Plan Review Stops For Permit 06060723 |
Review Stop |
AD |
ADDRESSING |
Rev No |
2 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-04-03 |
Time |
16:01 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-04-03 |
Time |
16:01 |
Sent To |
|
|
Notes |
2007-04-03 16:02:40 | ADDRESS ON PERMIT APPLICATION CORRECTED PER CONTRACTOR | | AND OK PER ADDRESS REVIEWERS COMMENTS. |
|
|
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
F |
Date |
2006-06-16 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-06-16 |
Time |
10:40 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-06-16 |
Time |
10:38 |
Sent To |
|
|
Notes |
2006-06-16 00:00:00 | IF THE PERMIT APPLIES TO MARRIOT HOTEL | | ,THE CORRECT ADDRESS IS 1001 OKEECHOBEE | | BLVD ( PCN = 74434321120010010) AND NOT | | 630 CLEARWATER PARK RD ( PCN = | | 74434321120020000) AS ON THE | | APPLICATION.APPLICATION MUST BE | | CORRECTED BT THE APPLICANT! |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
4 |
Status |
P |
Date |
2007-03-08 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-03-08 |
Time |
13:34 |
Rev Time |
0.77 |
Received By |
jwitmer |
Date |
2007-03-08 |
Time |
13:34 |
Sent To |
|
|
Notes |
2007-03-08 13:37:20 | FOR GENERATORPAD AND GENERATOR ONLY! |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2007-01-18 |
Time |
10:04 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2007-01-18 |
Time |
10:04 |
Sent To |
|
|
Notes |
2007-01-18 11:08:54 | UILDING PLAN REVIEW | | PERMIT: 06060723 | | ADD: WEST PALM BEACH MARRIOT | | 1001 OKEECHOBEE BLVD | | CONT: HIGGINS ELEC | | TEL: (561)714-4403 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 2NDREVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) COMMENT# 2 FROM THE PREVIOUS REVIEW, | | E3.1 & P4.1 BOTH INDICATE A REVISION# 2 OF NEW LOUVERS | | AND A STEEL DOOR. | | FL BLD CODE 1609.1.4: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) LOUVERS | | B) EXTERIOR DOORS | | | | W P B ADMINISTRTIVE CODE 106.3.3* | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | CONTRACTOR RESPONSE: | | INDICATES THAT THE LOUVERS ARE EXISTING. | | A PRODUCT APPROVAL FOR THE DOOR ( INGERSOLL-RAND) WAS | | SUBMITTED FOR REVIEW. | | CONTRACTOR FAILED TO HAVE THE DESIGN PROFESSIONAL | | REVIEW AS REQUIRED IN THE CITY ADMINISTRATIVE CODE | | 106.3.3. | | | | 3) COMMENT# 3 FROM THE PREVIOUS REVIEW, | | WILL A GENERAL CONTRACTOR BE SUBMITTING FOR THE WORK | | MENTIONED IN COMMENT # 2? | | CONTRACTORS RESPONSE; | | THE CONTRACTOR HIGGINS ELECTRIC RESPONSE INDICATES THAT | | THERE IS "ABSOLUTELY NO WIND LOAD" ON THE LOUVERED | | SYSTEM AND NEW DOOR LOCATED BELOW GRADE IN AN EXISTING | | PIT. WIND FROM THE POSITIVE DIRECTION WILL RACE ALONG | | THE GROUND AND EITHER BUILD PRESSURE OR CREATE A | | VENTURIE AFFECT CAUSING NEGATIVE | | PRESSURE WITHIN THE PIT. PLEASE PROVIDE THE POSITVE AND | | NEGATIVE PRESSURES FOR THIS AREA. IT IS NOT CLEAR AS TO | | IF THIS PORTION OF BUILDING IS CONNECTED TO THE | | HIGH-RISEREQUIRING THE DESIGN TO BE ASCE 7-02, | | SECTION 6.5.12.4.2 BUILDINGS . 60'. THE OTHER FACTORS | | OF THE WIND RAISING AROUND THE HIGHRISE | | (NEGATIVE PRESSURES) WILL CREATE GREATER PRESSURES. | | ASCE 7-02 SECTION 6.5.6.2 COMPONENTS AND CLADDING FOR | | BUILDINGS WITH A MEAN ROOF HEIGHT IN EXCESS OF 60' AND | | FOR OTHER STRUCTURES SHALL BE DESIGNED USING THE | | EXPOSURE RESULTING IN THE HIGHEST WIND LOADS FOR ANY | | WIND DIRECTION AT THE SITE. PLEASE PROVIDE PRESSURES. | | | | THE SECOND ISSUE WITH THE CONTRACTORS RESPONSE IS A 10" | | CUSTOM CHANNEL FRAME, PLEASE PROVIDE ADDITIONAL | | INFORMATION, WHAT IS THIS FRAME TO BE USED FOR/ | | 106.1.2*. WHY IS A WELDER INSTALLING THE FRAME? IS THE | | FRAME BEING WELDED TO EMBEDS OR OTHER STEEL FRAMING? ON | | THE EXTERIOR OF THE BUILDING A C.G.C WILL BE REQUIRED | | TO WORK ON THE EXTERIOR FRAME AND COMPONENTS AND | | CLADDING. A WELDER MAY BE CERTIFIED TO FIELD WELDING | | BUT NOT THE INSTALATION OF THE | | EXTERIOR COMPONENTS AND CLADDING. | | | | THE OTHER ISSUE WITH THE EXTERIOR OF THE BUILDING | | ENVELOPE IS THE INSTALATION OF THE DOOR, THIS PERMIT | | APPLICATION DOES NOT HAVE ANY SUB-CONTRACTORS SIGNED ON | | QUALIFIED TO DO WORK IN THIS AREA. | | | | AS TO THE LOUVERS BEING INSTALLED BY THE MAINTENCE | | DEPARTMENT, THIS IS AN ALTERATION TO THE EXTERIOR OF | | THE BUILDING, NOT A MAINTENCE ISSUE. TO BE CONSIDERED | | NEW WORK BEING ACCOMPLISHED, THE MAINTENCE PERSONNEL | | ARE NOT LICENSED TO DO THIS TYPE OF WORK!!!!! | | FL S S 489.489.105(3) CONTRACTOR. | | | | 4) NEW COMMENT, IT APPEARS THAT THE CONTRACTOR HIGGINS | | ELECTRIC IS ADVERTISING HIMSELF TO BE A ENGINEER BY | | HAVING ENGINEERING, DESIGN AND INSTALLATION. | | ONE SET OF LETTERHEAD WILL BE RETAINED. PLEASE PROVIDE | | ENGINEERS SEAL, SEAL AND SIGN ALL DOCUMENTS . PLANS, | | SPECIFICATIONS, REPORTS OR | | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND | | BEING FILED FOR PUBLIC | | RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED | | TO THE DOCUMENT. | | FL STATE STAT: 61G15-23.002 ENGINEERS | | FL ATATE STAT: 61G16.003 ARCHITECTS | | 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE | | AFFIXED. | | (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND | | AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS, | | FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE | | OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR | | ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC | | RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED | | AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS, | | SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY | | UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER. | | | | BUILDING PLAN REVIEW | | JIM WITMER C. B. O. | | | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | E-MAIL: [email protected] | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-11-13 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-11-13 |
Time |
14:23 |
Rev Time |
1.22 |
Received By |
jwitmer |
Date |
2006-11-13 |
Time |
14:23 |
Sent To |
|
|
Notes |
2006-11-13 14:25:55 | BUILDING PLAN REVIEW | | PERMIT: 06060723 | | ADD: WEST PALM BEACH MARRIOT | | 1001 OKEECHOBEE BLVD | | CONT: HIGGINS ELEC | | TEL: (561)714-4403 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) NEW COMMENT, E3.1 & P4.1 BOTH INDICATE A REVISION# 2 | | OF NEW LOUVERS AND A STEEL DOOR. | | FL BLD CODE 1609.1.4: COMPONENTS & | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | TESTING REPORTS,MISSING REPORTS ARE AS | | FOLLOWS: | | A) LOUVERS | | B) EXTERIOR DOORS | | | | W P B ADMINISTRTIVE CODE 106.3.3* | | PRODUCT APPROVALS. THOSE PRODUCTS WHICH | | ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD PRIOR TO SUBMITTAL | | FOR JURISDICTIONAL APPROVAL. | | | | 3) WILL A GENERAL CONTRACTOR BE SUBMITTING FOR THE | | WORK | | MENTIONED IN COMMEENT # 2? | | | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-08-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2006-08-10 |
Time |
07:07 |
Rev Time |
2.22 |
Received By |
jwitmer |
Date |
2006-08-10 |
Time |
07:07 |
Sent To |
|
|
Notes |
2006-08-10 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 06060723 | | ADD: WEST PALM BEACH MARRIOT | | 1001 OKEECHOBEE BLVD | | CONT: HIGGINS ELEC | | TEL: (561)714-4403 | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1)--- VERY IMPORTANT STATEMENT --- | | PLEASE DO NOT IGNORE! | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | THE REVISION & REMOVE & REPLACE ANY | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | LISTING THE ORIGINAL REVIEW COMMENT NUM- | | BER, WITH A DESCRIPTION OF THE REVISION | | MADE, IDENTIFYING THE SHEET OR SPECIFICA | | TION PAGE WHERE THE CHANGES CAN BE FOUND | | WILL HELP TO EXPEDITE YOUR PERMIT. THANK | | YOU FOR YOUR ANTICIPATED COOPERATION. | | | | 2) ADDRESSING ISSUES. THE PERMIT | | APPLICATION INDICATES 630 CLEARWATER RD. | | IF THIS GENERATOR IS TO BE INSTALLED IN | | THE MARRIOT AS PLANS INDICATE THEY | | REQUESTED A NEW ADDRESS YEARS AGO AND | | ARE CURRENTLY USING 1001 OKECCHOBEE | | BLVD. PLEASE CORRECT THE PERMIT | | APPLICATION AND ADDRESS IN THE PLAN | | TITLEBLOCK. | | | | 3) PROVIDE A RERECORDED NOTICE OF | | COMMENCEMENT WITH THE CORRECT ADDRESS. | | FL S S 713.13NOTICE OF COMMENCEMENT, | | TO BE FILED WITH THE CLERK OF THE COURT | | BEFORE A PERMIT WILL BE ISSUED. NOTE: | | 713.13(2) IF THE WORK DESCRIBED IN THE | | NOTICE OF COMMENCEMENT IS NOT ACTUALLY | | COMMENCED WITHIN 90 DAYS AFTER THE | | RECORDING THEREOF, SUCH NOTICE IS NULL & | | VOID. | | | | 4) GENERATOR SLAB & ANCHOR REQUIREMENT | | PLEASE PROVIDE SIZE OF GENERATOR(WXL), | | PLUS PROVIDE PLANS WITH THE INFORMATION | | DEPICTING HOLD DOWN BRACKETS, TYPE OF | | FASTENER, AND THE