Plan Review Stops For Permit 06070078 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-09-27 |
Time |
09:35 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-09-27 |
Time |
09:35 |
Sent To |
|
|
Notes |
2006-09-27 00:00:00 | EXT#0019 WAS CREATED FOR THIS UNIT 801. | 2006-07-21 00:00:00 | PLEASE SEE ONE CURRENT SPACE IS BEING | | CONVERTED TO THREE NEW TENANT SPACES. |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
P |
Date |
2006-07-31 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-07-31 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-07-31 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
P |
Date |
2006-11-17 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-17 |
Time |
14:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-17 |
Time |
14:22 |
Sent To |
FIRE |
|
Notes |
2006-11-17 14:29:20 | ROUTED TO FIRE AS THERE ARE NEW SHEETS WHICH DO NOT | | CONTAIN ANY STAMPS FROM FIRE REVIEWER. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2006-10-25 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-25 |
Time |
12:19 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-25 |
Time |
12:07 |
Sent To |
|
|
Notes |
2006-10-25 12:19:37 | **** UNSAT 3RD REVIEW ****** | | | | ** PLEASE SEE COMMENT(S) FROM PREVIOUS REVIEWS WHICH | | STILL NEED TO BE ADDRESSED. | | PLEASE SEE NOTES BELOW WHICH ARE TAKEN FROM PREVIOUS | | TWO REVIEWS. | | | | | | ** PLEASE SEE SOME COMMENTS BELOW ARE | | STILL IN NEED OF ADDRESSING. PLEASE SEE | | NOTES BELOW WHICH ARE TAKEN DIRECTLY | | FROM THE PREVIOUS REVIEW WITH NEW NOTES | | ADDED. | | | | 1) NOTE:NO, PLEASE SEE SHEETS 2.1, 3.1, 4.1, 5.1 AND | | 6.1 STILL DO NOT CORRELATE WITH PANEL AND EQUIPMENT | | IDENTIFICATION. PLEASE SEE SOME SHEETS SHOWS DIFFERENT | | DESIGNATIONS, SOME HAVE SHOW OTHER ETC. | | PLEASE CORRELATE AND SHOW ALL EQUIPMENT ON PLANS. | | FBC 106.1.2, 106.3.5.1.2, NEC 2002 | | | | ** PREVIOUS REVIEW NOTE REVIEW #2. ** | | NO, PLEASE SEE DESIGNATIONS ON | | PLANS FOR PANELS ARE NOT COMPLETE AND | | NOT ALL CORRELATE WITH RISER AND PANEL | | SCHEDULES. | | | | ** PREVIOUS REVIEW NOTE, REVIEW #1** | | PLEASE CORRELATE PLANS, RISER | | AND PANEL SCHEDULES. | | PLEASE SEE PLANS SHOWS PANEL R-8, P* AND | | SEE RISER SHOWS L8A, R8B, AND PANEL | | SCHEDULE SHOW P8B L8A. | | 106.1.2 FBC | | | | ** NEW NOTE ** | | | | 2) NOTE; PLEASE SEE A PREVIOUS NOTE WAS GIVEN WITH | | RESPECT TO REPEAT COMMENTS FOR PLAN REVIEW PER FS | | 553.80(2)(B). | | PLEASE KNOW AT THIS TIME A FEE FOR THE PLAN REVIEW | | PORTION OF THE PERMIT FEE HAS NOW BEEN ASSESSED AS | | REQUIRED PER FLORIDA STATUTES. | | PLEASE SEE THE FEE OF $1,380.00 MUST BE PAID BEFORE | | RESUBMITTING PLANS. | | ** PLEASE ALSO KNOWONE SET OF PLANS FROM EACH OF THE | | THREE SETS REVIEW ARE NOW RETAINED BY THIS OFFICE. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-09-26 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-26 |
Time |
16:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-26 |
Time |
15:23 |
Sent To |
AD |
|
Notes |
2006-09-26 00:00:00 | ***** UNSAT 2ND REVIEW ***** | | | | ** PLEASE SEE SOME COMMENTS BELOW ARE | | STILL IN NEED OF ADDRESSING. PLEASE SEE | | NOTES BELOW WHICH ARE TAKEN DIRECTLY | | FROM THE PREVIOUS REVIEW WITH NEW NOTES | | ADDED. | | | | | | | | 1) NOTE:NO, PLEASE SEE DESIGNATIONS ON | | PLANS FOR PANELS ARE NOT COMPLETE AND | | NOT ALL CORRELATE WITH RISER AND PANEL | | SCHEDULES. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE CORRELATE PLANS, RISER | | AND PANEL SCHEDULES. | | PLEASE SEE PLANS SHOWS PANEL R-8, P* AND | | SEE RISER SHOWS L8A, R8B, AND PANEL | | SCHEDULE SHOW P8B L8A. | | 106.1.2 FBC | | | | 2) NOTE:OK, HOWEVER STILL NEED TO | | CORRELATE WITH CHANGES. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE TRANSFORMER FOR | | EXISTING PANEL NOTED ABOVE COULD NOT BE | | LOCATED. | | IF EXISTING, PLEASE ALSO IDENTIFY ON | | TRANSFORMER SCHEDULE (EVEN IF EXISTING | | ). | | 106.1.2 FBC, 90.7 | | | | 3) NOTE: OK. | | | | 4) NOTE:NO, CODES FOR DESIGN AND | | PERMITTING OF PROJECT IS REQUIRED ON | | PLANS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE THAT PLANS REFLECT | | THE FOLLOWING CODES AT A MIN. | | 2002 NFPA-70, 2002 NFPA-72, 2003 | | NFPA-101 | | | | 5) NOTE: NO, PLEASE SEE THIS IS FOR ALL | | SHEETS AND FOR ALL TRADES WHETHER OR | | NOT COMMENT IS MADE BY OTHER TRADES. | | PLEASE KNOW, FOR SHEETS WHICH DO NOT | | NEED CHANGING, THESE MAY SIMPLY BE | | RESIGNED. | | | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE HAVE ENGINEER SIGN PLANS | | WITHHIS RECOGNIZED SIGNATURE AND THAT | | OF WHICH IS ONFILE WITH THE CITY OF | | WEST PALM BEACH. | | | | 5) NOTE: PLEASE SEE NOTICE WITH RESPECT | | TO FS 553.80(2)9B)IS ONLY GIVEN AS A | | NOTICE AT THIS TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-07-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-07-21 |
Time |
17:41 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-07-21 |
Time |
16:38 |
Sent To |
|
|
Notes |
2006-07-21 00:00:00 | ******* UNSAT ********* | | | | 1) NOTE: PLEASE CORRELATE PLANS, RISER | | AND PANEL SCHEDULES. | | PLEASE SEE PLANS SHOWS PANEL R-8, P* AND | | SEE RISER SHOWS L8A, R8B, AND PANEL | | SCHEDULE SHOW P8B L8A. | | 106.1.2 FBC | | | | 2) NOTE: PLEASE SEE TRANSFORMER FOR | | EXISTING PANEL NOTED ABOVE COULD NOT BE | | LOCATED. | | IF EXISTING, PLEASE ALSO IDENTIFY ON | | TRANSFORMER SCHEDULE (EVEN IF EXISTING | | ). | | 106.1.2 FBC, 90.7 | | | | 3) NOTE: PLEASE SEE 240.21 408.16 AS A | | NOTED ON TRANSFORMER SCHEDULE MENTIONS | | FOR THE MAINS ON THE PANELS ON THE | | SECONDARY SIDE OF TRANSFORMER TO BE THE DISCONNECTING | | MENAS, HOWEVER PLEASE SEE | | PANELS AS TWO ARE SHOWN AS MLO> | | | | 4) NOTE: PLEASE SEE THAT PLANS REFLECT | | THE FOLLOWING CODES AT A MIN. | | 2002 NFPA-70, 2002 NFPA-72, 2003 | | NFPA-101 | | | | 5) NOTE: PLEASE HAVE ENGINEER SIGN PLANS | | WITHHIS RECOGNIZED SIGNATURE AND THAT | | OF WHICH IS ONFILE WITH THE CITY OF | | WEST PALM BEACH. | | | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND BEFORE | | RESUBMITTING PLANS. PLEASE BE SURE TO | | COMPLETELY REMOVED ANY OLD/VOIDED SHEETS | | AND ONLY INSERT NEW REVISED SHEETS INTO | | COMPLETE SETS FOR REVIEW AND STAMPING. | | PLEASE ONLY SUBMIT ONE SET OF THE OLD | | VOIDED SHEETS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-11-27 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-27 |
Time |
12:34 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-27 |
Time |
12:12 |
Sent To |
|
|
Notes |
2006-11-27 12:40:36 | *****RETURNED TO DEWEW PALMER FOR PROCESSING****** |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-11-06 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-06 |
Time |
15:28 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-06 |
Time |
15:28 |
Sent To |
|
|
Notes |
2006-11-06 15:41:34 | *****APPROVED***** | | | | | | | | PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW THE | | FIRE PLAN REVIEW COMMENTS OF 08/18/2006 WERE ADDRESSED. | | PLANS WILL BE STAMPED WHEN ITEMS HAVE BEEN | | ACKNOWLEDGED. | | | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
P |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-08-18 |
Time |
14:55 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-08-18 |
Time |
13:54 |
Sent To |
|
|
Notes |
2006-08-18 00:00:00 | **ATTENTION** | | | | | | | | 1.) NFPA 241 SHALL BE ADHERED TO DURING | | CONSTRUCTIONS, ALTERATION, AND | | DEMOLITION OPERATIONS. | | | | 2.) WHERE THE BUILDING IS PROTECTED BY | | FIRE PROTECTION SYSTEMS, SYSTEMS SHALL | | BE MAINTAINED OPERATIONAL AT ALL TIMES | | DURING ALTERATION. | | | | 3.) PROVIDE PERMIT AND SHOP DRAWINGS FOR | | FIRE SPRINKLER AND(OR) FIRE ALARM | | REMODEL. | | | | 4.) WPBFR SHALL BE NOTIFIED IF FIRE | | PROTECTION SYSTEM IS SHUT DOWN AND WHEN | | THE SYSTEM IS RETURNED TO SERVICE. | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2006-11-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-15 |
Time |
15:37 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-15 |
Time |
15:37 |
Sent To |
E |
|
Notes |
2006-11-15 15:37:24 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-10-20 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-20 |
Time |
13:41 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-20 |
Time |
13:41 |
Sent To |
|
|
Notes |
2006-10-24 16:12:05 | TO "COMM" BD#46 | 2006-10-20 13:41:23 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-19 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-19 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-19 |
Time |
16:08 |
Sent To |
E |
|
Notes |
2006-09-19 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-08-18 |
Time |
13:53 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-07-06 |
Time |
15:58 |
Sent To |
|
|
Notes |
2006-07-19 00:00:00 | TO "COMM" BD#5 | 2006-07-06 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2006-08-22 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-22 |
Time |
10:49 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-08-22 |
Time |
10:49 |
Sent To |
|
|
Notes |
|
|