Plan Review Details - Permit 06061419
Plan Review Stops For Permit 06061419
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2007-01-16 Cont ID  
Sent By lmartine Date 2007-01-16 Time 17:40 Rev Time 0.00
Received By lmartine Date 2007-01-16 Time 17:40 Sent To  
Notes
2007-01-16 17:41:24ORIGINAL COMMENTS WERE NOT ADDRESSED

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:14 Rev Time 0.33
Received By alange Date 2006-07-13 Time 08:14 Sent To  
Notes
2006-07-13 00:00:00DENIED
  
 1.SHOW GENERATOR SLAB DETAIL AND
 METHOD OF ATTACHMENT TO SLAB.
  
 2.SUBMIT ON ORIGONAL DOCUMENT AND HAVE
 SIGNED BY THE PREPARER.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-01-05 Cont ID  
Sent By btrobaug Date 2007-01-05 Time 17:51 Rev Time 0.00
Received By btrobaug Date 2007-01-05 Time 17:45 Sent To  
Notes
2007-01-05 17:51:41 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.CHANGE AMOUNT WHEN RESUBMITTING, TELL CLERK.
  
 2}THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO
 RESUBMITTING.106.3.4.2 FBC.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON A SITE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 4} PROVIDE A PANEL SCHEDULE PER 408.4.
 FOR THE PANEL BEING FED FROM THE
 GENERATOR.
  
 5} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-07-07 Cont ID  
Sent By btrobaug Date 2006-07-07 Time 08:41 Rev Time 0.50
Received By btrobaug Date 2006-07-07 Time 08:00 Sent To P
Notes
2006-07-07 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE VALUE ON THE APPLICATION MUST
 INCLUDE THE COST OF LABOR AND MATERIAL
 FOR THE INSTALLATION OF ALL COMPONENTS
 UNDER THE SCOPE OF THIS PERMIT. FBC
 108.3.
  
 2}THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO
 RESUBMITTING.106.3.4.2 FBC.
  
 3} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE, GENERATOR,
 TRANSFER SWITCH, DISCONNECTS AND PANELS,
 SO THAT COMPLIANCE WITH ARTICLES 225 AND
 230 CAN BE REVIEWED.
  
 4} PROVIDE SPECIFICATIONS FOR THE
 TRANSFER SWITCH.
  
 5} PROVIDE A PANEL SCHEDULE PER 408.4.
 FR THE PANEL BEING FED FROM THE
 GENERATOR.
  
 6} PROVIDE MANUFACTURERS SPECIFICATIONS/RECOMMENDATION,
 REGARDING CLEARANCES.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By mperson Date 2006-07-07 Time 14:20 Rev Time 0.15
Received By mperson Date 2006-07-07 Time 14:20 Sent To M
Notes
2006-07-07 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-11-13 Cont ID  
Sent By adarroug Date 2006-11-13 Time 16:37 Rev Time 0.00
Received By adarroug Date 2006-11-13 Time 16:37 Sent To E
Notes
2006-11-13 16:37:45TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-05 Cont ID  
Sent By adarroug Date 2006-07-05 Time 13:23 Rev Time 0.00
Received By adarroug Date 2006-07-05 Time 13:23 Sent To E
Notes
2006-07-05 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-13 Cont ID  
Sent By alange Date 2006-07-13 Time 08:15 Rev Time 0.00
Received By alange Date 2006-06-26 Time 16:23 Sent To  
Notes
2006-06-26 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 09:56 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 09:56 Sent To B
Notes
2006-07-11 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-07-02 Cont ID  
Sent By mmclean Date 2006-07-02 Time 17:43 Rev Time 0.00
Received By mmclean Date 2006-07-02 Time 17:43 Sent To I
Notes
2006-07-02 00:00:00PROVISO: MUST PROVIDE A COPY OF THE HOA
 APPROVAL BEFORE THE PERMIT IS ISSUED.
  
 MUST PROVIDE A LANDSCAPE HEDGE AROUND
 THE PROPOSED GENERATOR.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved