Plan Review Details - Permit 06060809
Plan Review Stops For Permit 06060809
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-10-04 Cont ID  
Sent By rmcdouga Date 2006-10-04 Time 14:34 Rev Time 0.00
Received By rmcdouga Date 2006-10-04 Time 14:34 Sent To  
Notes
2006-10-04 00:00:00PLANS RETURNED FROM E. SCHINEDER IN
 ZONING. PROCESSED PLANS AND ISSUED
 PERMIT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-24 Cont ID  
Sent By rmcdouga Date 2006-08-24 Time 08:58 Rev Time 0.00
Received By rmcdouga Date 2006-08-24 Time 08:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-26 Cont ID  
Sent By rmcdouga Date 2006-06-26 Time 15:12 Rev Time 0.00
Received By rmcdouga Date 2006-06-26 Time 15:12 Sent To  
Notes
2006-06-26 00:00:00DENIED
  
 1) PRODUCT APPROVALS SUBMITTED
 WITH PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE
 AT WWW.FLORIDABUILDING.ORG. PRODUCTS
 WITH STATEWIDE APPROVAL ARE REQUIRED TO
 BE SUBMITTED WITH A COVER SHEET THAT
 LISTS THE PRODUCT IDENTITY NUMBER FROM
 THE STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. SUBMIT PRODUCT APPROVALS FOR
 THE IMPACT RATED STOREFRONT WINDOWS AND
 SIMPSON CONNECTORS.
  
 2) SPECIFY THE FASTENER TYPE AND NUMBER
 OF FASTENERS FOR THE SIMPSON CONNECTORS.
  
 3) SPECIFY THE EXTERIOR FINISH
 (CLADDING) AT THE SOFFIT.
  
 4) SPECIFY THE INSULATION AT THE
 SOFFIT/KNEEWALL.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-09-06 Cont ID  
Sent By mawillia Date 2006-09-06 Time 10:44 Rev Time 0.00
Received By mawillia Date 2006-09-06 Time 10:19 Sent To  
Notes
2006-09-06 00:00:00*****APPROVED*****
  
  
  
  
  
 1.)TO ASSIST EMERGENCY RESPONDERS IN
 LOCATING THIS PROPERTY, BE SURE THAT THE
 NUMERICAL ADDRESS IS VISIBLE FROM
 BROADWAY AVENUE. THESE NUMBERS(INCLUDING
 SUITE ALPHABET)SHALL BE NO LESS THAN 6"
 IN HEIGHT AND NO LESS THAN 1" IN WIDTH
 AS PER WEST PALM BEACH CODE. ADDRESS
 NUMBERS ARE TO BE POSTED ON THE BUILDING
 ( NOT ON THE WINDOWS OR DOORS. )
  
  
  
  
  
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2006-07-11 Cont ID  
Sent By mcarsill Date 2006-07-11 Time 10:59 Rev Time 0.00
Received By mcarsill Date 2006-07-11 Time 10:59 Sent To  
Notes
2006-07-11 00:00:001. SUBJECT TO FIELD INSPECTION AND
 APPROVAL WHEN FINAL INSTALLATION
 APPROVAL IS GIVEN BY THE CONSTRUCTION
 SERVICE DEPARTMENT.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709+

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-09-26 Cont ID  
Sent By adarroug Date 2006-09-26 Time 11:31 Rev Time 0.00
Received By adarroug Date 2006-09-26 Time 11:31 Sent To Z
Notes
2006-09-26 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-14 Cont ID  
Sent By adarroug Date 2006-08-14 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-08-14 Time 11:51 Sent To  
Notes
2006-08-23 00:00:00TO "BOB"#6
2006-08-14 00:00:00WAITING FOR "BOB"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-19 Cont ID  
Sent By adarroug Date 2006-07-19 Time 16:01 Rev Time 0.00
Received By adarroug Date 2006-06-15 Time 11:03 Sent To  
Notes
2006-06-26 00:00:00TO "COMM" BD#28
2006-06-15 00:00:00WAITING FOR "COMM" BD

Review Stop Z ZONING
Rev No 3 Status P Date 2006-10-03 Cont ID  
Sent By eschneid Date 2006-10-03 Time 09:55 Rev Time 0.00
Received By eschneid Date 2006-10-03 Time 09:55 Sent To  
Notes
2006-10-03 00:00:00NOTE - LANDSCAPE SHALL BE INSTALLED AS
 DISCUSSED DURING THE SITE VISIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-09-05 Cont ID  
Sent By eschneid Date 2006-09-05 Time 13:20 Rev Time 0.00
Received By eschneid Date 2006-09-05 Time 13:20 Sent To  
Notes
2006-09-05 00:00:00PRIOR COMMENTS NOT ADDRESSED.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-19 Cont ID  
Sent By eschneid Date 2006-07-19 Time 15:12 Rev Time 0.00
Received By eschneid Date 2006-07-19 Time 15:12 Sent To  
Notes
2006-07-19 00:00:001) SITE IS REQUIRED TO MEET THE PARKING
 LOT LANDSCAPE REQUIREMENTS SET FORTH IN
 SECTION 94-219(D)(9)B OF THE ZONING AND
 LAND DEVELOPEMENT REGULATIONS.
  
 2) EXTERIOR FINICH MATERIALS SHALL BE
 SHOWN ON THE ELEVATIONS MEETING SECTION
 94-221(D)(1).
  
 3) THE FACADE GLAZING CALCULATION AND
 THE HEIGHT OF THE WINDOW FROM THE GROUND
 IS REQUIRED TO MEET SECTION
 940219(D)(5).
  
 CONTACT ERIC SCHNEIDER (561) 822-1435.