Plan Review Details - Permit 06061619
Plan Review Stops For Permit 06061619
Review Stop AD ADDRESSING
Rev No 2 Status N Date 2006-11-03 Cont ID  
Sent By jleech Date 2006-11-03 Time 12:48 Rev Time 0.00
Received By jleech Date 2006-07-17 Time 14:16 Sent To  
Notes
2006-07-17 00:00:00A NEW TEMP PCN IS CREATED FOR THIS UNIT
 16 & 17 , TEMP7442430208A16 FOR THE UNIT
 16 & 17.
2006-07-15 00:00:00NEEDS ADDRESSING FOR SUITE/BAY
 EXTENSION.

Review Stop AD ADDRESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By ssherman Date 2006-06-28 Time 16:23 Rev Time 0.00
Received By ssherman Date 2006-06-28 Time 16:20 Sent To  
Notes
2006-06-28 00:00:00SENT TO ADDRESSING IN ERROR EXTENSION
 ALREADY CREATED

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-10-30 Cont ID  
Sent By alange Date 2006-10-30 Time 14:00 Rev Time 0.00
Received By alange Date 2006-10-30 Time 14:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 09:49 Rev Time 0.00
Received By alange Date 2006-08-11 Time 09:09 Sent To  
Notes
2006-08-11 00:00:00DENIED
  
 1.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 2.PAGES A8.01 MISSING FROM TWO SETS OF
 PLANS AND PAGE INDEX DOES NOT REFLECT
 PAGES SUBMITTED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 21:12 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 21:02 Sent To  
Notes
2006-10-27 21:11:32**** NOTE ****
  
  
 OLD/VOIDED ELECTRICAL SHEETS WHICH WERE LEFT IN SETS
 WERE REMOVED AND THROWN OUT.
 ALL OLD/VOIDED SHEETS SHOULD HAVE BEEN REMOVED BEFORE
 RESUBMITTING COMPLETED SETS FOR REVIEW AND STAMPING.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 18:11 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 17:54 Sent To  
Notes
2006-07-15 00:00:00**** REDLINED *****
  
 CIRCUIT #WHICH WAS HAND WRITTEN ON
 PLANS THAT ARE SIGNED AND SEALED OK AS
 THIS WAS REDLINED. ON ALL SETS.
 ANY REVISIONS DONE, SHALL INCLUDE THIS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-11-02 Cont ID  
Sent By mwennerg Date 2006-11-02 Time 14:18 Rev Time 0.00
Received By mwennerg Date 2006-11-02 Time 14:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By mcarsill Date 2006-07-17 Time 12:36 Sent To  
Notes
2006-07-17 00:00:001. ONLY ONE SET OF DRAWINGS CONTAIN PAGE
 A8.01. THE ONLY SET CONTAINING A8.01 WAS
 REVIEWED AND NO PROBLEMS WERE NOTED.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-10-16 Cont ID  
Sent By adarroug Date 2006-10-16 Time 15:41 Rev Time 0.00
Received By adarroug Date 2006-10-16 Time 15:41 Sent To  
Notes
2006-10-27 14:13:53TO "BOB"#5
2006-10-16 15:42:06WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-11 Cont ID  
Sent By alange Date 2006-08-11 Time 09:48 Rev Time 0.00
Received By alange Date 2006-06-30 Time 09:14 Sent To  
Notes
2006-07-13 00:00:00TO "BOB"#9
2006-06-30 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 15:23 Rev Time 0.20
Received By tgordon Date 2006-08-04 Time 15:23 Sent To  
Notes
2006-08-04 00:00:00NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-11-03 Cont ID  
Sent By jleech Date 2006-11-03 Time 12:47 Rev Time 0.00
Received By jleech Date 2006-11-03 Time 12:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-08-11 Cont ID  
Sent By jleech Date 2006-08-11 Time 07:49 Rev Time 0.00
Received By jleech Date 2006-08-11 Time 07:49 Sent To  
Notes
2006-08-11 00:00:00DENIED;
 1.SERVICE SINK REQUIRES HOT WATER.
 FBC-2004 PLUMBING SECTION 607.1.
 2.DRINKING FOUNTAIN REQUIRED. TABLE
 403.1#8.
 3.A EMERGENCY SHOWER AND EYE WASH
 STATION MAY BE REQUIRED. TABLE 403.1,
 PLEASE LIST TYPE OF MATERIAL TO BE
 STORED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695