Plan Review Details - Permit 06061405
Plan Review Stops For Permit 06061405
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-14 Cont ID  
Sent By mperson Date 2006-07-14 Time 14:19 Rev Time 0.33
Received By mperson Date 2006-07-14 Time 14:19 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By mperson Date 2006-07-03 Time 15:41 Rev Time 0.33
Received By mperson Date 2006-07-03 Time 15:41 Sent To PC
Notes
2006-07-03 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW:
  
 1. PER FBC-2004, CHAPTER 1, SECTION 106
 CONSTRUCTION DOCUMENTS: ISOMETRIC
 DRAWINGS IN PENCIL ARE UNACCEPTABLE.
 PLEASE PRINT NAME ABOVE THE SIGNATURE
 AND DATE DRAWING
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. (NOTE: THIS INCLUDES THE
 EXISTING1-1/4" LINE INDICATED ON THE
 DRAWING)
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).(NOTE: THIS INCLUDES THE BTU'S
 OF THE EXISTING SYSTEM)
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 (NOTE: THIS INCLUDES THE EXISTING
 SYSTEM, LONGEST LENGTH METHOD USED IN
 SIZING SYSTEM)
 5. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 PLEASE INDICATE PRESSURE ON THE DRAWING.
 6. PER FBC-2004 FUEL GAS, SEC. 403.4.1:
 IRON PIPE SHALL NOT BE USED PLEASE
 CHANGE TO STEEL OR GALVANIZED.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE CORRECTED DRAWING IN
 RED INK FOR REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-10 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-07-10 Time 15:10 Sent To G
Notes
2006-07-10 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-10 Cont ID  
Sent By adarroug Date 2006-07-03 Time 15:10 Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 14:19 Sent To  
Notes
2006-06-26 00:00:00TO "G" BOX