Plan Review Details - Permit 06061708
Plan Review Stops For Permit 06061708
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-30 Cont ID  
Sent By lursu Date 2006-06-30 Time 12:40 Rev Time 0.00
Received By lursu Date 2006-06-30 Time 10:27 Sent To  
Notes
2006-06-30 00:00:00NEED # ADDRESS FOR NORTH MILITARY TRAIL
 ON PCN # 74424313000005010
 PERMIT TO BE ATTACHED TO PCN =
 74424313000005020

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-02 Cont ID  
Sent By jwitmer Date 2006-10-02 Time 16:29 Rev Time 0.77
Received By jwitmer Date 2006-10-02 Time 16:29 Sent To  
Notes
2006-10-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061708
 ADD: 3200 N MILITARY TRL
 CONT: CONTACT ELEC
 TEL: (561)620-0812
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) LOCATION FLOOD ZONE : A-8 FLOODZONE
 MINIMUM TOP ELEVATION OF SLAB IS 16.5'.
 PANEL# 120229 0015 B
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, WILL BE REQUIRED
 BEFORE A CERTIFICATE OF COMPLETION WILL
 BE ISSUED.
 PLEASE PROVIDE THE MINIMUM BASE
 FLOOD ELEVATION ON PLAN!!!!
  
 3) EDUARDO SAMOUR P. E. ELECTRICAL
 SHEETS ARE NOT SIGNED NOR SEALED BUT
 HAVE ENGINEERS NAME ON PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 4) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 5) VALUE IS LOW THE VALUE OF THIS PERMIT
 WILL BE BASED ON THE VALUES OF MARSHAL
 AND SWIFT IF NOT CORRECTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By jwitmer Date 2006-08-10 Time 08:24 Rev Time 1.11
Received By jwitmer Date 2006-08-10 Time 08:24 Sent To  
Notes
2006-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06061708
 ADD: 3200 N MILITARY TRL
 CONT: CONTACT ELEC
 TEL: (561)620-0812
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) LOCATION FLOOD ZONE : A-8 FLOODZONE
 MINIMUM TOP ELEVATION OF SLAB IS 16.5'.
 PANEL# 120229 0015 B
 PROVIDE FLOOD ZONE ELEVATION
 CERTIFICATE FOR NEW CONSTRUTION WITH
 BASE FLOOD ELEVATION, WILL BE REQUIRED
 BEFORE A CERTIFICATE OF COMPLETION WILL
 BE ISSUED.
  
 3) PLANS INDICATE SLAB BY OTHERS, WHO?
 A PERMIT IS REQUIRED.
 GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-24 Cont ID  
Sent By dpalmer Date 2006-09-24 Time 11:23 Rev Time 0.00
Received By dpalmer Date 2006-09-24 Time 10:17 Sent To  
Notes
2006-09-24 00:00:00******** UNSAT 2ND REVIEW ************
  
 ** PLEASE SEE MOST NOTES FROM PREVIOUS
 REVIEW STILL APPLY ALONG WITH SOME NEW
 COMMENTS DUE TO CHANGES IN PLANS.
 **PLEASE SEE THE EXACT SAME PLANS WERE
 SUBMITTED BACK WITH OUT CODE CORRECTIONS
 BEING MADE.??
  
 1) NOTE:NO, A VALUE WAS CHANGED ON
 APPLICATIONWAS INCREASED TO $55K,
 HOWEVER THIS VALUE IS WAY LOW. PLEASE
 KNOW, IF THIS IS NOT ADJUSTED
 APPROPRIATLY, ONE WILL BE ASSESSED BASED
 ON THE MARSHALLS & SWIFT GUIDE AND
 TODAYS CURRENT RATES ADOPTED INTO TEH
 FBC. 108.3.
 THE VALUE ON THE GENERATO ALONE IS
 HIGHER THAN THAT GIVEN, WHICH DOES NOT
 INCLUDE THE $10K+ ATS, , SLAB, AND
 LABOUR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL BE
 INLCUDED. PLEASE KNOW, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3 , ADMIN SECT.
 PLEASE ADJUSTOR ONE WILL BE ASSESSED
 PER MARSHALL'S SWIFT GUIDE AS ADOPTED
 UNDER THE FBC.
  
