Plan Review Details - Permit 06060899
Plan Review Stops For Permit 06060899
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-23 Cont ID  
Sent By lursu Date 2006-06-23 Time 11:10 Rev Time 0.00
Received By lursu Date 2006-06-23 Time 11:09 Sent To  
Notes
2006-06-23 00:00:00EXT #0006 WAS CREATED FOR UNITS A11 THRU
 A14

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-08-08 Cont ID  
Sent By rmcdouga Date 2006-08-08 Time 08:43 Rev Time 0.00
Received By rmcdouga Date 2006-08-08 Time 07:15 Sent To  
Notes
2006-08-08 00:00:00DENIED
  
 1) THE DOOR TO THE EXISTING H/C BATHROOM
 IS REQUIRED TO HAVE A MINIMUM OF 18" OF
 CLEARANCE AT THE LATCH SIDE OF THE DOOR
 ON THE PULL SIDE. FBC 11-4.22.2 AND
 FBC 11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 2) SEE PLUMBING COMMENT #3 FOR REQUIRED
 HEIGHT OF COUNTER AND SINK IN WORK ROOM
 #2. SEE FBC 11-4.24 AND 11-4.32.4.
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By rmcdouga Date 2006-06-23 Time 9:00 Rev Time 0.00
Received By rmcdouga Date 2006-06-23 Time 9:00 Sent To  
Notes
2006-06-23 00:00:00DENIED
  
 1) THE EXISTING ACCESSIBLE BATHROOM MUST
 BE MADE CODE COMPLIANT. FBC 2004
 EXISTING BUILDINGS 606.1 AND 2004 FBC
 11-4.1.6. PROVIDE DETAIL SHOWING
 COMPLIANCE.
  
 2) THE TWO DOORS IN SERIES AT THE
 BATHROOM IN OFFICE 1 DO NOT COMPLY WITH
 CODE. SEE FBC 11-4.13.7.
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-05 Cont ID  
Sent By dpalmer Date 2006-08-05 Time 10:39 Rev Time 0.00
Received By dpalmer Date 2006-08-05 Time 10:15 Sent To  
Notes
2006-08-05 00:00:00*** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE NOTE FROM PREVIOUS
 REVIEW. PLEASE SEE FBC CHAPTER 13, AS
 THE SPACE IS IN A BUILDING LARGER THAN
 5K SQ FT. PLEASE SEE 13-415.1.ABC.1.1,
 .1.2, .1.3.
 THIS SPACE IS NOT A BUILDING. PLEASE SEE
 ELECTRICAL IS FED FROM A SERVICE WHICH
 FEEDS ONE BUILDING. PLEASE SEE FBC
 DEFINITIONS OF BUILDINGS. IF THIS SPACE
 WAS SEPARATED BY A "FIRE WALL" ON BOTH
 SIDES WHICH REQUIRES 4HR SEPARATION AND
 ALSO REQUIRES COMPLETE COLLAPSE OF THE
 ADOINING ROOFS WITH OUT AFFECTTING THE
 STRUCTURAL INTEGRITY OF THE BUILDING
 ETC.
 PLEASE SEE AT THIS POINT THE SPACE WOULD
 BE CONSIDERED A BUILDING AND A SEPARATE
 ELECTRICAL SERVICE WOULD BE REQUIRED.
  
 ** PLEASE SEE SPACE #11&12 SEEM TO BE
 EXISTINGWITH ONLY THE NEW SEPARATION
 BEING ADDED, IF SO PLEASE LABEL ALL
 ELECTRICAL OR CLOUD SPACE AS EXISTING.
 PLEASE SEE SPACE #13&14 WILL REQUIRE NEW
 CONTROLS PER CHAPTER 13 AS NOTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By dpalmer Date 2006-06-21 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2006-06-21 Time 18:04 Sent To  
Notes
2006-06-21 00:00:00****** UNSAT *****
  
 1) NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS TO SPLIT FOUR BAYS DOWN TO TWO,
 HOWEVER FROM WHAT THE PLASN INDICATE,
 THERE IS ONLY ONE BAY EXISTING WHICH IS
 NOW BEING SEPARATED BY NEW PROPOSED
 TENANT SEPARATION WALL INTO TWO NEW
 BAYS.???
 PLEASE VERIFY.
 IT WAS NOTED THAT THE UNITS MAY HAVE
 BEEN LABELED 11,12,13 AND 14, HOWEVER
 NEW SUITES MAY BE ASSIGNED.
  
 2) NOTE: PLEASE SUBMIT LOADS ON EXISTING
 SERVICES WITH NEW LOADS ADDED.
 220, 215.5
  
 3) NOTE: PLEASE SEE FBC CHAPTER 13 ,
 13-415.1.ABC.1.1,.1.2,.1.3
 13-415.1.AB.1, 13-415.2.ABC.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By mwennerg Date 2006-08-08 Time 14:35 Rev Time 0.00
Received By mwennerg Date 2006-08-08 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By mwennerg Date 2006-06-27 Time 13:10 Rev Time 0.00
Received By mwennerg Date 2006-06-27 Time 13:10 Sent To  
Notes
2006-06-27 00:00:00***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA
 101, 2003 EDITION.
  
 2) A FIRE EXTINGUISHER IS SHOWN IN
 RECEPTION (1). A 2A-10B,C RATED FIRE
 EXTINGUISHER IS ALSO REQUIRED IN OTHER
 TENANT SPACE DUE TO THE SEPARATION.
  
 3) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 13:11 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 13:11 Sent To  
Notes
2006-08-01 00:00:00TO "BOB"#10
2006-07-20 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-27 Cont ID  
Sent By adarroug Date 2006-06-27 Time 13:10 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 14:22 Sent To  
Notes
2006-06-21 00:00:00TO "BOB"#14
2006-06-15 00:00:00WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-08-04 Cont ID  
Sent By tgordon Date 2006-08-04 Time 09:34 Rev Time 0.30
Received By tgordon Date 2006-08-04 Time 09:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By tgordon Date 2006-06-22 Time 13:59 Rev Time 0.45
Received By tgordon Date 2006-06-22 Time 13:59 Sent To  
Notes
2006-06-22 00:00:00*** DENIED ***
 1) ENERGY CAL'S PAGE #1 SEE MAX TONNAGE
 3.7, PLANS ARE SHOWING TWO 3 1/2 TON
 SYSTEMS= 7 TONS, PLEASE CORRECT.
  
 2) ENERGY CAL'S PAGE #5 IS SHOWING THREE
 A/C SYSTEMS, PLANS ARE SHOWING TWO
 SYSTEMS, PLEASE CORRECT.
  
 3) PROVIDE RETURN AIR FOR AHU #2.
  
 4) PROVIDE RETURN AIR TO ALL OFFICES.
 BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By jleech Date 2006-08-11 Time 08:19 Rev Time 0.00
Received By jleech Date 2006-08-11 Time 08:19 Sent To  
Notes
2006-08-11 00:00:00DENIED;
 1.WHAT TYPE OF WORK WILL BE DONE IN THE
 WORK ROOM AND WHY IS A REFRIGERATOR
 REQUIRED?
 2. MEN'S ROOM IS NOT HANDICAP COMPLIANT.
 A)DOOR SWINGS INTO CLEAR FLOOR SPACE
 OF THE LAVITORY.
 B) THE URINAL AND LAVATORY IN THE
  
 HANDICAP BATHROOM MUST MEET ALL
 THE REQUIREMENTS OF CHAPTER 11.
 URINAL TO COMPLY WITH SECTIONS
 11-4.18.2 THRU 11-4.18.4.
 LAVATORY TO COMPLY WITH SECTIONS
 11-4.19.1 THRU 11-4.19.6.
 3. A WATER HEATER IS SHOWN ON PAGE 2
 (FLOOR PLAN) BUT NO HOT WATER PIPING IS
 SHOWN ON WATER RISER DIAGRAM. PLEASE
 NOTE ON PLANS IF NEW BATHROOM WILL NOT
 HAVE HOT WATER TO THE LAV.
 4.CUP DISPENSOR REQUIRED AT DRINKING
 FOUNTAINS. CHAPTER 11 SECTION
 11-4.1.3(10). PLEASE ADD NOTE ON PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By jleech Date 2006-06-27 Time 08:00 Rev Time 0.00
Received By jleech Date 2006-06-27 Time 08:00 Sent To  
Notes
2006-06-27 00:00:00DENIED;
 1.BOTH BATHROOMS ARE REQUIRED TO BE
 HANDICAPED SEE FBC-2004 CHAPTER 11 SEC.
 11-4.1.3(11).
 2.SHOW DETAILS OF H/C BATHROOMS. ALL
 MEASUREMENTS, FOR PLUMBING FIXTURES,
 BATHROOM SIZE, AND GRAB BAR HIGHT.
 3.LOUNGE SINK TO COMPLY WITH
 SECS.11-4.24.1 THRU 11-4.24.7. SHOW
 DETAIL ON PLAN.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved