Plan Review Details - Permit 06070058
Plan Review Stops For Permit 06070058
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-24 Cont ID  
Sent By amorse Date 2006-08-24 Time 12:12 Rev Time 0.00
Received By amorse Date 2006-08-24 Time 12:12 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By amorse Date 2006-08-08 Time 14:32 Rev Time 0.00
Received By amorse Date 2006-08-08 Time 14:32 Sent To M
Notes
2006-08-08 00:00:00 
  
 DENIED
  
 1) OWNER BUILDER DISCLOSURE STATEMENT IS
 MISSING FROM SUBMITTAL PLEASE RESUBMIT
 OR FILL OUT NEW STATEMENT
  
 2) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 4) PLEASE SEE ZONING COMMENTS
 (PROVIDE 2 COPIES OF SURVEY)
  
 5) SEE ADDITONAL MECHANICAL COMMENTS AS
 NO MECH REVIEW WAS PERFORMED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-17 Cont ID  
Sent By amorse Date 2006-07-17 Time 07:04 Rev Time 0.75
Received By amorse Date 2006-07-17 Time 07:04 Sent To PC
Notes
2006-07-17 00:00:00 
  
 DENIED
  
 1) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC
  
 2) THE STATE OF FLORIDA REQUIRES
 COLLECTION OF A RADON SURCHARGE ON ALL
 NEW CONSTRUCTION COMPUTED ON UNDER ROOF
 FLOOR SPACE PER 10D-91 FAC
  
 3) BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 4) IN AREAS OF QUESTIONABLE SOILS AS
 SHOWN IN THE OFFICIAL ZONING MAP ADOPTED
 BY THE CITY OF WEST PALM BEACH, A SOIL
 TEST REPORT SHALL BE SUBMITTED PER
 R401.4 FBC
  
 5) SUBMIT ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT
 APPLICATION OR BEFORE INSTALLATION
  
 6) THE PERMIT APPLICATION SHALL INCLUDE
 TWO COPIES OF EACH PRODUCT APPROVAL THAT
 IS RELEVANT PER 9B-72. THESE SHOULD
 INCLUDE THE FLORIDA STATE APPROVAL COVER
 PAGES, AND THE PRODUCT NOA THAT LISTS
 THE SYSTEM COMPONENTS/ FASTENER LIST
 PAGES, THE PAGES WITH THE CHOSEN
 ASSEMBLY/ SYSTEM TO BE USED AND THE
 GENERAL LIMITATIONS PAGE. ALL CAN BE
 FOUND ON WWW.FLORIDABUILDING.ORG
  
 7) THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By btrobaug Date 2006-08-08 Time 11:25 Rev Time 0.33
Received By btrobaug Date 2006-08-08 Time 11:20 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-14 Cont ID  
Sent By btrobaug Date 2006-07-14 Time 07:15 Rev Time 0.33
Received By btrobaug Date 2006-07-14 Time 07:08 Sent To B
Notes
2006-07-14 00:00:00 
 NONCOMPLIANT
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-22 Cont ID  
Sent By adarroug Date 2006-08-22 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-08-22 Time 13:58 Sent To M
Notes
2006-08-22 00:00:00TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-16 Cont ID  
Sent By adarroug Date 2006-08-16 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-08-16 Time 14:30 Sent To Z
Notes
2006-08-16 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-07 Cont ID  
Sent By adarroug Date 2006-08-07 Time 14:30 Rev Time 0.00
Received By adarroug Date 2006-08-07 Time 14:30 Sent To E
Notes
2006-08-07 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-01 Cont ID  
Sent By adarroug Date 2006-08-01 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-08-01 Time 14:49 Sent To Z
Notes
2006-08-01 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 16:23 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 16:23 Sent To E
Notes
2006-07-10 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-17 Time   Rev Time 0.00
Received By adarroug Date 2006-07-06 Time 14:38 Sent To  
Notes
2006-07-06 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-08-24 Cont ID  
Sent By tgordon Date 2006-08-24 Time 13:41 Rev Time 0.15
Received By tgordon Date 2006-08-24 Time 13:41 Sent To Z
Notes
2006-08-24 00:00:00NO MECHANICAL PLANS SUBMITTED, AND
 MECHANICAL PERMIT NUMBER 06070062 WAS
 VOIDED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-09 Cont ID  
Sent By tgordon Date 2006-08-09 Time 08:28 Rev Time 0.20
Received By tgordon Date 2006-08-09 Time 08:28 Sent To  
Notes
2006-08-09 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06070062 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop Z ZONING
Rev No 4 Status P Date 2006-08-26 Cont ID  
Sent By mmclean Date 2006-08-26 Time 13:52 Rev Time 0.00
Received By mmclean Date 2006-08-26 Time 13:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2006-08-19 Cont ID  
Sent By mmclean Date 2006-08-19 Time 15:45 Rev Time 0.00
Received By mmclean Date 2006-08-19 Time 15:45 Sent To  
Notes
2006-08-19 00:00:00DENIED, - 3RD REQUEST.
 1. MUST SHOW THE LOCATION OF THE
 PROPOSED WORK ON TWO COPY OF SURVEY WITH
 SETBACKS (SIDE & REAR).
 2. SEVERAL SURVEY SUBMITTED, BUT NO
 PROPOSED WORK SHOWN ON THE COPIES OF
 SURVEYS.
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By mmclean Date 2006-08-05 Time 09:15 Rev Time 0.00
Received By mmclean Date 2006-08-05 Time 09:15 Sent To I
Notes
2006-08-05 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF THE
 PROPOSED WORK ON TWO COPY OF SURVEY WITH
 SETBACKS (SIDE & REAR).
 2. SURVEY NOT SUBMITTED IN PACKAGE.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-09 Cont ID  
Sent By mmclean Date 2006-07-09 Time 17:38 Rev Time 0.00
Received By mmclean Date 2006-07-09 Time 17:38 Sent To I
Notes
2006-07-09 00:00:00DENIED,
 1. MUST SHOW THE LOCATION OF THE
 PROPOSED WORK ON TWO COPY OF SURVEY WITH
 SETBACKS (SIDE & REAR).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720