 2) NOTE: SUBMITTED, HOWEVER THIS WILL BE
 REVIEWED BY BUILDING. PLEASE SEE THAT
 THE ELEVATIONS FOR THIS MUST BE A MINOF
 6" ABOVE BFE. THIS IS NOT YET INDICATED
 ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE SLAB INFORMATION
 AT THIS TIME. PLEASE KNOW, THE SIZE, TIE
 DOWN ETC FOR GEN AND SLAB INFORMATION IS
 REQUIRED AT THIS TIME BEFORE PERMIT FOR
 GENERATOR CAN BE ISSUED.
 PLEASE SEE BUIDLING REVIEW COMMENTS.
 106.1.2
  
 3) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE AND CLARIFY
 ATS BEING INSTALLED. NO
 SPES/MANUFCATURES CUT SHEETS WERE
 SUBMITTED FOR REVIEW. PLEASE SEE A PRINT
 OUT FROM AN WEBSITE INDICATE AN "ONAN"
 YET PLANS CALL FOR GENERAC ATS WHICH
 WOULD CORRELATE WITH THE LISTED GENERAC
 GENERATOR.
 PLEASE CORRELATE AND SUBMIT ALL
 INFORMATION.
 PLEASE SEE MISSING WP HOUSING SPECS.
 PLEASE BE SURE MIN CLEARENCES ARE
 INDICATE FOR GEN AND PLEASE BE SURE AIC
 RATINGS FOR ALL EQUIPMENT IS SHOWN.
 110.9,702.6,215.5,110.26,110.3,90.7 ETC
  
 4) NOTE: NO, SEEMS TO BE SUBMITTED,
 HOWEVER LISTINGS TO BE VERIFIED.
 PLEASE SEE NO CALCULATIONS WERE
 SUBMITTED FOR FUEL USESAGE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT THE SPECS/CUT
 SHEET FOR FUEL TANK AND SIZE. PLEASE
 INDICATE GPH USESAGE AND SHOW ON PLANS.
 PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT
 WILL BE SEPARATE THIS INFORMATION IS
 REQUIRED AT THIS TIME. PLEASE ALSO SEE
 MECH REVIEW AND FIRE REVIEW COMMENTS.
 110.3,90.7,
 106.1.2 FBC
  
 5) NOTE: NO, SAME NOTE>
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SPECIFY THE NFPA-110
 PLEASE SEE CHAPTER 27 OF THE 2004 FBC,
 AND 2002 110.
  
 6) NOTE: NO, THIS WAS DONE, HOWEVER THIS
 INFORMATION WAS HANDWRITTEN ON PLANS
 WHICH IS NOT PERMITTED. PLEASE BES URE
 THE ENGINEER OF RECORD MAKES THE
 REQUIRED CHANGES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW AND INDICATE ALL
 SETBACKS FOR GENERATOR AND EQUIPMENT.
 106.1.2
  
 7) NOTE:NO, SAME NOTE. NOT ENNOUGH
 INFORMATION SUBMITTED FOR COMPLETE
 REVIEW AND CODE COMPLIANCE IS NOT YET
 MET.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY IF THE EXISTING
 MAIN PANEL WHERE IT APPEARS TO BE
 LOCATED ADJACENT TO THE NEW SE RATED ATS
 CONTAINS A MAIN?
 PLEASE ALSO PROVIDE INFORMATION BY THE
 WAY OF THE SPECS TO BE SUBMITTED AND
 PLANS THAT THE ATS CONTAINS A MANUAL
 MEANS OF DISCONNECT RATED FOR THE LOAD
 SERVED ON THE OUTSIDE AS REQUIRED PER
 230.70,230.76,230.79.
 PLEASE KNOW, IF THE EXISTING MAIN PANEL
 DOES NOT CONTAIN MCB, AND THE ATS DOES
 NOT DISCONNECT POWER FROM BOTH NORMAL
 AND EM SIDES TO A CENTER OFF POSITION, A
 MEANS OF DISCONNECT WILL BE REQUIRED
 LOCATED AT BUIDLING GROUPED WITH OUTHER
 MAINS.
 225.31-225.39, 230.72, 230.70
  
