Plan Review Details - Permit 06061148
Plan Review Stops For Permit 06061148
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2006-07-27 Cont ID  
Sent By mperson Date 2006-07-27 Time 13:40 Rev Time 0.45
Received By mperson Date 2006-07-27 Time 13:40 Sent To PC
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2006-07-11 Cont ID  
Sent By mperson Date 2006-07-11 Time 10:58 Rev Time 0.45
Received By mperson Date 2006-07-11 Time 10:58 Sent To PC
Notes
2006-07-11 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLAN REVIEW FOR A GAS
 PERMIT:
 (NOTE: COMMENTS NOT ADDRESSED)
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.3, QUALITY OF BUILDING PLANS: THE
 BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS
 AND SPECIFICATIONS, IN ORDER TO PROVIDE
 CONFORMITY TO ITS RECORD RETENTION
 PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST,
 CLARITY, OR OTHER ITEMS RELATED TO
 RECORDS MANAGEMENT.
 A) RESUBMITTED DRAWINGS SHALL BE SUBMIT-
 TED CLEAR OF PLAN REVIEWERS COMMENT
 CORRECTION REFERENCES.
 B) WHITE-OUT ON DRAWING CORRECTIONS
 UNACCEPTABLE.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. (NOTE: A COPY OF ONE OF THE
 OLD/VOIDED SHEETS FOR REFERENCE WAS NOT
 DONE FOR THE RESUBMITTAL)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-29 Cont ID  
Sent By mperson Date 2006-06-29 Time 14:31 Rev Time 0.45
Received By mperson Date 2006-06-29 Time 14:31 Sent To PC
Notes
2006-06-29 00:00:00******DENIED******
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR A GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).(NOTE: THE
 LONGEST RUN INDICATED ON DRAWING IS
 INCORRECT, AND THE PIPE SIZING IS WRONG
 PER FBC-2004 FUEL GAS TABLES 402.4(2),
 AND 402.4(20). SYSTEM MIGHT NEED TO GO
 TO A 2LB SYSTEM WITH REGULATORS, PLEASE
 CORRECT FOR RESUBMITTAL)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. PLEASE SEE MARKED UP DRAWING IN
 RED INK, AND ATTACHED SIZING TABLESFOR
 REFERENCE FOR RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-25 Cont ID  
Sent By adarroug Date 2006-07-25 Time 11:05 Rev Time 0.00
Received By adarroug Date 2006-07-25 Time 11:05 Sent To G
Notes
2006-07-25 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 08:19 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 08:19 Sent To G
Notes
2006-07-07 00:00:00TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-06-29 Time 08:19 Rev Time 0.00
Received By adarroug Date 2006-06-21 Time 17:05 Sent To  
Notes
2006-06-21 00:00:00TO "G" BOX