Plan Review Details - Permit 06061717
Plan Review Stops For Permit 06061717 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2007-01-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-09 |
Time |
18:02 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-01-09 |
Time |
18:00 |
Sent To |
|
|
Notes |
2007-01-09 18:03:22 | BUILDING PROVISO: | | | | 3001.1 SCOPE. | | THIS CHAPTER GOVERNS THE DESIGN, CONSTRUCTION, | | INSTALLATION, ALTERATION AND REPAIR OF ELEVATORS AND | | CONVEYING SYSTEMS AND THEIR COMPONENTS. | | | | NOTE: OTHER ADMINISTRATIVE AND PROGRAMMATIC PROVISIONS | | MAY APPLY. SEE THE DEPARTMENT OF BUSINESS AND | | PROFESSIONAL REGULATION [DBPR] CHAPTER 399, FLORIDA | | STATUTES, AND 61C-5, FLORIDA ADMINISTRATIVE CODE . THE | | REGULATION AND ENFORCEMENT OF THE FOLLOWING SECTIONS OF | | THE ADOPTED CODES, AND THEIR ADDENDA, ARE PREEMPTED TO | | THE BUREAU OF ELEVATOR SAFETY OF THE DEPARTMENT OF | | BUSINESS AND PROFESSIONAL REGULATION: ASME A 17.1, PART | | 8, ASME A17.3, SECTIONS 1.2, 1.5, ASME A 18.1, PART 10. | | | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-10-04 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-10-04 |
Time |
07:35 |
Rev Time |
0.88 |
Received By |
jwitmer |
Date |
2006-10-04 |
Time |
07:35 |
Sent To |
|
|
Notes |
2006-10-04 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06061717 | | ADD: 1001 OKEECHOBEE BLVD | | CONT: CHA TECH SERVICES, LLC | | TEL: (770)286-7297 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2ND REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT BEFORE A | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | 3) COMMENT# 7 FROM THE PREVIOUS REVIEW | | DEALS WITH THE CONDUITS IN THE | | STAIRWELL, THAT ARE ENCASED IN A 2 | | LAYERS OF ROCK, 1" FIRECORE C CORE PANEL | | AND 1/2" DRYWALL. PLEASE PROVIDE THE | | LISTING FOR A 2 HR ASSEMBLY. 703.2 | | FIRE-RESISTANCE RATINGS. | | | | THE SECOND ISSUE IS THE LOCATION OF | | THIS ASSEMBLY IN THE STAIRWELL. 1009.4 | | STAIRWAY LANDINGS. THERE SHALL BE A | | FLOOR OR LANDING AT THE TOP AND BOTTOM | | OF EACH STAIRWAY. THE WIDTH OF LANDINGS | | SHALL NOT BE LESS THAN THE WIDTH OF | | STAIRWAYS THEY SERVE. EVERY LANDING | | SHALL HAVE A MINIMUM DIMENSION MEASURED | | IN THE DIRECTION OF TRAVEL EQUAL TO THE | | WIDTH OF THE STAIRWAY. SUCH DIMENSION | | NEED NOT EXCEED 48 INCHES (1219 MM) | | WHERE THE STAIRWAY HAS A STRAIGHT RUN. | | E07 INDICATES THAT THE SHAFT | | ENCLOSURE WILL BE 8" AWAY FROM THE WALL | | BUT THE LENGTH IN NOTE# 1 IS AS NEEDED. | | THIS COULD BE ACROSS THE WHOLE LANDING. | | 1009.4 STATES THE WIDTH OF LANDINGS | | SHALL NOT BE LESS THAN THE WIDTH OF THE | | STAIRWAYS THEY SERVE. | | | | THE THIRD ISSUE IS LOCATED ON E01 NOTE | | NUMBER 24, JUNCTION BOX SIZE AS REQUIRED | | BY THE NEC. THE ELECTRICAL PLAN REVIEWER | | | | MAY COMMENT ON THIS ISSUE. THERE CAN BE | | NO JUNCTION BOXES THAT WILL COMMUNICATE | | WITHIN THE STAIR TOWER. SEE ORIGINAL | | COMMENT 1019.2 PENETRATIONS INTO AND | | OPENINGS THROUGH AN EXIT ENCLOSURE. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-08-08 |
Time |
15:15 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2006-08-08 |
Time |
15:15 |
Sent To |
|
|
Notes |
2006-08-08 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06061717 | | ADD: 1001 OKEECHOBEE BLVD | | CONT: CHA TECH SERVICES, LLC | | TEL: (770)286-7297 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) FL S S 713.13 | | NOTICE OF COMMENCEMENT, TO BE FILED | | WITH THE CLERK OF THE COURT BEFORE A | | PERMIT WILL BE ISSUED. NOTE: 713.13(2) | | IF THE WORK DESCRIBED IN THE NOTICE OF | | COMMENCEMENT IS NOT ACTUALLY COMMENCED | | WITHIN 90 DAYS AFTER THE RECORDING | | THEREOF, SUCH NOTICE IS NULL & VOID. | | | | 3) CHA, CLOUGH HARBOUR & ASSOCIATESLLP | | PLEASE PROVIDE THE ADDRESS AS STATED | | UNDER THE CERTIFICATE OF AUTHORIZATION | | FILED WITH THE STATE. IF THIS LOCATION | | IS A SECOND OFFICE THE OFFICE REGISTERED | | WITH STATE IS REQUIRED, THIS SECONDARY | | ADDRESS THEN MAY BE INCLUDED. | | | | 4) THE TITLE BLOCK LIST PB MARKETPLACE | | AS THE LOCATION FOR THE JOB? THIS | | ADDRESS IS FOR THE "MARRIOT".PLEASE | | CORRECT THE TITLE BLOCK. 61G15-23.002. | | | | 5) 110.2* W. P. B. ADMINISTRATIVE CODE, | | INFORMATION THAT IS REQUIRED FOR RECORD | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. LEVEL OF | | ALTERATION EXISTING BUILDING CODE. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | | | 6) SHEET CO4 DETAIL# 5 FOR WALL AND | | CEILING, PLANS INDICATE THAT UL LISTING | | U-334 WILL BE USED. PLANS INDICATE A 2 | | HR RATED WALL WHEREAS THE DETAIL | | INDICATES ONLY ONE LAYER OF 5/8" DRYWALL | | BUT THE UL LISTING REQUIRES 2 LAYERS. | | THE OTHER ISSUE IS THE LISTING INDICATES | | THE USE OF WOOD STUDS FOR A BEARING | | WALL. IS THIS TO BE USED AS A BEARING | | WALL.? THE OTHER ISSUE IS WOOD STUDS | | BEING USED IN A TYPE 1A BUILDING. | | WILL THERE BE FIRE SPRINKLERS ADDED TO | | THIS SPACE OR A DRY SYSTEM (HALON)? | | | | 7) SHEET E01 INDICATES CONDUITS TO BE | | INSTALLED IN THE STAIR TOWER.1019.1.2 | | PENETRATIONS. | | PENETRATIONS INTO AND OPENINGS THROUGH | | AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT | | FOR REQUIRED EXIT DOORS, EQUIPMENT AND | | DUCTWORK NECESSARY FOR INDEPENDENT | | PRESSURIZATION, SPRINKLER PIPING, | | STANDPIPES, ELECTRICAL RACEWAY FOR FIRE | | DEPARTMENT COMMUNICATION AND ELECTRICAL | | RACEWAY SERVING THE EXIT ENCLOSURE AND | | TERMINATING AT A STEEL BOX NOT EXCEEDING | | 16 SQUARE INCHES (0.010 M 2 ). SUCH | | PENETRATIONS SHALL BE PROTECTED IN | | ACCORDANCE WITH SECTION 712 . THERE | | SHALL BE NO PENETRATIONS OR | | COMMUNICATION OPENINGS, WHETHER | | PROTECTED OR NOT, BETWEEN ADJACENT EXIT | | ENCLOSURES. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-12-31 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-12-31 |
Time |
16:00 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-12-31 |
Time |
15:41 |
Sent To |
|
|
Notes |
2006-12-31 16:02:46 | ** REDLINED NOTES ** | | | | | | 1) MCB ON THE SECONDARY SIDE OF THE TRANSFORMER SHALL | | BE INSTALLED WITHIN 25FT OF CONDUCTORS MAX PER | | 240.21C. | | OCP TO BE PER PLANS, 200A MAX. | | 2) THE GENERATOR CHANGE OUT/UPGRADE SHALL BE COMPLETED | | BEFORE FINAL ON THIS PERMIT CAN BE GRANTED. | | | | | | *** OWES $1,210 FOR INCREASED VALUE. MUST BE PAID | | BEFORE PERMIT CAN PRINT. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-09-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-18 |
Time |
14:49 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-18 |
Time |
12:39 |
Sent To |
|
|
Notes |
2006-10-04 00:00:00 | **** PLEASE SEE 300.19A FOR SIZE AND | | LENGTH OF CONDUCTORS. | | SUPPORTS WHICH WOULD REQUIRE SOME TYPE | | OF PULL BOXES, WOULD NOT BE PERMITTED IN | | STAIRTOWERS. | 2006-09-18 00:00:00 | **** UNSAT 2ND REVIEW *** | | | | ** PLEASE SEE SOME NOTE FROM PREVIOUS | | REVIEW AND SOME NEW NOTES DUE TO | | INFORMATION ON PLANS. | | PLEASE SEE NOTES BELOW ARE TAKEN | | DIRECLTY FROM PREVIOUS REVIEW WITH NEW | | NOTES ADDED AT THE BOTTOM. | | | | | | | | | | 1) NOTE: NO, EXISTING RISER, OCP, SIZE | | ETC STILL NEEDS TO BE SHOWN. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE CLARIFY AND SPECIFY THE | | TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW | | PROPOSED CONNECTION IS COMING FROM. | | PLEASE KNOW, AS SHOWN THIS MAY NOT BE | | TAPPED FROM THE EXISTING EM DIST SYSTEM. | | PLEASE KNOW THERE IS MUCH INFORMATION | | NOT SUBMITTED FOR CONSIDERATION TO DO | | SO. | | 700,701,NFPA-110CHAPTERS 5,6,7. | | | | 2) NOTE:NO, PLEASE SEE DETAIL AS SHOWN | | FOR STAIRS IS STILL IN QUESTION, AND | | CONFORMATION WITH THE BUILDING REVIEW | | APPEARS THE SIZE OF REQUESTED ENCLOSURE | | IS TOO LARGE IN STAIRS. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE BUILDING AND FIRE | | REVIEW COMMENTS, AS CONDUITS SHOWN ARE | | BEING PROPOSED IN THE STAIR WAYS WHICH | | ARE NOT PERMITTED. NO EXCEPTIONS. | | | | 3) NOTE:NO, PLEASE KNOW THAT NO | | VERIFICATION OF EXISTING CAN BE DONE AS | | THE PERMITTING , INSTALLATION AND | | UPGRADE FOR EXISTING OLD GENERATOR IS | | NOT YET DONE. | | ** PLEASE SEE NOTE WHICH MENTIONS "KEMM" | | CONSULTING.? PLEASE VERIFY ,AS THIS MAY | | BE A MISPRINT FOR NAME. | | PLEASE KNOW, AS THESE ARE NOW PART OF A | | LEGALLY REQUIRED SYSTEM, SIZING , | | LOCATION ETC MUST BE VERIFIED. | | | | ** PREVIOUS REVIEW NOTE ** | | | | PLEASE PROVIDE LOAD | | CALCULATIONS FOR ALL PROPOSED LOADS | | BEING ADDED TO EXISTING LOADS. | | DEPENDING ON THE CONNECTIONS OF THE EM | | DIST SYSTEM AND TRANSFER DEVICES ETC, IT | | IS KNOWN TO THIS OFFICE THAT THIS | | BUILDING (MARRIOTT HOTEL) IS CURRENTLY | | PROPOSING THE INSTALLATION OF A NEW EM | | GEN AND DIST SYSTEM WHICH IS NOT YET | | PERMITTED. | | PLEASE KNOW, COMPLETE LOAD CALCS AND/OR | | DEMANDS AND NEW LOADS ARE REQUIRED AT | | THIS TIME. THERE WILL BE NO EXCEPTIONS | | OR "PROVISOS" (CONDITION TO ISSUE) | | GRANTED. | | 220, 215.5, ETC | | 106.1.2 FBC ADMIN SECT | | | | 4) NOTE: NO, PLEASE SEE PLANS STILL | | INDICATE THE 2005. THIS WAS REDLINED AND | | HIGHLIGHTED ON PLANS. | | | | ** PREVIOUS REVIEW NTOE ** | | PLEASE SEE PLANS CURRENTLY CALL | | FOR THE 2005 NEC. PLEASE KNOW, THE STATE | | OF FLORIDA IS STILL CURRENTLY UNDER | | UNDER THE 2002 NFPA-70 | | | | 5) NOTE: NO?? THIS IS IN QUESTION , AS | | ALL EQUIPMENT BEING SHOWN ON PLANS AND | | LABOUR FOR INSTALLATION SEEMS TO BE | | HIGHER THAN SHOWN ON APPLICATION. | | SIGNED, DATED AND NOTARIZED CONTRACT(S) | | ARE REQUIRED. FBC 108.3. | | THIS SCOPE IS FOR ALL ELECTRICAL , | | BUILDING, MECHANICALETC. | | | | ** PLEASE SEE VALUE SHALL BE BASED | | ON ALL LABOR AND MATERIALS, EVEN IF ANY | | OF THE EQUIPMENT OR MATERIALS ARE OWNER | | SUPPLIED. PLEASE KNOW, IF VALUE IS NOT | | ADJUSTED, ONE WILL BE ASSESSED BY THIS | | OFFICE USING GUIDES AS ADOPTED INTO THE | | FBC. 108.3 ADMIN SETC. | | | | 6) NOTE: NO, PLEASE SEE SOME NOTES SHOWN | | ON SHEETS DO NOT CORRELATE WITH "CODED | | NOTES", PLEASE SEE UNABLE TO VERIFY SOME | | ITEMS. | | 240.21, PANEL ON SECONDARY SIDE OF THE | | TRANSFORMER ETC. | | | | ** PREVIOUS REVIEW NOTE** | | PLEASE COMPLETE PLANS , NOTES | | AND RISER. PLEASE SEE THERE ARE | | NUMERICAL NOTES ON PLANS WHICH ARE SHOWN | | SHOWN ON NOTES.. PLEASE PLACE NOTES AND | | INFORMATION ON RISER. THIS WILL HELP THE | | REVIEW PROCESS OF JUMPING BACK AND FORTH | | FROM PAGES. PLEASE SEE NOTES ONLY GO | | THROUGH 24. | | 106.1.2.,90.7 | | | | 7) NOTE: OK. | | | | 8) NOTE: OK. | | | | PLEASE SEE COMMENTS FROM OTHER | | REVIEWER(S). | | | | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH | | RESPECT TO REPEAT CODE COMPLIANT | | COMMENTS. THIS IS ONLY NOTED AT THIS | | TIME. | | | | ** IMPORTANT** | | | | ONCE ALL REVIEWS ARE DONE, PLANS ARE | | PICKED UP AND BEFORE RESUBMITTING. | | PLEASE COMPLETELY REMOVED ALL OLD/VOIDED | | SHEETS FROM SETS AND ONLY INSERT NEW | | REVISED SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | ONLY ONE COPY OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED BACK FOR REFERENCE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-07-21 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-07-21 |
Time |
18:42 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-07-21 |
Time |
17:52 |
Sent To |
|
|
Notes |
2006-07-21 00:00:00 | ************ UNSAT **************** | | | | ** PLEASE SEE THE FOLLOWING COMMENTS AS | | THE DESIGN AS SHOWN WILL NOT BE | | PERMITTED AND CHANGES WILL BE REQUIRED. | | | | 1) NOTE: PLEASE CLARIFY AND SPECIFY THE | | TYPE OF EM DISTRIBUTION SYSTEMTHIS NEW | | PROPOSED CONNECTION IS COMING FROM. | | PLEASE KNOW, AS SHOWN THIS MAY NOT BE | | TAPPED FROM THE EXISTING EM DIST SYSTEM. | | PLEASE KNOW THERE IS MUCH INFORMATION | | NOT SUBMITTED FOR CONSIDERATION TO DO | | SO. | | 700,701,NFPA-110CHAPTERS 5,6,7. | | | | 2) NOTE: PLEASE SEE BUILDING AND FIRE | | REVIEW COMMENTS, AS CONDUITS SHOWN ARE | | BEING PROPOSED IN THE STAIR WAYS WHICH | | ARE NOT PERMITTED. NO EXCEPTIONS. | | | | 3) NOTE: PLEASE PROVIDE LOAD | | CALCULATIONS FOR ALL PROPOSED LOADS | | BEING ADDED TO EXISTING LOADS. | | DEPENDING