFORMATION TO BE
 INDICATED ON GAS PERMIT APPLICATION
 INFORMATION.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. NOT USED.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INCLUDING THE INFORMATION FOR MINIMUM
 DISTANCE FROM WALLS, STRUCTURES ETC. PER
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6721
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-18 Cont ID  
Sent By adarroug Date 2006-12-18 Time 10:45 Rev Time 0.00
Received By adarroug Date 2006-12-18 Time 10:45 Sent To Z
Notes
2006-12-18 10:46:16TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-28 Cont ID  
Sent By adarroug Date 2006-09-28 Time 15:42 Rev Time 0.00
Received By adarroug Date 2006-09-28 Time 15:42 Sent To  
Notes
2006-10-13 15:03:42TO "COMM" BD#35
2006-09-28 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By mawillia Date 2006-08-22 Time 13:06 Rev Time 0.00
Received By mawillia Date 2006-07-06 Time 15:11 Sent To  
Notes
2006-07-19 00:00:00TO "COMM" BD#3
2006-07-06 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-22 Cont ID  
Sent By dpalmer Date 2006-08-22 Time 16:21 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2006-12-22 Cont ID  
Sent By lfranco Date 2006-12-22 Time 16:19 Rev Time 0.00
Received By lfranco Date 2006-12-22 Time 16:19 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-08 Cont ID  
Sent By lfranco Date 2006-11-08 Time 16:33 Rev Time 0.00
Received By lfranco Date 2006-11-07 Time 18:38 Sent To I
Notes
2006-11-13 16:34:56PLANNING AND ZONING: ***** FAILED *****
  
 1.PROVIDE RESPONSE TO COMMENTS IN WRITING.
  
 2. THE ENLARGED DETAIL ON THE (8 1/2 X 11 SHEET) ,
 PROVIDED SHOWS A PROPOSED FENCE TO FULFILL THE
 SCREENING REQUIREMENT FOR THE GENERATOR.HOWEVER, THE
 APPLICANT SHALL APPLY FOR A FENCE PERMIT PRIOR TO FINAL
 ZONING APPROVAL OF THIS GENERATOR PERMIT.
  
 NOTE:NO C.O. WILL BE GIVEN UNTILLANDSCAPE AND FENCE
 ARE IN PLACE.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By lfranco Date 2006-07-31 Time 18:02 Rev Time 0.00
Received By lfranco Date 2006-07-31 Time 18:02 Sent To I
Notes
2006-07-31 00:00:00PLANNING AND ZONING DEPARTMENT:FAILED
  
 1.PROVIDE A BETTER DETAIL OF THE AREA
 WHERE THE GENERATOR IS PROPOSED, NOT AN ENLARGEMENT.
 THE SURVEY SHALL INCLUDE
 THE FOLLOWING:
  
 A. SCREENING AND ELEVATION OF
 WALL/HEDGES AROUND GENERATOR/ FUEL TANK,
 AND SETBACK DISTANCE FROM PROPERTY
 LINE.
  
 2.PURSUANT TO SECTION 94-444(B) OPEN
 SPACE STANDARDS:
 (B) FUEL OR OIL OR PROPANE
 TANKS, GENERATORS SHALL NOT BE PERMITTED
 UNLESS APPROPRIATE SCREENING IS
 PROVIDED. SCREENING SHALL BE CONSTRUCTED
 OF BRICK, DECORATIVE CONCRETE, OTHER
 DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL.
  
 WALLS SHALL BE LANDSCAPED WITH SHRUBS
 AND HEDGES PLANTED AT TWO-FOOT
 INTERVALS.A FOUR-SIDED ENCLOSURE
 WITH MASONRY, OR COMPARABLY DURABLE WOOD
 AND STEEL, AN OBSCURING GATE IS REQUIRED
 AS A CONDITION FOR SITE PLAN APPROVAL.
  
 THE SCREENING SHALL ENCLOSE BOTH FUEL
 TANK INCLUDING ROOFTOP EXHAUST (TANK, IF APPLICABLE AND
 GENERATOR.
  
 3.PURSUANT TO SECTION 94-305(B)(4)
 SETBACKS
 (B)(4) SETBACK ENCROACHMENT:
 MECHANICAL EQUIPMENT SHALL NOT PROJECT
 MORE THAN 4 FEET INTO A SETBACK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435