Plan Review Details - Permit 06061595
Plan Review Stops For Permit 06061595
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2007-02-22 Cont ID  
Sent By jwitmer Date 2007-02-22 Time 16:32 Rev Time 0.77
Received By jwitmer Date 2007-02-22 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-12-13 Cont ID  
Sent By jwitmer Date 2006-12-13 Time 10:56 Rev Time 1.11
Received By jwitmer Date 2006-12-13 Time 10:56 Sent To  
Notes
2006-12-13 11:18:40 
 BUILDING PLAN REVIEW
 PERMIT: 06061595
 ADD: 422 SUNSET
 CONT: BURKHARDT CONSTRUCTION
 TEL: (561)718-2602
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 PLANS INDICATE THAT EYE-HOOKS ARE TO BE EMBEDDED INTO
 THE CONCRETE POUR WITH STRAPPING OVER THE GENERATOR?
 106.1.2* ADDITIONAL INFORMATION REQUIRED:
  
 1A) PLANS ARE TO IDENTIFY THE SIZE OF THE EYE-HOOK
 DIA.X LENGTH.
 1B) WILL THERE BE A NUT AND WASHER AS PART OF THE
 EMBEDMENT?
 1C) TYPE OF MATERIAL EYE-HOOK TO BE MADE OF? CARBON
 STEEL, GALVANINIZED?
 1D) PLACEMENT OF EYE-HOOKS?VERSES STRAPS, PLEASE
 PROVIDE THE PLACEMENT OF BOTH THE BOLT EMBEDMENT AND
 STRAPS SINCE THE STRAPS CAN NOT BLOCK THE DOORS TO THE
 UNIT.
 1E) PROVIDE ADDITIONAL INFORMATION ON THE TYPE OF
 MATERIAL TO BE USSED FOR THE STRAPS?
 1F) WITH STRAP TYPE OF HOLD-DOWN AND TYPE OF MATERIAL
 STRAP IS TO BE MADE FROM, HOW MUCH PRESSURE IS TO BE
 REQUIRED TO HOLD THE GENERATOR IN PLACE WITHOUT
 SLIPPAGE OR MOMMENT
 OF OVERTURNING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 14:20 Rev Time 0.00
Received By alange Date 2006-07-26 Time 14:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 11:47 Sent To  
Notes
2007-02-11 12:01:08ELECTRICAL RISER SHEETS FOR GENERATTOR INSTALL ONLY.
 STAMPED SPECS AND E SHEETS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-12-06 Cont ID  
Sent By dpalmer Date 2006-12-06 Time 18:58 Rev Time 0.00
Received By dpalmer Date 2006-12-06 Time 18:58 Sent To  
Notes
2006-12-06 18:59:59**** UNSAT 2ND REVIEW ***
  
  
  
  
 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS FOR
 REVIEW. PLEASE SEE THE ONE SET SUBMITTED IS NOT
 ACCURATE TO THE LATEST REVISED RISER DIAGRAM FOR
 BUILDING.
 PLEASE KNOW THAT THIS PERMIT SHALL CONTAIN A COMPLETE
 RECORD SET OF PLANS AS THIS IS A STAND ALONE PERMIT.
 SITE PLANS,/SURVEY'S. STRUCTURAL FOUNDATION, ELECTRICAL
 RISER, ETC
 FBC 106.1.2,
 90.7, 110.3, ETC.
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 16:37 Sent To  
Notes
2006-07-15 00:00:00****** UNSAT *********
  
 ** PLEASE SEE NOTES UNDER THE TWO
 PERMITS FOR REMODEL, AS THEY WILL AFFECT
 THIS PERMIT, SERVICE RISER ETC.
 PLEASE SEE SERVICE.
  
  
 1) NOTE: PLEASE SEE TYPE OF GENERATOR IS
 UNCLEAR AT THIS TIME. PLEASE SEE PERMIT
 APPLICATION HAS A MECHANCICAL CONTRACTOR
 SIGNED ON FOR A "FUEL PERMIT" WHICH
 LENDS TO THIS GEN BEING DIESEL, HOWEVER
 NO INFORMATION ON PLANS. PLEASE SEE NO
 SPECS ARE SUBMITTED FOR FUEL TANK ETC.
 PLEASE SEE PARTIAL "SITE PLAN" MENTIONS
 400 GAL TANK, BUT DOES NOT SPECIFY TYPE
 OF FUEL.
 PLEASE SEE COMMENTS FROM FIRE AND
 MECHANICAL REVIEW.
 PLEASE SUBMIT SPECS.
 106.1.2 FBC ADMIN SECT.
  