  
 ** NEW NOTRES**
  
 8) NOTE: PLEASE SEE ONLY ONE SET OF
 PLANS ARE SIGNED, DATED AND SEALED.
 PLEASE SEE FAC 61G15-23.002, FS 471.025.
  
 9) NOTE: PLEASE SEE AS THE SAME PLANS
 ORIGINAL SUBMITTED WERE BROUGHT BACK
 WITH HAND DRAWN CHANGES ON SOME SHEETS,
 AND NOT CORRECTIONS MADE, ONE SET OF
 PLANS ARE BEING RETAINED FOR FILE FOR
 POSSIBLE REVIEW BY THE FBPE'S.
 PLEASE SEE FS 553.80(2)(B) WITH RESPECT
 TO REPEAT CODE COMPLIANT COMMENTS FOR
 DESIGN PREOFESSIONALS.
  
 10) NOTE: PLEASE SEE THE NOTICE OF
 COMMENCMENT SUBMITTED IS NO LONGER VALID
 AND IS NULL AND VOID. PLEASE SEE FS
 713.13(2). WHEN WORK HAS NOT COMMENCED
 WITHIN 90 DAYS OF RECORDING SUCH NOC,
 THEN THE DOCUMENT OF VOID>
 ** THE RECORDED NOC IS ONLY REQUIRED
 WHEN PICKING UP PERMIT.
  
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL AND OTHER
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-21 Cont ID  
Sent By dpalmer Date 2006-07-21 Time 11:50 Rev Time 0.00
Received By dpalmer Date 2006-07-21 Time 11:34 Sent To  
Notes
2006-07-21 00:00:00******** UNSAT ************
  
 1) NOTE: PLEASE SEE THE VALUE FOR
 COMPLETE SCOPE OF WORK SHALL BE
 INLCUDED. PLEASE KNOW, EVEN IF ANY
 EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3 , ADMIN SECT.
 PLEASE ADJUSTOR ONE WILL BE ASSESSED
 PER MARSHALL'S SWIFT GUIDE AS ADOPTED
 UNDER THE FBC.
  
 2) NOTE: PLEASE PROVIDE SLAB INFORMATION
 AT THIS TIME. PLEASE KNOW, THE SIZE, TIE
 DOWN ETC FOR GEN AND SLAB INFORMATION IS
 REQUIRED AT THIS TIME BEFORE PERMIT FOR
 GENERATOR CAN BE ISSUED.
 PLEASE SEE BUIDLING REVIEW COMMENTS.
 106.1.2
  
 3) NOTE: PLEASE CORRELATE AND CLARIFY
 ATS BEING INSTALLED. NO
 SPES/MANUFCATURES CUT SHEETS WERE
 SUBMITTED FOR REVIEW. PLEASE SEE A PRINT
 OUT FROM AN WEBSITE INDICATE AN "ONAN"
 YET PLANS CALL FOR GENERAC ATS WHICH
 WOULD CORRELATE WITH THE LISTED GENERAC
 GENERATOR.
 PLEASE CORRELATE AND SUBMIT ALL
 INFORMATION.
 PLEASE SEE MISSING WP HOUSING SPECS.
 PLEASE BE SURE MIN CLEARENCES ARE
 INDICATE FOR GEN AND PLEASE BE SURE AIC
 RATINGS FOR ALL EQUIPMENT IS SHOWN.
 110.9,702.6,215.5,110.26,110.3,90.7 ETC
  
