2006-06-28 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW FOR A GAS PERMIT: |
| |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. PLEASE SEE CORRECTED |
| DRAWING IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED. PLEASE SEE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR RESUBMITTAL |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). PLEASE |
| CLARIFY TOTAL DISTANCE OF PIPE. (NOTE: |
| THIS INCLUDES EXISTING SYSTEM) DRAWING |
| INDICATES 40' EXISTING 1-1/4" PE PIPE, |
| AND 18' FLEX HOSE, THATS 58', NOT |
| COUNTING THE PIPE LENGTHS REQUISTED IN |
| COMMENT #1 THAT NEED TO BE ADDED TO THIS |
| TO GET THE TOTAL LONGEST LENGTH. |
| NOTE:IF SYSTEM IS LONGER THAN 40', |
| 1-1/4" PIPE SIZE IS TO SMALL, SEE |
| ATTACHED FBC-2004 TABLES FOR REFERENCE |
| FOR RESUBMITTAL. |
| 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| (NOTE: IS THE 18' FLEX HOSE APPROVED BY |
| ONE OF THE ABOVE) |
| 5. NOTE: PER FBC-2004 CHAPTER 1 SECTION |
| 106, THE PERSON RESPONSIBLE FOR THE |
| DRAWING SHALL PRINT AND SIGN NAME, AND |
| ALSO DATE DRAWING. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |