Plan Review Details - Permit 06060983
Plan Review Stops For Permit 06060983
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-07-18 Cont ID  
Sent By amorse Date 2006-07-18 Time 15:38 Rev Time 0.50
Received By amorse Date 2006-07-18 Time 15:38 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-14 Cont ID  
Sent By dpalmer Date 2006-08-14 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2006-08-14 Time 19:49 Sent To M
Notes
2006-08-14 00:00:00***** REDLINED NOTES**
  
 PLEASE SEE 424.3B FOR MIN OCP FOR AHU
 HEAT, @ 125%. (MIN)
 PREVIOUS REVIEW>
  
 PLEASE SEE A REVISED PANEL SCHEDULE WILL
 BE NEED TO BE SUBMITTED BEFORE FINAL.
 ALL OTHER REVISIONS REQUIRED BEFORE
 ROUGH.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By dpalmer Date 2006-06-20 Time 12:04 Rev Time 0.00
Received By dpalmer Date 2006-06-20 Time 10:21 Sent To M
Notes
2006-06-20 00:00:00*********** UNSAT **************
  
 ** PLEASE SEE 2002 NEC, NFPA-72 2002
  
  
 1) NOTE: PLEASE SEE MIN VA FOR SMALL
 APPLIANCES SHALL BE PER 210.11C1,220.16
  
 2) NOTE: PLEASE SEEM MIN VA FOR DRYER TO
 BE PER 220.18
  
 3) NOTE: PLEASE SEE
 210.52B1,210.11,220.16 FOR DINING AREA
 RECEPTS TO BE ON ONE OR MORE OF THE
 REQUIRED DEDICATED SM APPL BRANCH
 CIRCUITS.
  
 4) NOTE: PLEASE SEE 2002 NEC 210.12B FOR
 REQUIRED ARC FAULT PROTECTION REQUIRED.
 NOTES ON PLANS MENTIONS RECEPTS, HOWEVER
 ALL OUTLETS IN BEDRMS REQUIRE
 PROTECTION, NOT ONLY RECEPTS.
  
 5) NOTE: PLEASE SEE MISSING SD'S
 REQUIRED PER NFPA-72 11.5.1.1,11.8.3.5.
 PLEASE SEE MISSING INSIDE AND OUTSIDE
 ALL SLEEPING RMS. PLEASE ALSO SEE TYPE
 OF SD'S WHICH ARE REQUIRED WHEN
 INSTALLED WITHIN 20' OF COOKING
 APPLIANCES.
  
 6) NOTE: PLEASE SEE MISSING EGRESS
 LIGHTING CONTROL AND LT FIXTURE PER
 210.70, LS101 7.8
 (LAUNDRY RM).
  
 7) NOTE: PLEASE SEE MISSING GFI RECEPT
 FOR CU. PER 210.63,210.8
  
 8) NOTE: PLEASE SEE PLANS SHALL INDICATE
 THE CURRENT CODES. 2002 NFPA-70, 2002
 NFPA-72, 2003 NFPA-101
  
 9) NOTE: PLEASE CLARIFY USE OF RECEPT IN
 WIC IN MAST BEDRM.
 PLEASE KNOW, THIS IS A RECEPT TO PLUG IN
 ANY TYPE OF LV TRANSFORMER, THEN THE
 RECEPT SHALL NOT BE PLACED IN LOCATION
 OF STORAGE OR SHELVING. THE RECEPT MAY
 BE PLACED ABOVE DOOR.
 240.24, 110.26
  
 10) NOTE: PLEASE SEE PLANS INDICATE A
 NEW RISER SERVICE , YET NOTE BELOW LOAD
 CALCULATIONS MENTIONS EXISTING??
 PLEASE CLARIFY
 215.5
  
 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 12) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN DISC TO
 PANEL.
 250.110,250.24B,250.122 ETC
  
 13) NOTE: PLEASE SEE GROUNDING RISER
 SHOWS THE GEC GOING TO FOOTER/FOUNDATION
 STEEL? PLEASE KNOW, ON AN EXISTING OLDER
 BUILDING THIS IS NOT REQUIRED, HOWEVER
 IF SHOWN ON RISER THEN IT WILL BE
 REQUIRED.
 PLEASE KNOW, IN EXISTING BLDGS, THERE
 MAY OR MAY NOT BE FOOTER STEEL, AND TO
 CAN BE MORE DETRIMENTAL TO THE
 STRUCTURAL INTEGRITY OF AN EXISTIGN
 BUILDING TO DO SO.
 250.50,215.5
  
 14) NOTE: PLEASE SEE 424.3B,240.4,310.16
 FOR MIN SIZE FOR OCP AND MIN AWG FOR THE
 AHU AND THE 10KW LOAD SHOWN.
 MININUM OCP SHALL BE 125% AND CONDUCTOR
 SIZES SHALL BE ADJUSTED ACCORDINGLY.
  