 2) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR THE GEN, ATS'S ETC.
 PLEASE KNOW, ALL SHALL INDICATE LISTINGS
 FROM A NRTL.
 110.3,702.6 ETC.
  
 3) NOTE: PLEASE SEE THAT PLANS SPECIFY
 FUEL CONSUMPTION. GPH ETC.
 PLEASE KNOW, AS PERMIT FOR GENERATOR IS
 BEING SUBMITTED UNDER 433 AVON RD, WHICH
 IS A SEPARATE LEGAL PCN ETC AND IF GEN
 IS FEEDING AND LEGALLY REQUIRED STAND-BY
 DEVICES ON 422 SUNSET RD, IT MAY BE
 DETERMINED THAT A UNITY OF TITLE MAY BE
 REQUIRED IF NOT ONE ALREADY.
 THIS WILL REQUIRE FURTHER CONSULTATION.
  
 4) NOTE: PLEASE CLARIFY IF THE GEN
 ENCLOSURE WILL REMAIN LOCKED, AS ACCESS
 TO SERVICE MEANS OF DISCONNECT SHALL BE
 READILY ACCESSIBLE.
 100, 230.70
  
  
 5) NOTE: PLEASE KNOW, THE NOC SUBMITTED
 WHICH MENTIONS "SITE-WORK" DOES NOT
 COVER THE INSTALLATION OF THE EM GEN
 ETC.
 PLEASE SEE KNOW, THAT A RECORDED NOC
 INCLUDING THE INSTALLATION OF THE GEN
 SHALL BE REQUIRED BEFORE PICKING UP
 PERMIT.
 FS 713.13
  
 6) NOTE: PLEASE INDICATE ALL EQUIPMENT
 ON "PARTIAL SITE PLAN" AS CLEARNECE OF
 ALL SERVICE EQUIPMENTNEEDS TO BE
 VERIFIED.110.26
  
 ** PLEASE KNOW, DUE TO POSSIBLE CHANGES
 IN SERVICE RISER, AND SOME INFORMATION
 NOT SUBMITTED THERE MAY BE COMMENTS ON
 FURTHER REVIEWS WHICH ARE NOT MENTIONED
 ABOVE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2007-02-23 Cont ID  
Sent By mawillia Date 2007-02-23 Time 18:22 Rev Time 0.00
Received By mawillia Date 2007-02-23 Time 18:22 Sent To B
Notes
2007-02-23 18:23:50*****APPROVED*****
  
 PLAN SHEET SP-1 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-08-23 Cont ID  
Sent By mawillia Date 2006-08-23 Time 11:41 Rev Time 0.00
Received By mawillia Date 2006-08-23 Time 09:25 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2007-01-03 Cont ID  
Sent By kstevens Date 2007-01-03 Time 10:23 Rev Time 0.00
Received By kstevens Date 2007-01-03 Time 10:23 Sent To  
Notes
2007-01-03 10:24:15COMMENT RESPONSE - DIESEL GENERATOR - NO LP OR NATURAL
 GAS

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By kstevens Date 2006-08-08 Time 11:11 Rev Time 0.00
Received By kstevens Date 2006-08-08 Time 11:11 Sent To  
Notes
2006-08-08 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A. MORE INFORMATION IS REQUIRED.
 APPLICATION INDICATES GAS FUEL TANK.
 PLEASE INDICATE TYPE OF FUEL TANK. WILL
 THIS BE AN LP TANK? WILL THIS BE A
 DIESEL TANK?.
  
 B. IF THE TANK IS AN LP TANK, THE
 FOLLOWING INFORMATION IS REQUIRED:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. NOT USED.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. NOT USED.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. -
 INSTALLATION SPECIFICATIONS REQUIRED
 WITH MANUF. SHEETS TO VERIFY CLEARANCES.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-01-29 Cont ID  
Sent By adarroug Date 2007-01-29 Time 18:53 Rev Time 0.00
Received By adarroug Date 2007-01-29 Time 18:53 Sent To E
Notes
2007-02-07 08:51:23TO "COMM" BD#63
2007-01-29 18:54:13WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-01-20 Cont ID  
Sent By adarroug Date 2007-01-20 Time 12:23 Rev Time 0.00
Received By adarroug Date 2007-01-20 Time 12:23 Sent To Z
Notes
2007-01-20 12:24:10TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-21 Cont ID  
Sent By adarroug Date 2006-11-21 Time 15:48 Rev Time 0.00
Received By adarroug Date 2006-11-21 Time 15:48 Sent To  
Notes
2006-12-05 13:34:21TO "COMM" BD#7
2006-11-21 15:49:37WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 09:20 Rev Time 0.00
Received By tgordon Date 2006-06-29 Time 14:16 Sent To  
Notes
2006-07-13 00:00:00TO "COMM" BD#7
2006-06-29 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-16 Cont ID  
Sent By tgordon Date 2007-02-16 Time 11:30 Rev Time 0.20
Received By tgordon Date 2007-02-16 Time 11:30 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-12 Cont ID  
Sent By tgordon Date 2006-12-12 Time 13:43 Rev Time 0.20
Received By tgordon Date 2006-12-12 Time 13:43 Sent To  
Notes
2006-12-12 13:46:07*** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES REGARDING PLANS NEEDED,
 PLEASE COMPLY.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-25 Cont ID  
Sent By tgordon Date 2006-08-25 Time 09:11 Rev Time 0.25
Received By tgordon Date 2006-08-25 Time 09:11 Sent To  
Notes
2006-08-25 00:00:00*** DENIED ***
 1) PLEASE SEE ELECTRICAL REVIEW NOTES
 AND CORRECT.
 2) PLEASE SEE THE FOLLOWING NOTES
 REGARDING GENERATOR LOCATION.
 3) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 FOLLOW MANUFACTURE'S RECOMMENDED
 CLEARANCES AROUND EQUIPMENT FOR
 SERVICING,AND PROVIDE MANUFACTURE'S
 INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2007-01-25 Cont ID  
Sent By lfranco Date 2007-01-25 Time 16:58 Rev Time 0.00
Received By lfranco Date 2007-01-25 Time 16:57 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2007-01-09 Cont ID  
Sent By jbabcock Date 2007-01-09 Time 09:50 Rev Time  
Received By lfranco Date 2007-01-09 Time 09:12 Sent To I
Notes
2007-01-09 09:13:09PLANNING AND ZONING:FAILED
  
 1.PROVIDE ALL COMMENTS IN WRITING.
  
 2.PURSUANT TO SECTION 94-444(B)-APPROPRIATE SCREENING
 IS REQUIRED.THEREFORE, THE WALLS SHALL BE LANDSCAPED
 WITH SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS.
 MAKE SURE THAT THE SPACE IS PROVIDED TO ACCOMODATE
 REQUIRED LANDSCAPING AND DOES NOT ENCROACH ON THE
 EXISTING PARKING ADJACENT TO THE PROPOSED GENERATOR.
  
 *NOTATION SHALL BE MADE TO SHOW THAT THE HEDGES WILL BE
 PLANTED AT TWO-FOOT INTERVALS
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
 JULIA BABCOCK
 PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By lfranco Date 2006-08-03 Time 11:30 Sent To  
Notes
2006-08-03 00:00:00PLANNING AND ZONING:FAILED
  
 1.PROVIDE ALL COMMENTS IN WRITING.
  
 2.PURSUANT TO SECTION
 94-444(B)-APPROPRIATE SCREENING IS
 REQUIRED.THIS INCLUDES THE WALLS
 SHALL BE LANDSCAPED WITH SHRUBS AND
 HEDGES PLANTED AT TWO-FOOT INTERVALS.
 MAKE SURE THAT THE SPACE IS PROVIDED TO ACCOMMODATE
 REQUIRED LANDSCAPING AND DOES
 NOT ENCROACH ON THE EXISTING PARKING
 ADJACENT TO THE PROPOSED GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT ME AT THE NUMBER BELOW.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1435