 4) NOTE: PLEASE SUBMIT THE SPECS/CUT
 SHEET FOR FUEL TANK AND SIZE. PLEASE
 INDICATE GPH USEGAE AND SHOW ON PLANS.
 PLEASE KNOW, EVEN THOUGH THE FUEL PERMIT
 WILL BE SEPARATE THIS INFORMATION IS
 REQUIRED AT THIS TIME. PLEASE ALSO SEE
 MECH REVIEW AND FIRE REVIEW COMMENTS.
 110.3,90.7,
 106.1.2 FBC
  
 5) NOTE: PLEASE SPECIFY THE NFPA-110
 PLEASE SEE CHAPTER 27 OF THE 2004 FBC,
 AND 2002 110.
  
 6) NOTE: PLEASE SHOW AND INDICATE ALL
 SETBACKS FOR GENERATOR AND EQUIPMENT.
 106.1.2
  
 7) NOTE: PLEASE CLARIFY IF THE EXISTING
 MAIN PANEL WHERE IT APPEARS TO BE
 LOCATED ADJACENT TO THE NEW SE RATED ATS
 CONTAINS A MAIN?
 PLEASE ALSO PROVIDE INFORMATION BY THE
 WAY OF THE SPECS TO BE SUBMITTED AND
 PLANS THAT THE ATS CONTAINS A MANUAL
 MENAS OF DISCONNECT RATED FOR THE LOAD
 SERVICED ON THE OUTSIDE AS REQUIRED PER
 230.70,230.76,230.79.
 PLEASE KNOW, IF THE EXISTING MAIN PANEL
 DOES NOT CONTAINA MCB, AND THE ATS DOES
 NOT DISCONNECT POWER FROM BOTH NORMAL
 AND EM SIDES TO A CENTER OFF POSITION, A
 MEANS OF DISCONNECT WILL BE REQUIRED
 LOCATED AT BUIDLING GROUPED WITH OUTHER
 MAINS.
 225.31-225.39
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL AND OTHER
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-10-23 Cont ID  
Sent By mawillia Date 2006-10-23 Time 14:24 Rev Time 0.00
Received By mawillia Date 2006-10-23 Time 14:24 Sent To  
Notes
2006-10-23 14:32:06*****DENIED*****
  
  
  
  
 PLEASE ADDRESS PREVIOUS FIRE PLAN REVIEW COMMENTS BY
 WAY OF NOTATION ON THE APPROVED SET OF PLANS OR A
 COMMENT SHEET DEPICTING THAT THEY HAVE BEEN
 ACKNOWLEDGED.
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By mwennerg Date 2006-08-18 Time 12:28 Rev Time 0.00
Received By mwennerg Date 2006-08-18 Time 12:28 Sent To  
Notes
2006-08-18 00:00:00***DENIED***
  
 1) PLEASE PROVIDE SITE SURVEY INDICATING
 DIMENSIONS OF GENERATOR AND FUEL TANK AS
 IT RELATES TO BUILDING OPENINGS AND
 PROPERTY LINES.
  
 2) IN ADDITION TO CODES REFERENCED ON
 E0, NFPA 110, 2002 EDITION SHALL BE
 COMPLIED WITH.
  
 3) PLEASE PROVIDE ADDITIONAL
 INFORMATION/SPEC SHEETS FOR FUEL TANK.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status N Date 2006-10-20 Cont ID  
Sent By pkrauss Date 2006-10-20 Time 11:22 Rev Time 0.00
Received By pkrauss Date 2006-10-20 Time 11:22 Sent To  
Notes
2006-10-20 11:23:38SUB-BASE FUEL TANK - NO FUEL PIPING OR REMOTE TANK

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 15:12 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 15:12 Sent To  
Notes
2006-08-21 00:00:00DENIED:SEE COMMENTS UNDER MECHANICAL
 PLAN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-09-11 Cont ID  
Sent By adarroug Date 2006-09-11 Time 16:33 Rev Time 0.00
Received By adarroug Date 2006-09-11 Time 16:33 Sent To  
Notes
2006-09-20 00:00:00TO "COMM" BD#42
2006-09-11 00:00:00WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 15:16 Rev Time 0.00
Received By pkrauss Date 2006-07-03 Time 16:26 Sent To  
Notes
2006-07-19 00:00:00TO "COMM" BD#58
2006-07-03 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-10-20 Cont ID  
Sent By pkrauss Date 2006-10-20 Time 11:12 Rev Time 0.00
Received By pkrauss Date 2006-10-20 Time 10:20 Sent To  
Notes
2006-10-20 11:20:24 
 DENIED:
 ELECTRICAL PLANS SHALL BE SIGNED,SEALED AND DATED PER
 FS 471.025 AND FAC 61G15-23..002.
  
 PROVISO:
 PLEASE NOTE, EXHAUST PRODUCED BY THE GENERATOR SHALL BE
 DISCHARGED IN SUCH A MANNER IN WHICH IT WILL NOT
 MIDIGATE INTO THE BUILDING IN ACCORDANCE WITH 2004 FMC
 501.2.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 14:39 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 14:37 Sent To  
Notes
2006-08-21 00:00:00DENIED:DIESEL GENRATOR
 ELECTICAL PERMIT 06061709
  
 1.PLEASE PROVIDE INFORMATION ON THE
 GENERATOR'S FUEL TANK, I.E. SUB-BASE,
 ABOVE GROUND, UNDERGROUND, CAPACITY,
 ETC.
  
 2.PROVIDE INFORMATION FOR THE FUEL
 PIPING, SIZE, MATERIAL, LAYOUT, SUPPORT,
 ETC.
  
 3.INDICATE DISTANCES/CLEARANCES FROM
 THE GENERATOR TO PROPERTY LINES,
 BUILDINGS, FRESH AIR INTAKES, WINDOWS,
 DOORS, LOUVERS, ETC.SHOW COMPLIANCE
 WITH 2004 FMC 401.5, 401.5.1 & 501.2.
  
 4.ADDITIONAL PERMIT FOR THE FUEL OIL
 STORAGE, IF THIS IS NOT A SUB-BASE FUEL
 TANK.PLEASE NOTE, ABOVE GROUND &
 UNDERGROUND TANKS WITH THE CAPACITY
 GREATER THAN 500 GALLON SHALL BE
 SUBMITTED TO DERM TO THE ATTENTION OF
 CHIP GREEN.PLANS MAY BE SUBMITTED AT
 3323 BELVEDERE RD., BUILD # 502.
  
 5.PLEASE PROVIDE ANCHORING DETAIL.
  
 6.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL OF THE "PRECAST CONTRETE
 BASE".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719
 OR E-MAIL [email protected].
  

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-26 Cont ID  
Sent By eschneid Date 2006-09-26 Time 10:21 Rev Time 0.00
Received By eschneid Date 2006-09-26 Time 10:21 Sent To  
Notes
2006-09-26 00:00:00 
  
 1) NO DETAILS OF THE SOLID FENCE AND
 LANDSCAPE SUBMITTED.
  
 2) SUBMISSION OF A PERMIT FOR THE
 INSTALLATION OF THE FENCE AND LANDSCAPE
 IS REQUIRED PRIOR TO THE ZONING RELEASE
 OF THIS PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561)822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-31 Cont ID  
Sent By eschneid Date 2006-07-31 Time 14:11 Rev Time 0.00
Received By eschneid Date 2006-07-31 Time 14:11 Sent To  
Notes
2006-07-31 00:00:001) PLEASE SHOW SETBACKS FROM THE NORTH
 PROPERTY LINE ON SHEET E-1.
  
 2) GENERATOR IS REQUIRED TO BE SCREENED
 BY SOLID FENCE OR WALL AND LANDSCAPE ON
 NORTH, EAST AND WEST SIDES.PROVIDE
 DETAILS OF FENCE/WALL AND LANDSCAPE
 PLAN.
  
 3) HOW TALL IS THE GENERATOR?
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.