 15) NOTE: PLEASE SEE WATER HEATER IS
 SHOWING 5400VA ON 2-POLE 20A BRKR.
 PLEASE SEE MIN OCP SHALL BE 125%,PLEASE
 ADJUST OCP AND AWG.
 422.13, 240.4, 310.16
  
 16) NOTE: PLEASE SEE 408.4 AS PANEL
 SCHEDULE SHALL BE SPECIFIC TO CICUITING
 OF AREAS AND ROOMS.
  
 17) NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES A 26 CIR PANEL. PLEASE KNOW,
 THIS NOT A COMMON SIZE AND VERIFICATION
 SHOULD BE MADE AND PANEL SHOULD BE
 CORRECTED.
 215.5
  
 18) NOTE: PLEASE SUBMIT MIN LOAD
 CALCULATIONS PER 220 OF THE NEC 2002
 215.5
  
 19) NOTE: PLEASE SEE RISER SHOWS NEW
 OVER HEAD AND NEW UNDER GROUND FROM FPL.
 PLEASE SEE THAT ONE OR OTHER SHOULD BE
 INDICATED.
 THIS CAN BE REVISED AT A LATER DATE IF
 IT IS CHANGED.
 215.5
  
 20) NOTE: PLEASE SEE THE LIGHTING
 CONTROL FOR THE LIGHTS IN THE MASTER
 BEDRM SHOULD BE AT NEAREST POINT OF
 ENTRANCE TO THE BEDRM. SHOWN ON THE
 OTHER SIDE OF THE RM AWAY FROM THE
 ENTRANCE DOOR.??
 PLEASE ALSO SEE THE SW FOR MAST BATH IS
 OUTSIDE THE BATHRM, WHERE THE SW
 LOCATION IS REQUIRED INSIDE.
 LS 101 7.8, 210.70
  
 21) NOTE: PLEASE VERIFY CIRCUITING SHOWN
 FOR LIGHTING AS THE FRONT PORCH LT IS
 BEING SHOWN ON A DEDICATE LT CIRCUIT,
 AND THE REST OF THE ENTIRE HOSUE IS
 SHOWN ON ONE CIRCUIT???
 PLEASE SEE 220 FOR MAX VA PERMITED ON
 ONE CIRCUIT, PLEASE SEE A MAX OF 1440VA.
 240.4,310.16 ETC.
 215.5
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2007-02-08 Cont ID  
Sent By adarroug Date 2007-02-08 Time 09:31 Rev Time 0.00
Received By adarroug Date 2007-02-08 Time 09:31 Sent To M
Notes
2007-02-08 09:33:09TO "MECH" IN BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 10:18 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 10:18 Sent To E
Notes
2006-08-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-18 Time   Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 15:18 Sent To  
Notes
2006-06-19 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2007-02-12 Cont ID  
Sent By tgordon Date 2007-02-12 Time 08:33 Rev Time 0.30
Received By tgordon Date 2007-02-12 Time 08:33 Sent To  
Notes
2007-02-12 08:34:13REVISION TO MACH. PLANS AND E-CAL'S.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-15 Cont ID  
Sent By tgordon Date 2006-08-15 Time 08:36 Rev Time 0.45
Received By tgordon Date 2006-08-15 Time 08:36 Sent To  
Notes
2006-08-15 00:00:00*** PROVISO ***
 1) STRAPING CAN NOT GO OVER CONDENSER
 UNIT, UNIT MUST BE ANCHORED WITH ANCHOR
 CLIPS. PER 2004 FBC/R M1307.3.1 1
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By tgordon Date 2006-06-21 Time 11:36 Rev Time 0.30
Received By tgordon Date 2006-06-21 Time 11:36 Sent To P
Notes
2006-06-21 00:00:00*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT, PER 2004 FBC
 13-600.3.ABC.2 .
  
 2) PLEASE SUBMIT A COMPLETEMANUAL J
 CALCULATIONS, SHOWING CFM'S AND DUCT
 SIZES TO EACH ROOM, PER 2004 FBC
 13-607.1.ABC.1 ; OR A MANUAL D
 CALCULATION, PER 2004 FBC/R M1601.1 .
  
 3) PLEASE CORRECT SUPPLY AIR DUCT SIZES
 ON PLANS ACCORDING TO THE MANUAL J
 CALCULATIONS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-07-08 Cont ID  
Sent By jleech Date 2006-07-08 Time 10:33 Rev Time 0.00
Received By jleech Date 2006-07-08 Time 10:33 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***