Plan Review Details - Permit 06060909
Plan Review Stops For Permit 06060909
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status N Date 2006-07-31 Cont ID  
Sent By alange Date 2006-07-31 Time 13:14 Rev Time 0.00
Received By alange Date 2006-07-31 Time 13:14 Sent To  
Notes
2006-07-31 00:00:00BUILDING REVIEW DONE BY ELECTRICAL
 REVIEWER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 13:21 Rev Time 0.50
Received By alange Date 2006-06-28 Time 13:21 Sent To  
Notes
2006-06-28 00:00:00DENIED
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.SHOW GENERATOR SLAB DETAIL AND
 METHOD OF ATTACHMENT TO SLAB.
  
 3.PROPERTY IS IN FLOOD ZONE "A".SHOW
 SLAB ELEVATION AT 6" ABOVE THE BASE
 FLOOD ELEVATION OF 7FT. NGVD.AN
 ELEVATION CERTIFICAT WILL BE REQUIRED
 FOR FINAL INSPECTION.
  
 4.SEE ELECTRICAL REVIEW REGARDING
 BUILDING COMMENTS.
  
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-28 Cont ID  
Sent By dpalmer Date 2006-07-28 Time 20:10 Rev Time 0.00
Received By dpalmer Date 2006-07-28 Time 19:57 Sent To B
Notes
2006-07-28 00:00:00**** UNSAT ****
  
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 REVIEW AND SOME NEW NOTES.
  
 1) NOTE: NO, SAME, ONLY CONTAINS A
 PRINTED NAME. PLEASE KNOW,PLANS SHALL BE
 SIGNED BY THE PERSON WITH THE PRINTED
 NAME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE PRINTED NAME
 AND SIGNATURE IS ON PLANS FOR THE PERSON
 REPSONSIBLE FOR PLANS.
 FBC 106.2.1
  
 2) NOTE:NO, UNCLEAR AS THE FLOOD
 ELEVATION COULD NOT BE FOUND. AN ELEV OF
 6.02 IS SHOWN BUT IT IS UNCLEAR WHAT
 THIS IS. ?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, LOCATION OF
 HOUSE/GEN IS IN A "A" FLOOD ZONE AND
 PLANS SHALL INDICATE EQUIPMENT AT 6"
 MIN ABOVE THE BFE.
  
 3) NOTE: NO, THE LAYOUT IS STILL UNCLEAR
 AS SITE PLANS SHOW THE NEW EM PANEL
 OUTSIDE AND THE PTHER PANELS INSIDE.
 PLEASE SEE SPECS INDICATE THE EM PANEL
 AS NEMA 1 AND PLANS PLACE THIS PANEL
 OUTSIDE??
 PLEASE ALSO KNOW THAT THE DISCONNECTING
 MEANS FOR THE FEEDERS COMING FROM THE
 GEN SHALL BE GROUPED WITH THE EXISTING
 MAIN(S). 225.34, 230.72
 PLEASE INDICATE THE OCP FEEDIGN THE EM
 PANEL. PLEASE CLARIFY THE 200 A MAIN. IT
 IS BEING ASSUMED IT IS A MCB PANEL?
 240.4,310.16,110.3,90.7, ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT FOR ALL
 EQUIPMENT AS VERIFICATION OF THE
 GROUPING OF THE MAINS AND DISCONECT CAN
 NOT BE DONE AT THIS TIME.
 230.72,225.34
  
 ** SAME NOTE, NO SLAB DETAIL PROVIDED
 FOR GEN UNIT.
  
 ** PREVIOUS NOTE **
 PLEASE SEE BLDG COMMENTS AS SLAB DETAIL
 FOR GEN IS MISSING.
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS
 RESPONSIBLE FOR PLANS AND REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY GIVEN AS A NOTICE AT THIS
 TIME.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 16:24 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 16:24 Sent To M
Notes
2006-06-23 00:00:00**** UNSAT ****
  
  
 1) NOTE: PLEASE BE SURE THE PRINTED NAME
 AND SIGNATURE IS ON PLANS FOR THE PERSON
 REPSONSIBLE FOR PLANS.
 FBC 106.2.1
  
 2) NOTE: PLEASE KNOW, LOCATION OF
 HOUSE/GEN IS IN A "A" FLOOD ZONE AND
 PLANS SHALL INDICATE EQUIPMENT AT 6"
 MIN ABOVE THE BFE.
  
 3) NOTE: PLEASE PROVIDE A LAYOUT FOR ALL
 EQUIPMENT AS VERIFICATION OF THE
 GROUPING OF THE MAINS AND DISCONECT CAN
 NOT BE DONE AT THIS TIME.
 230.72,225.34
  
 PLEASE SEE BLDG COMMENTS AS SLAB DETAIL
 FOR GEN IS MISSING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-27 Cont ID  
Sent By adarroug Date 2006-07-27 Time 13:58 Rev Time 0.00
Received By adarroug Date 2006-07-27 Time 13:58 Sent To E
Notes
2006-07-27 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 11:19 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 11:19 Sent To E
Notes
2006-06-19 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 13:27 Rev Time 0.00
Received By alange Date 2006-06-16 Time 14:46 Sent To  
Notes
2006-06-16 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 15:25 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 15:25 Sent To B
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By dpalmer Date 2006-07-28 Time 20:12 Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 18:02 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 18:02 Sent To I
Notes
2006-06-18 00:00:00THE PROPOSED GENERATOR IS 5FT FROM REAR
 PROPERTY LINE & 20FT FROM THE SIDE
 PROPERTY LINE.
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  