Plan Review Details - Permit 06060867
Plan Review Stops For Permit 06060867
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-08-03 Cont ID  
Sent By rmcdouga Date 2006-08-03 Time 10:10 Rev Time 0.00
Received By rmcdouga Date 2006-08-03 Time 10:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-07-10 Cont ID  
Sent By rmcdouga Date 2006-07-10 Time 10:20 Rev Time 0.00
Received By rmcdouga Date 2006-07-10 Time 10:20 Sent To  
Notes
2006-07-10 00:00:00DENIED
  
 1) THE ROOFING SYSTEM SPECIFIED ON PAGE
 40 OF THE MULE-HIDE PRODUCT NOA HAS A
 MAXIMUM DESIGN PRESSURE OF -60 PSF. THIS
 PRESSURE IS TO LOW FOR ZONE 3 (CORNERS).
 GENERAL LIMITATION #7 ON PAGE 43 OF THE
 NOA ALLOWS THE CORNERPRESSURES TO BE
 INCREASED BY INCREASING THE FASTENER
 DENSITIES USING THE CALCULATIONS
 SPECIFIED IN (RAS 117) ROOFING
 APPLICATION STANDARD 117. HOWEVER,
 GENERAL LIMITATION #7 ON THIS NOA
 REQUIRES THESE RAS 117 CALCULATIONS TO
 BE PREPARED, SIGNED AND SEALED BY A
 FLORIDA REGISTERED ENGINEER, ARCHITECT
 OR REGISTERED ROOF CONSULTANT. PLEASE
 SUBMIT TWO COPIES OF SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR THIS SYSTEM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By rmcdouga Date 2006-06-15 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2006-06-15 Time 07:48 Sent To  
Notes
2006-06-15 00:00:00DENIED
  
 1) THE ROOFING ASSEMBLY SELECTED FROM
 THE NOA (PAGE 35) FOR THE MULE HIDE
 BITUMEN ROOF SYSTEM HAS A DESIGN
 PRESSURE OF -45 PSF WHICH IS TOO LOW AND
 IS NOT ALLOWED TO BE INCREASED. SEE
 LIMITATION #9 ON PAGE 43.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  