MINIMUM EDGE DISTANCE | | THE DEVICE REQUIRES WITHOUT LOAD | | REDUCTION. | | SECOND, PROVIDE INFORMATION ON THE | | SLAB, THICKNESS, WIDTH AND LENGTH, IF | | WIREMESH, FIBER MESH OR IF STEEL REBAR | | WILL BEUSED. | | THE NEW SLAB AND HOLD DOWN DETAILS: | | 104.2.1* ALL INFORMATION, DRAWINGS, | | SPECIFICATIONS AND ACCOMPANYING DATA | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN. | | | | 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION | | THAT IS REQUIRED FOR RECORD | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | F) FLOOD ZONE(B) | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
5 |
Status |
P |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-03-30 |
Time |
09:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-03-30 |
Time |
08:46 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
F |
Date |
2007-02-11 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-02-11 |
Time |
18:37 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-02-11 |
Time |
17:51 |
Sent To |
|
|
Notes |
2007-02-11 18:38:38 | ** UNSAT ** | | | | 1) NOTE: PLEASE SEE PREVIOUS ZONING REVIEW COMMENTS AS | | SCREENING DOES SEEM TO HAVE BEEN SUBMITTED. | | | | 2) NOTE: PLEASE SEE GENERATOR LOAD SUMMARY ON E5.1 | | WHICH SHOWS HQ ON LOAD SUMMARY. IS THIS ANOTHER UNIT OR | | IS THIS EQ? THIS SEEMS TO HAVE BEEN A MISPRINT AND MAY | | HAVE BEEN REDLINED, HOWEVER AS THE PLANS AND RISER HAVE | | BEEN COMPLETELY REVISED ON SO MANY OCCASIONS, THIS IS | | NOT BEING ASSUMED. | | | | 3) NOTE: PLEASE SEE THE LOAD ON EMDP IS NOT THE SAME | | LOAD AS SHOWN ON MDP2 FOR THE SAME ? | | PLEASE CORRECT AND CORRELATE. | | 220, 215.5, 240.4, 310.16 ETC | | FBC 106.1.2 | | | | 4) NOTE: PLEASE SEE A 4X FEED WAS ASSESSED FOR THE | | INSTALLATION OF GENERATOR/ GAS /ELECTRICAL ETC. | | A FEE OF $6300 IS NOW DUE. | | | | 5) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT | | SUBMITTED WILL BE REQUIRED TO BE RE-RECORDED AND | | SUBMITTED BEFORE PICKING UP PERMIT AS IT HAS BECOME | | VOID PER FS 713.13(2). THIS IS INFORMATION GIVEN AT | | THIS TIME. | | | | | | * ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
F |
Date |
2007-01-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-13 |
Time |
17:28 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2007-01-13 |
Time |
15:38 |
Sent To |
|
|
Notes |
2007-01-13 17:29:32 | ** UNSAT 3RD REVIEW** | | | | | | ** PLEASE SEE COMMENTS BELOW ARE BASED ON THE REVISED | | PLANS SUBMITTED. | | ** PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW, NO | | PREVIOUS REVIEWED ORIGINAL PLANS WERE SUBMITTED FOR | | REFERENCE. PLEASE SUBMIT ONE SET OF EACH OF THE | | PREVIOUS PLANS. | | | | 1) NOTE:PLEASE SUBMIT TWO SETS OF PLANS WITH ALL | | SHEETS PLACED INTO SETS AND SHEETS ATTACHED. | | PLEASE SEE MORE THAN TWO SETS OF MANUFACTURES SPEC/CUT | | SHEETS WERE SUBMITTED AND EACH OF THESE CONTAIN | | DIFFERENT SHEETS. PLEASE SUBMIT ONLY THE TWO SETS NEED | | FOR REVIEW OF SAID SHEETS. | | 106.1.2, 106.1. | | | | ***PLEASE SEE COORDINATION BETWEEN THE RISER, LOADS AND | | PANELS NEED TO BE ADDRESSED. | | THE COMMENTS BELOW ARE BEING NOTED, HOWEVER DUE TO THE | | NEW REVISED RISER AND THE AMOUNT OF NEEDED CHANGES | | THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW. | | | | 2) NOTE: | | A) PLEASE SEE MDP2-8 SHOWS A 400A BREAKER FEEDING WHAT | | IS LABELED ATS-EQ. | | PLEASE SEE THE LOAD ON THIS IS BEING SHOWN AS | | 34.7/35.1/34.5 WHICH IS THE LOAD SHOWN ON PANEL HEQ. | | B) PLEASE SEE HOWEVER RISER IS NOW SHOWING THE MDP3 | | BEING FED FROM THE ATS-EQ NOW WITH OUT ANY LOAD | | CONSIDERATION BEING SHOWN. PLEASE SEE THE LOAD ALONE | | BEING SHOWN ON MDP3 IS 416.7 KVA WHICH IS NOT ON MDP2 | | OR IN THE GENERATOR LOAD SUMMARY. | | PLEASE CORRELATE THE GENERATOR LOAD SUMMARY WITH ALL | | LOADS. | | C) PLEASE SEE THE RISER NOW SHOWS A 175AMP DISCONNECT | | BEING INSTALLED FROM THE ATS EQ TO THE MDP3? HOW IS IT | | POSSIBLE FOR THIS TO BE 175AMPS WHEN THE LOAD UNDER | | NORMAL EXCEEDS THAT OF THIS EQUIPMENT? PLEASE SEE THE | | NOTE ABOVE AS ONCE AGAIN, NO LOADS FOR THE MDP3 IS | | BEING SHOWN AS PART OF THE LOAD ON THE GENERATOR, YET | | IT IS BEING SHOWN CONNECTED TO THIS SYSTEM. | | D) PLEASE CLEAR UP RISER AND WHETHER OR NOT THE MDP3 IS | | FED FROM THE SAME BREAKER THAT IS BEING SHOWN FOR | | ATS-EQ AND HEQ. IF THE HEQ IS FED FROM THE 400A BREAKER | | ON MDP2 THIS IS FINE HOWEVER THE ADDITION OF THE NEW | | MDP3 HAS CREATED AN ENTIRE NEW LIST OF COMMENTS. | | E) PLEASE SEE BASED ON THE ADDITION OF MDP3 ON THE | | RISER, THE FEEDERS BEING SHOWN AS ATS-2 AND ATS-3 ARE | | NOT SUFFICIENT UNDER NORMAL OR LOADS UNDER EMERGENCY. | | HOW CAN THE NORMAL SIDE OR THE EMERGENCY SIDE INDICATE | | CONDUCTORS LESS THAN THE LOAD AS SHOWN? | | | | 240.4, 310.16, 230.70, 220, 240.21, 215.5, 215.3, | | 230.42, 230.79, 225.39 ETC. | | PLEASE KNOW THERE ARE NUMEROUS SECTIONS WHICH COULD BE | | NOTED.2002 NEC | | PLEASE REVISE RISER AND COORDINATE ALL. | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | REVIEWER. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-11-20 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-11-20 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-11-20 |
Time |
07:30 |
Sent To |
|
|
Notes |
2006-11-20 09:02:28 | *** UNSAT 2ND REVIEW *** | | | | | | *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS | | STILL IN NEED OF ADDRESSING. PLEASE ALSO WEE NOTES | | WHICH ARE NEW BASED ON REVISED ITEMS NOW SHOWN ON | | PLANS. | | | | ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM | | PREVIOUS REVIEW AND MARKED WITH AN OK! , NO! (WITH | | FURTHER EXPLANATION) OR SOME MAY BE LABELED WITH OK/NO | | AS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED ONLY. | | | | | | 1) NOTE: OK. | | | | 2) NOTE: OK. | | | | 3) NOTE: OK. | | | | 4) NOTE: OK. | | | | 5) NOTE:NO, PLEASE SEE THE COMMENT AS PREVIOUSLY | | NOTED WAS TO OBTAIN CORRECT LOCATION TO BE COORDINATED | | WITH THE FIRE MARSHAL'S OFFICE AND SHALL BE SHOWN AND | | NOTED ON THE PLANS THIS WAY. THE PLANS RESPONSE AND | | "KEY NOTE" READS TO BE LOCATED WITH THE OWNER. THIS IS | | THE DECISION OF THE FIRE MARSHAL'S OFFICE AND THE CODE | | ONLY. PLEASE ALSO SEE CODE SECTION AS PREVIOUSLY GIVEN. | | FOR LOCATION REQUIREMENTS | | | | ** PREVIOUS REVIEW NOTE REVIEW # 1 ** | | PLEASE SEE GEN ANNUCIATOR PANEL SHALL BE LOCATED IN THE | | FIRE COMMAND ROOM, OR LOCATION OF FACP, NEAREST POINT | | DESIGNATED BY THE FIRE MARSHAL'S OFFICE. | | NFPA-101 CHAPTER 11.8.5. | | | | 6) NOTE: OK. RESPONSE LETTER MENTIONS THERE IS A DIESEL | | DRIVEN FIRE PUMP. | | | | | | 7) NOTE: OK/ NO, | | PLEASE SEE SPECIFICATIONS FROM THE MANUFACTURE STILL | | INDICATE AS 706 GALLONS. RESPONSE LETTER MENTIONS THAT | | THE TANK WILL BE BAFFLED, YET THE SPECIFICATIONS FROM | | THE MANUFACTURE NEED TO INDICATE THIS AT THIS TIME. | | PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES. | | | | | | | | | | 8) NOTE: OK, HOWEVER SEE NEW NOTES. | | | | | | 9) NOTE:NO, PLEASE SEE PREVIOUS NOTE, AS SHOWN ON | | PLANS, 4-POLE TRANSFER SWITCHES WILL BE REQUIRED. THIS | | IS BASED ON THE RISER AS SHOWN. THE GENERATOR IS BEING | | SHOWN AS SEPARETLY DERIVED, EVEN THOUGH NOTE MENTIONS | | IT WILL NOT BE. | | PLEASE SEE RISER. | | | | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** | | PLEASE SEE NOTES MENTIONS THAT THE GEN WILL "NOT" BE A | | "SEPARATELY | | DERIVED SYSTEM" YET, GENERATOR SEEMS TO | | BE SHOWN WITH A BOND FROM THE GEN FRAME AND GROUND BAR | | TO THE GEN WINDINGS? | | PLEASE KNOW, IF THIS OCCURS, THEN THIS "IS" A SDS AND | | SHALL THEN CONTAIN A | | 4-POLE ATS'S, GE SYSTEM AND NOTED AS SO. | | PLEASE VERIFY AND ADJUST PLANS AS NEEDED. | | | | 10) NOTE: NO, PLEASE SEE THIS WAS SUBMITTED; HOWEVER | | PLEASE SEE THE SHEETS IN FACT CONTAIN RAISED SEALS OVER | | A "PHOTO-COPIED" SIGNATURE FROM THE ENGINEER OF RECORD. | | ( MR. ALBERT KWAN) PLEASE SEE FLORIDA STATUTES 471.025, | | AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE | | KNOW THIS IS REVIEW WHETHER OR NOT COMMENT IS MADE BY | | BUILDING REVIEW. | | PLEASE ALSO SEE SHEET MENTIONS TO BE 6INCHES ABOVE | | FLOOR ELEVATION HOWEVER, EQUIPMENT SHALL BE 6 INCHES | | ABOVE THE BFE BASED ON THE 100 YR YEAR STORM SURGES | | LEVELS OR SURGE LEVELS BASED ON A CAT 4 STORM. PLEASE | | SEE SLOSH CHARTS ETC. | | PLEASE SEE SECTIONS GIVEN IN PREVIOUS REVIEW NOTE. | | | | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** | | PLEASE BUILDING REVIEW COMMENTS WITH RESPECT TO THE | | GEN SLAB DETAIL. PLEASE SEE NO DETAIL, CONNECTIONS, | | ELEVATIONS WERE SUBMITTED. | | PLEASE ALSO SEE NOTE MENTIONS THE GEN @ OR ABOVE BFE. | | PLEASE KNOW, THE GEN/ ASSOCIATED EQUIPMENT SHALL BE 6" | | ABOVE THE BFE. | | PLEASE SEE NFPA-110 CHAPTER 7, 7.2, 7.3, | | 7.4, 7.9 ETC. | | ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, EPSS | | REQUIREMENTS ETC,THE SLAB WILL BE REQUIRED TO BE | | SIGNED, DATED AND SEALED BY AN ENGINEER. | | FS 471.003 | | | | 11) NOTE:NO, SAME NOTE. | | | | ** PREVIOUS REVIEW NOTE FROM REVIEW #1 ** | | PLEASE BE SURE THE ENGINEER OF RECORD SIGNS PLANS WITH | | HIS LEGAL/EASILY RECOGNIZABLE SIGNATURE KNOWN TO THIS | | OFFICE AND ON RECORD IN THIS OFFICE. | | FS 471.025, FAC 61G15-23.002 | | | | | | **** NEW NOTES FROM THE 2ND REVIEW *** | | | | 12) NOTE: PLEASE SUBMIT THE MANUFACTURE | | SPECIFICATION/CUT SHEETS ON THE WP HOUSING FOR THE | | GENERATOR. | | FBC 106.1.2, | | 110.3,90.7 | | | | 13) NOTE: PLEASE BE SURE EITHER PLANS OR MANUFACTURE | | SPECIFICATIONS INDICATE THE FUEL CONSUMPTION BASED ON | | DIESEL ONLY. | | SPECS APPEAR TO SHOW AS BI-FUEL ONLY. | | | | 14) NOTE: PLEASE SEE RESPONSE LETTER MENTIONS SHEETS | | EQ.1, IS THIS NOT E0.1? THIS ONLY APPEARS TO BE A | | MISPRINT. | | PLEASE EXPLAIN RATIONAL ON THE SIZING OF THE BREAKERS | | FROM THE GENERATOR. PLEASE SEE THE EMDP HAS A LOAD OF | | 238A'S +/- WITH A 300A BREAKER FEEDING THIS 600A PANEL | | BOARD. WHEREAS THE PANEL "HEQ" WHICH IS ONLY RATED | | 400A'S AND HAS ONLYA LOAD OF 105A'S +/- , YET HAS A | | 350A BREAKER AT THE GENERATOR FOR OVER CURRENT | | PROTECTION. | | THIS IS UNCLEAR WHY THE EQUIPMENT WITH LOAD WHICH IS | | SUBSTANTIALLY MORE CONTAINS A LOWER OVER CURRENT | | PROTECTION. | | PLEASE EXPLAIN AND CORRELATE. | | FBC 106.1.2 ADMIN SECT. | | | | 15) NOTE: PLEASE SEE FEEDER SCHEDULE ON RISER AND THAT | | ON MDP2, PLEASE CORRELATE. PLEASE ALSO SEE FEEDER | | SCHEDULE. | | | | 16) NOTE: PLEASE SEE RISER SHOWS A TRANSFORMER T-8 | | BEING FED FROM HEQ, YET HEQ WITH THE CIRCUITS AS SHOWN | | ON RISER INDICATE THESE AS ?SPARE? ON SCHEDULE??? | | PLEASE CORRELATE CIRCUITING AS SHOWN FROM RISER TO | | PANEL SCHEDULE. | | FBC 106.1.2 ADMIN SECTION. | | | | 17) NOTE: PLEASE HIGH-LIGHT THE SPECIFIC TRANSFER | | SWITCH BEING USED ON THE MANUFACTURE SPECS/CUT SHEETS | | SUBMITTED. THERE IS A "SUGGESTED SPECIFICATION" BOOKLET | | SUBMITTED, HOWEVER PLEASE INDICATE ON SPECS. | | 110.3,90.7. | | FBC 106.1.2 | | | | | | | | | | ** ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. | | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF | | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE | | DO NOT HESITATEIN CONTACTING THIS REVIEWER. | | | | | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTRUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-30 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-30 |
Time |
07:55 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-30 |
Time |
06:46 |
Sent To |
|
|
Notes |
