Plan Review Details - Permit 06070032
Plan Review Stops For Permit 06070032
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-01 Cont ID  
Sent By shill Date 2006-09-01 Time 09:41 Rev Time 0.00
Received By shill Date 2006-09-01 Time 09:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By shill Date 2006-08-05 Time 10:45 Rev Time 0.00
Received By shill Date 2006-08-05 Time 10:45 Sent To  
Notes
2006-08-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 COMMENTS FROM FIRST REVIEW
  
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 PLEASE PROVIDE BUILDING HEIGHT.THE
 PLAN STATES <60'.NO EXPOSURE CATEGORY
 WAS GIVEN.IF THE BUILDING IS 59',
 EXPOSURE C, THE DESIGN PRESSURE FOR THE
 24X50 OPENING IS -76.46.IF THE
 BUILDING IS 29', EXPOSURE B, THE SAME
 OPENING HAS A DP OF -47.2.THE
 PRESSURES ARE DETERMINED BY BUILDING
 HEIGHT, NOT OPENING LOCATION (INDICATED
 AS FIRST FLOOR).SEE FBC TABLE 1609.6B.
 I CAN DETERMINE DESIGN PRESSURES FOR YOU
 BUT YOU MUST PROVIDE THE REQUESTED
 INFORMATION.
  
 _XX_6.ON THE PRODUCT APPROVAL, MARK
 WHICH DETAILS APPLY TO THIS JOB.PLEASE
 USE INK RATHER THAN A HIGHLIGHTER.
  
 IT IS NOT CLEAR IF THE ANCHORING
 SPECIFIED IS CODE COMPLIANT.PLEASE
 CIRCLE APPROPRIATE NUMBER ON THE
 ANCHORING CHART.SOME CONNECTION TYPES
 REQUIRE DIFFERENT SPACING.
  
 2ND REVIEW - SPANS DO NOT APPEAR TO BE
 CORRECT.OPENING 1 STATES THAT THE SPAN
 IS 155" WITH A VERTICAL INSTALLATION,
 BUT THE HEIGHT IS ONLY 96".YOU HAVE
 SPECIFIED 12" FOR THE BOTTOM ANCHORING,
 BUT CIRCLED 5" AND 6" ON THE PRODUCT
 APPROVAL WITH THE NOTE THAT THIS IS THE
 FLOOR TRACK..THERE ARE OTHER
 INCONSISTENCIES.ALL NOTES CIRCLED
 ARE FOR -47.2, NOTE THAT THIS WILL BE
 NONCOMPLIANT UNLESS THE BUILDING IS LESS
 THAN 30' IN EXPOSURE B.
  
 CODE COMPLIANCE CANNOT BE DETERMINED DUE
 TO CONFLICTING INFORMATION AND LACK OF
 INFORMATION TO DETERMINE DESIGN
 PRESSURES.
  
 PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-11 Cont ID  
Sent By shill Date 2006-07-11 Time 13:44 Rev Time 0.00
Received By shill Date 2006-07-11 Time 13:43 Sent To  
Notes
2006-07-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED
 ITEMS APPLY
  
 ____1.A NOTICE OF COMMENCEMENT MUST
 BE FILED WITH THE CLERK OF COURTS BEFORE
 A PERMIT CAN BE ISSUED, FS713.13.
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 _XX_3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 ____4.COMPLETE THE ATTACHED
 INSTALLATION SCHEDULE OR PROVIDE
 REQUIRED INFORMATION IN A SIMILAR
 FORMAT.YOU MAY SHOW ANCHOR SPACING BY
 CIRCLING IT ON THE APPROPRIATE CHARTS ON
 THE PRODUCT APPROVAL.PLEASE USE INK
 RATHER THAN HIGHLIGHTER.
  
 _XX_5.FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 THE SHEET PROVIDED IS A LIST OF ALL
 PRODUCTS FOR THIS MANUFACTURER.PROVIDE
 A COPY OF THE FLORIDA STATE PRODUCT
 APPROVAL.
  
 _XX_6.ON THE PRODUCT APPROVAL, MARK
 WHICH DETAILS APPLY TO THIS JOB.PLEASE
 USE INK RATHER THAN A HIGHLIGHTER.
  
 IT IS NOT CLEAR IF THE ANCHORING
 SPECIFIED IS CODE COMPLIANT.PLEASE
 CIRCLE APPROPRIATE NUMBER ON THE
 ANCHORING CHART.SOME CONNECTION TYPES
 REQUIRE DIFFERENT SPACING.
  
 _XX_7.SHOW THE EMERGENCY MEANS OF
 ESCAPE, FBC R310.
  
 _XX_8.PROVIDE A FLOOR PLAN SHOWING
 WHERE THE SHUTTERS WILL BE INSTALLED AND
 PANEL SIZES WHICH CORRELATES WITH THE
 INSTALLATION SCHEDULE, ITEM 4 ABOVE.
  
 _XX_ 9.PROVIDE TWO COMPLETE COPIES OF
 ALL DOCUMENTS.FOUR PRODUCT APPROVALS
 WERE SUBMITTED, BUT ONLY ONE SHUTTER
 INSTALLATION SCHEDULE.
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 18:29 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 18:29 Sent To B
Notes
2006-08-11 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 14:56 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 14:56 Sent To B
Notes
2006-07-31 00:00:00TO "SHILL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-11 Cont ID  
Sent By shill Date 2006-07-11 Time 13:52 Rev Time 0.00
Received By shill Date 2006-07-06 Time 10:03 Sent To  
Notes
2006-07-06 00:00:00TO "MISC" BOX#1