Plan Review Details - Permit 06060912
Plan Review Stops For Permit 06060912
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By amorse Date 2006-07-03 Time 07:54 Rev Time 0.50
Received By amorse Date 2006-07-03 Time 07:54 Sent To PC
Notes
2006-07-03 00:00:00 
 DENIED
  
 1) PROVIDE LIST OF WINDOW TYPE AND SIZE
 FOR EACH OPENING
  
 2) PER 507.3 OF THE EXISTING BUILDING
 CODE AND 1609.1.4 FBC OPENING THAT ARE
 NOT IMPACT RESISTANT SHALL BE PROTECTED
 BY IMPACT RESISTANT COVERINGS. (THE
 SINGLE HUNG ARE NOT IMPACT THE CASEMENTS
 ARE)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
2006-06-14 00:00:00HISTORIC APPROVAL BY H MITTNER
 ACCIDENTALLY SIGNED OFF ON BLDG RATHER
 THAN HISTORIC

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2006-06-14 Cont ID  
Sent By ssherman Date 2006-06-14 Time 15:59 Rev Time 0.00
Received By ssherman Date 2006-06-14 Time 15:59 Sent To  
Notes
2006-06-14 00:00:00HISTORICAL APPROVED BY L MITTNER

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-03 Time   Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 14:44 Sent To  
Notes
2006-06-16 00:00:00TO "MISC" BOX