Plan Review Details - Permit 06060856
Plan Review Stops For Permit 06060856
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-09 Cont ID  
Sent By amorse Date 2006-07-09 Time 10:22 Rev Time 0.75
Received By amorse Date 2006-07-09 Time 10:22 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By amorse Date 2006-07-03 Time 16:06 Rev Time 0.75
Received By amorse Date 2006-07-03 Time 16:06 Sent To PC
Notes
2006-07-03 00:00:00 
  
 DENIED
  
 1) THE PRESSURES THAT ARE STATED IN
 INSTALLATION SCHEDULE ARE HIGH AND THE
 SHUTTER SPANS AT THOSE PRESSURES MAX OUT
 BELOW WHAT YOU REQUIRE (SEE SHUTTER #3
 AT 13'-7" AND #12 AT 12'-9")
  
 2) PROVIDE TOP AND BOT MOUNT # ON
 INSTALLATION SCHEDULE FOR EACH SHUTTER
 TO BETTER SEE MAX ANCHOR SPACING
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-07 Cont ID  
Sent By adarroug Date 2006-07-07 Time 11:19 Rev Time 0.00
Received By adarroug Date 2006-07-07 Time 11:19 Sent To B
Notes
2006-07-07 00:00:00TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time   Rev Time 0.00
Received By adarroug Date 2006-06-16 Time 16:43 Sent To  
Notes
2006-06-16 00:00:00TO "MISC" BOX#1