2006-06-20 00:00:00 | *********** UNSAT ************** |
| |
| ** PLEASE SEE 2002 NEC, NFPA-72 2002 |
| |
| |
| 1) NOTE: PLEASE SEE MIN VA FOR SMALL |
| APPLIANCES SHALL BE PER 210.11C1,220.16 |
| |
| 2) NOTE: PLEASE SEEM MIN VA FOR DRYER TO |
| BE PER 220.18 |
| |
| 3) NOTE: PLEASE SEE |
| 210.52B1,210.11,220.16 FOR DINING AREA |
| RECEPTS TO BE ON ONE OR MORE OF THE |
| REQUIRED DEDICATED SM APPL BRANCH |
| CIRCUITS. |
| |
| 4) NOTE: PLEASE SEE 2002 NEC 210.12B FOR |
| REQUIRED ARC FAULT PROTECTION REQUIRED. |
| NOTES ON PLANS MENTIONS RECEPTS, HOWEVER |
| ALL OUTLETS IN BEDRMS REQUIRE |
| PROTECTION, NOT ONLY RECEPTS. |
| |
| 5) NOTE: PLEASE SEE MISSING SD'S |
| REQUIRED PER NFPA-72 11.5.1.1,11.8.3.5. |
| PLEASE SEE MISSING INSIDE AND OUTSIDE |
| ALL SLEEPING RMS. PLEASE ALSO SEE TYPE |
| OF SD'S WHICH ARE REQUIRED WHEN |
| INSTALLED WITHIN 20' OF COOKING |
| APPLIANCES. |
| |
| 6) NOTE: PLEASE SEE MISSING EGRESS |
| LIGHTING CONTROL AND LT FIXTURE PER |
| 210.70, LS101 7.8 |
| (LAUNDRY RM). |
| |
| 7) NOTE: PLEASE SEE MISSING GFI RECEPT |
| FOR CU. PER 210.63,210.8 |
| |
| 8) NOTE: PLEASE SEE PLANS SHALL INDICATE |
| THE CURRENT CODES. 2002 NFPA-70, 2002 |
| NFPA-72, 2003 NFPA-101 |
| |
| 9) NOTE: PLEASE CLARIFY USE OF RECEPT IN |
| WIC IN MAST BEDRM. |
| PLEASE KNOW, THIS IS A RECEPT TO PLUG IN |
| ANY TYPE OF LV TRANSFORMER, THEN THE |
| RECEPT SHALL NOT BE PLACED IN LOCATION |
| OF STORAGE OR SHELVING. THE RECEPT MAY |
| BE PLACED ABOVE DOOR. |
| 240.24, 110.26 |
| |
| 10) NOTE: PLEASE SEE PLANS INDICATE A |
| NEW RISER SERVICE , YET NOTE BELOW LOAD |
| CALCULATIONS MENTIONS EXISTING?? |
| PLEASE CLARIFY |
| 215.5 |
| |
| 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 12) NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTOR FROM MAIN DISC TO |
| PANEL. |
| 250.110,250.24B,250.122 ETC |
| |
| 13) NOTE: PLEASE SEE GROUNDING RISER |
| SHOWS THE GEC GOING TO FOOTER/FOUNDATION |
| STEEL? PLEASE KNOW, ON AN EXISTING OLDER |
| BUILDING THIS IS NOT REQUIRED, HOWEVER |
| IF SHOWN ON RISER THEN IT WILL BE |
| REQUIRED. |
| PLEASE KNOW, IN EXISTING BLDGS, THERE |
| MAY OR MAY NOT BE FOOTER STEEL, AND TO |
| CAN BE MORE DETRIMENTAL TO THE |
| STRUCTURAL INTEGRITY OF AN EXISTIGN |
| BUILDING TO DO SO. |
| 250.50,215.5 |
| |
| 14) NOTE: PLEASE SEE 424.3B,240.4,310.16 |
| FOR MIN SIZE FOR OCP AND MIN AWG FOR THE |
| AHU AND THE 10KW LOAD SHOWN. |
| MININUM OCP SHALL BE 125% AND CONDUCTOR |
| SIZES SHALL BE ADJUSTED ACCORDINGLY. |
| |
| 15) NOTE: PLEASE SEE WATER HEATER IS |
| SHOWING 5400VA ON 2-POLE 20A BRKR. |
| PLEASE SEE MIN OCP SHALL BE 125%,PLEASE |
| ADJUST OCP AND AWG. |
| 422.13, 240.4, 310.16 |
| |
| 16) NOTE: PLEASE SEE 408.4 AS PANEL |
| SCHEDULE SHALL BE SPECIFIC TO CICUITING |
| OF AREAS AND ROOMS. |
| |
| 17) NOTE: PLEASE SEE PANEL SCHEDULE |
| INDICATES A 26 CIR PANEL. PLEASE KNOW, |
| THIS NOT A COMMON SIZE AND VERIFICATION |
| SHOULD BE MADE AND PANEL SHOULD BE |
| CORRECTED. |
| 215.5 |
| |
| 18) NOTE: PLEASE SUBMIT MIN LOAD |
| CALCULATIONS PER 220 OF THE NEC 2002 |
| 215.5 |
| |
| 19) NOTE: PLEASE SEE RISER SHOWS NEW |
| OVER HEAD AND NEW UNDER GROUND FROM FPL. |
| PLEASE SEE THAT ONE OR OTHER SHOULD BE |
| INDICATED. |
| THIS CAN BE REVISED AT A LATER DATE IF |
| IT IS CHANGED. |
| 215.5 |
| |
| 20) NOTE: PLEASE SEE THE LIGHTING |
| CONTROL FOR THE LIGHTS IN THE MASTER |
| BEDRM SHOULD BE AT NEAREST POINT OF |
| ENTRANCE TO THE BEDRM. SHOWN ON THE |
| OTHER SIDE OF THE RM AWAY FROM THE |
| ENTRANCE DOOR.?? |
| PLEASE ALSO SEE THE SW FOR MAST BATH IS |
| OUTSIDE THE BATHRM, WHERE THE SW |
| LOCATION IS REQUIRED INSIDE. |
| LS 101 7.8, 210.70 |
| |
| 21) NOTE: PLEASE VERIFY CIRCUITING SHOWN |
| FOR LIGHTING AS THE FRONT PORCH LT IS |
| BEING SHOWN ON A DEDICATE LT CIRCUIT, |
| AND THE REST OF THE ENTIRE HOSUE IS |
| SHOWN ON ONE CIRCUIT??? |
| PLEASE SEE 220 FOR MAX VA PERMITED ON |
| ONE CIRCUIT, PLEASE SEE A MAX OF 1440VA. |
| 240.4,310.16 ETC. |
| 215.5 |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS |
| FROM OTHER TRADES WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |