Plan Review Details - Permit 06061469
Plan Review Stops For Permit 06061469
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-09-06 Cont ID  
Sent By rmcdouga Date 2006-09-06 Time 09:41 Rev Time 0.00
Received By rmcdouga Date 2006-09-05 Time 11:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-31 Cont ID  
Sent By rmcdouga Date 2006-07-31 Time 16:01 Rev Time 0.00
Received By rmcdouga Date 2006-07-31 Time 16:01 Sent To  
Notes
2006-08-01 00:00:00DENIED
  
 1) THE DESIGN WIND PRESSURES FOR THE
 WIND AND DOOR OPENINGS ON THE PLANS ARE
 INCORRECT. THE SIMPLIFIED PROVISIONS FOR
 DETERMINING THE WINDLOAD PRESSURES IN
 FBC 1609.6 CAN NOT BE USED FOR BUILDINGS
 MORE THAN 60 FEET IN HEIGHT. WINDLOADS
 FOR THIS STRUCTURE MUST BE DETERMINED BY
 ASCE7-02. SUBMIT SIGNED AND SEALED
 WINDLOAD CALCULATIONS FROM A FLORIDA
 LICENSED DESIGN PROFESSIONAL EXPERIENCED
 IN THIS TYPE OF WORK FOR THE WINDOW AND
 DOOR OPENINGS.
  
 2) PRODUCT APPROVAL FOR THE STORM PANELS
 DOES NOT SPECIFY A FASTENER FOR
 ATTACHMENT TO STEEL. THE IMPACT
 PROTECTION DEVICES ARE REQUIRED TO BE
 TESTED AND MUST MEET THE REQUIREMENTS
 LISTED IN FBC 1609.1.4. YOU CAN NOT
 SPECIFY FASTENERS FROM ANOTHER PRODUCT.
 THEREFORE THEY CAN NOT BE INSTALLED AS
 YOU HAVE INDICATED.
  
 3) THE KEY PLAN SPECIFIES 13'-2" PANELS
 AT THE DOORS. THIS EXCEEDS THE MAXIMUM
 SPAN ALLOWED BY PRODUCT APPROVAL. PLEASE
 CLARIFY.
  
 4) PLEASE USE THE INSTALLATION SCHEDULE
 LOCATED AT THE BACK OF THE IMPACT
 PROTECTION STANDARD ATTACHED TO
 COMMENTS.
  
 5) PLEASE PROVIDE A BREAKDOWN AS TO THE
 TIME IT WILL TAKE TO INSTALL AN
 INDIVIDUAL PANEL, THE NUMBER OF PANELS
 AND THE TOTAL TIME FOR COMPLETE
 INSTALLATION OF ALL PANELS PER REQUEST
 OF BUILDING OFFICIAL.
  
 6) EMERGENCY EGRESS FROM THE UNIT MUST
 BE MAINTAINED WHILE SHUTTERS ARE
 INSTALLED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By rmcdouga Date 2006-06-29 Time 08:13 Rev Time 0.00
Received By rmcdouga Date 2006-06-29 Time 08:13 Sent To  
Notes
2006-06-29 00:00:00DENIED
  
 1) SPECIFY THE BUILDING HEIGHT AND
 NUMBER OF STORIES ON THE PLANS. FBC
 106.1.2
  
 2) SPECIFY THE POSITIVE AND NEGATIVE
 WIND PRESSURES FOR THE EXTERIOR OPENINGS
 ON THE PLANS. FBC 1603.1.4
  
 3) SHUTTER INSTALLATION ON LARGE OR
 MULTISTORY BUILDINGS REQUIRE PRE-STORM
 PREPARATION PLANS APPROVED BY THE
 CONSTRUCTION SERVICES DEPARTMENT. SEE
 #13 OF THE ATTACHED IMPACT PROTECTION
 STANDARD.
  
 4) THE FASTENER INDICATED (HI-LIGHTED)
 ON THE PRODUCT APPROVAL FOR THE STORM
 PANELS IS FOR ATTACHMENT TO WOOD. THE
 PLANS SPECIFY CONCRETE AND STEEL
 CONSTRUCTION.
  
 5) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE. SPECIFY THE FASTENERS,
 FASTENER SPACING, SPANS, VERTICAL OR
 HORIZONAL INSTALLATION, ETC. A SAMPLE
 INSTALLATION SCHEDULE IS ATTACHED TO THE
 IMPACT PROTECTION STANDARD.
  
 6) IF THE DOORS ARE REQUIRED FOR EGRESS
 EXIT THEY CAN NOT BE SHUTTERED.
  
 7) THE FLORIDA COVERSHEET FOR THE ARCH
 ALUMNIUM DOORS IS FOR IMPACT RATED DOORS
 THE STOREFRONT DOOR NOA IS FOR
 NON-IMPACT DOORS. SUBMIT COVERSHEET AND
 EVALUATION REPORTS FOR THE SAME PRODUCT.
  
 8) THE FLORIDA COVERSHEET FOR THE ARCH
 ALUMINUM STOREFRONT PANEL WALLS DOES NOT
 MATCH THE NOA THAT WAS SUBMITTED.
 COVERSHEET IS FOR IMPACT AND NOA IS FOR
 NON-IMPACT.
  
 9) PROVIDE BUCK ATTACHMENT DETAILS.
  
 10)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-03 Cont ID  
Sent By mwennerg Date 2006-07-03 Time 11:10 Rev Time 0.00
Received By mwennerg Date 2006-07-03 Time 11:10 Sent To  
Notes
2006-07-03 00:00:00***PROVISO***
  
 1) IF DOORS ARE PART OF THE MEANS OF
 EGRESS, THEY SHALL COMPLY WITH
 APPLICABLE BUILDING CODES, AND NFPA 101
 2003 EDITION, SEC. 7.2.1. EXISTING EXIT
 SIGN TO REMAIN OR BE REPLACED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 10:39 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 10:39 Sent To B
Notes
2006-08-24 00:00:00TO "RMCDOUGAL" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-17 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-07-17 Time 11:28 Sent To  
Notes
2006-07-20 00:00:00TO "BOB"10
2006-07-17 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-17 Cont ID  
Sent By adarroug Date 2006-07-03 Time 11:28 Rev Time 0.00
Received By adarroug Date 2006-06-27 Time 15:25 Sent To  
Notes
2006-06-27 00:00:00TO "BOB"#5