ON THE CONNECTIONS OF THE EM | | DIST SYSTEM AND TRANSFER DEVICES ETC, IT | | IS KNOWN TO THIS OFFICE THAT THIS | | BUILDING (MARRIOTT HOTEL) IS CURRENTLY | | PROPOSING THE INSTALLATION OF A NEW EM | | GEN AND DIST SYSTEM WHICH IS NOT YET | | PERMITTED. | | PLEASE KNOW, COMPLETE LOAD CALCS AND/OR | | DEMANDS AND NEW LOADS ARE REQUIRED AT | | THIS TIME. THERE WILL BE NO EXCEPTIONS | | OR "PROVISOS" (CONDITION TO ISSUE) | | GRANTED. | | 220, 215.5, ETC | | 106.1.2 FCB ADMIN SECT | | | | 4) NOTE: PLEASE SEE PLANS CURRENTLY CALL | | FOR THE 2005 NEC. PLEASE KNOW, THE STATE | | OF FLORIDA IS STILL CURRENTLY UNDER | | UNDER THE 2002 NFPA-70 | | | | 5) NOTE: PLEASE SEE VALUE SHALL BE BASED | | ON ALL LABOR AND MATERIALS, EVEN IF ANY | | OF THE EQUIPMENT OR MATERIALS ARE OWNER | | SUPPLIED. PLEASE KNOW, IF VALUE IS NOT | | ADJUSTED, ONE WILL BE ASSESSED BY THIS | | OFFICE USING GUIDES AS ADOPTED INTO THE | | FBC. 108.3 ADMIN SETC. | | | | 6) NOTE: PLEASE COMPLETE PLANS , NOTES | | AND RISER. PLEASE SEE THERE ARE | | NUMERICAL NOTES ON PLANS WHICH ARE SHOWN | | SHOWN ON NOTES.. PLEASE PLACE NOTES AND | | INFORMATION ON RISER. THIS WILL HELP THE | | REVIEW PROCESS OF JUMPING BACK AND FORTH | | FROM PAGES. PLEASE SEE NOTES ONLY GO | | THROUGH 24. | | 106.1.2.,90.7 | | | | 7) NOTE: PLEASE CLARIFY TITLE BLOCKS AS | | ADDRESSING INFORMATION FOR SAID ENGINEER | | AND FIRM DO NOT SEEM TO CORRELATE WITH | | THE STATE'S WEBSITE. PLEASE SEE ATTACHED | | COPIES PRINTED FROM THE DEPARTMENT OF | | BUSINESS AND PROFESSIONAL REGULATION. | | FAC 61G15-23.002, FS 471 | | | | 8) NOTE: PLEASE SEE LOCATION OF PROJECT | | IS NOTED AS "PB MARKETPLACE"?? THIS | | BUIDLING IS THE MARRIOTT HOTEL. PLEASE | | ADJUST TITLE BLOCKS. | | FAC 61G15-23.002 | | | | PLEASE SEE COMMENTS FROM OTHER | | REVIEWER(S). | | | | ** IMPORTANT** | | | | ONCE ALL REVIEWS ARE DONE, PLANS ARE | | PICKED UP AND BEFORE RESUBMITTING. | | PLEASE COMPLETELY REMOVED ALL OLD/VOIDED | | SHEETS FROM SETS AND ONLY INSERT NEW | | REVISED SHEETS INTO COMPLETE SETS FOR | | REVIEW AND STAMPING. | | ONLY ONE COPY OF THE OLD/VOIDED SHEETS | | SHOULD BE SUBMITTED BACK FOR REFERENCE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2007-01-11 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-01-11 |
Time |
11:03 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-01-11 |
Time |
11:03 |
Sent To |
|
|
Notes |
2007-01-11 11:08:13 | *****APPROVED***** | | | | | | SHEET NUMBERS CO-2 AND EO-5, WHICH SHOWS/DISPLAYS THAT | | THE ELETRICAL CONDUITS WILL NOT PENETRATE THE FIRE | | RATED STAIRWELL, WERE STAMPED, INITIALED, AND DATED. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-10-03 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-10-03 |
Time |
13:23 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-10-03 |
Time |
13:23 |
Sent To |
|
|
Notes |
2006-10-03 00:00:00 | *****DENIED***** | | | | | | 1.) CONTRARY TO YOUR COMMENT RESPONSE | | SHEET DATED AUGUST 30TH,2006, THE | | RESUBMITTED PLANS STILL REFLECT THAT THE | | SCOPE OF THE WORK WILL ENTAIL THAT THE | | CONDUIT (ALTHOUGH ENCLOSED IN A 2 HOUR | | RATED CHASE) PENETRATES A FIRE RATED | | STAIRWELL.AS STATED IN THE PREVIOUS | | FIRE PLAN REVIEW, PENETRATIONS INTO, AND | | OPENINGS THROUGH, AN EXIT ENCLOSURE | | ASSEMBLY SHALL BE LIMITED TO THOSE AS | | RECORDED IN NFPA 101, 2003 EDITION, | | SECTION 7.1.3.2.1.(6). | | | | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-08-09 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-08-09 |
Time |
11:34 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-08-09 |
Time |
11:34 |
Sent To |
|
|
Notes |
2006-08-09 00:00:00 | ***DENIED*** | | | | 1) ALL EQUIPMENT INSTALLATIONS SHALL NOT | | INTERFERE WITH FIRE PROTECTION EQUIPMENT | | INSIDE BUILDING OR ON ROOF. | | | | 2) NO EQUIPMENT WILL BE ALLOWED INSIDE | | OF STAIRWELLS. PLEASE SEE NFPA 101, 2003 | | EDITION SEC. 7.1.3.2.1.(6). | | | | 3) PLEASE INDICATE SPECIFIC NFPA CODES | | THAT WILL BE COMPLIED WITH AS STATED ON | | M0.1, NOTE 10. PLEASE INCLUDE | | APPROPRIATE EDITIONS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-12-08 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-08 |
Time |
14:51 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-08 |
Time |
14:51 |
Sent To |
|
|
Notes |
2006-12-31 14:59:22 | TO COMM BOARD #44, 12/31 | 2006-12-08 14:51:59 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-09-09 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-09-09 |
Time |
15:49 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-09-09 |
Time |
15:49 |
Sent To |
|
|
Notes |
2006-09-15 00:00:00 | TO "COMM" BD#27 | 2006-09-09 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-25 |
Time |
11:29 |
Rev Time |
0.00 |
Received By |
tgordon |
Date |
2006-07-05 |
Time |
15:53 |
Sent To |
|
|
Notes |
2006-07-19 00:00:00 | TO "COMM" BD#34 | 2006-07-05 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2007-01-08 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2007-01-02 |
Time |
11:25 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2007-01-02 |
Time |
11:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2006-09-19 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-09-19 |
Time |
08:14 |
Rev Time |
0.20 |
Received By |
tgordon |
Date |
2006-09-19 |
Time |
08:14 |
Sent To |
|
|
Notes |
2006-09-19 00:00:00 | RE-STAMP. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
P |
Date |
2006-08-25 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-08-25 |
Time |
11:28 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-08-25 |
Time |
11:37 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2006-09-27 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2006-09-27 |
Time |
16:26 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2006-09-27 |
Time |
16:25 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2006-07-28 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2006-07-28 |
Time |
15:14 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2006-07-28 |
Time |
15:14 |
Sent To |
|
|
Notes |
|
|
|