2006-06-30 00:00:00 | ********* UNSAT ********* | | | | 1) NOTE: PLEASE SEE ADDRESSING REVIEW | | AND COMMENTS AS THE CORRECT ADDRESS FOR | | THE MARRIOT IS 1001 OKEECHOBEE BLVD. | | THIS ADDRESS WAS CHANGED A COUPLE OF | | YEARS AGO. | | PLEASE ADJUST ALL PLANS/TITLE BLOCKS ARE | | REQUIRED FAC 61G15-23.002/61G1-16.004 | | | | 2) NOTE: PLEASE CLARIFY THE KW RATING OF | | THE GEN AS ONE SHEET IN THE | | SUBMITTAL/SPEC PACKAGE CONTAINS 400KW? | | | | 3) NOTE: PLEASE BE SURE TO PROVIDE ALL MANUFACTURES | | CUT/SPEC SHEETS FOR GEN AND | | ATS. APPEARS TO BE MISSING COVER SHEETS | | ETC. | | FBC ADMIN SECT 106.1.2 | | | | 4) NOTE: PLEASE SEE THAT PLANS REFLECT | | ALL CURRENT CODES IN AFFECT. | | NFPA-70 2002, NFPA-101 2003, NFPA-110 | | 2002. | | | | 5) NOTE: PLEASE SEE GEN ANNUCIATOR PANEL | | SHALL BE LOCATED IN THE FIRE COMMAND | | ROOM, OR LOCATION OF FACP, NEAREST POINT DESIGNATED BY | | THE FIRE MARSHAL'S OFFICE. | | NFPA-101 CHAPTER 11.8.5. | | | | 6) NOTE: PLEASE CLARIFY IF THE FIRE PUMP | | IS FED FROM THIS GEN. ?? | | IF SO, PLEASE KNOW, THERE MUST BE A MIN | | OF 8HRS "ON-SITE" FUEL FOR 100% OF THE | | FULL LOAD RATING OF THE FIRE PUMP AND | | OTHER ASSOCIATED EM EQUIPMENT.2003 | | NFPA-20 9.6.2.2 | | PLEASE ALSO PROVIDE GPH WITHOUT THE TIE | | IN OF THE NAT GAS LINE AND WITH THE TIE | | IN OF THE NAT GAS LIN. | | | | | | 7) NOTE: PLEASE SEE FIRE REVIEW AND | | MECHANICAL REVIEW COMMENTS WITH RESPECT | | TO FUEL PIPING/ TANK SIZE AND STORAGE. | | 7.9.12LISTED GENERATOR SUB-BASE | | SECONDARY CONTAINMENT FUEL TANKS OF 2498 | | L (660 GAL) CAPACITY AND BELOW SHALL BE | | PERMITTED TO BE INSTALLED OUTDOORS OR | | INDOORS WITHOUT DIKING OR REMOTE | | IMPOUNDING. | | 7.9.12.1A MINIMUM CLEARANCE OF 0.9 M | | (36 IN.) SHALL BE MAINTAINED ON ALL | | SIDES. | | 7.9.3.1GALVANIZED FUEL LINES SHALL NOT | | BE USED. | | ** | | PLEASE SEE TANK SIZE IS BEING INDICATED | | AS 706 GALS. | | | | | | 8) NOTE: PLEASE SEE ATS-LS IS BEING FROM | | A 400A OCP AND EQUIPMENT IS RATED FOR | | 300A'S AND FEED FROM GEN IS 250A'S?? | | PLEASE CORRELATE. | | 215.5 | | | | 9) NOTE: PLEASE SEE NOTES MENTIONS THAT | | THE GEN WILL "NOT" BE A "SEPARATELY | | DERIVED SYSTEM" YET, GENERATOTR SEEMS TO | | BE SHOWN WITH A BOND FRON THE GEN FRAME | | AND GRND BAR TO THE GEN WINDINGS? | | PLEASE KNOW, IF THIS OCCURS, THEN THIS | | "IS" A SDS AND SHALL THEN CONTAIN A | | 4-POLE ATS'S, GE SYSTEM ANDNOTED AS | | SO. | | PLEASE VERIFY AND ADJUST PLANS AS | | NEEDED. | | | | 10) NOTE: PLEASE BUILDING REVIEW | | COMMENTS WITH RESPECT TO THE GEN SLAB | | DETAIL. PLEASE SEE NO DETAIL, | | CONNECTIONS, ELEVATIONS WERE SUBMITTED. | | PLEASE ALSO SEE NOTE MENTIONS THE GEN @ | | OR ABOVE BFE. PLEASE KNOW, THE GEN/ | | ASSOCIATED EQUIPMENT SHALL BE 6" ABOVE | | THE BFE. | | PLEASE SEE NFPA-110 CHAPTER 7, 7.2,7.3, | | 7.4,7.9 ETC. | | ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, | | EPSS REQUIREMNTS ETC,THE SLAB WILL BE | | REQUIRED TO BE SIGNED, DATED AND SEALED | | BY AN ENGINEER. | | FS 471.003 | | | | 11) NOTE: PLEASE BE SURE THE ENGINEER OF | | RECORD SIGNS PLANS WITH HIS LEGAL/EASILY RECOGNIZABLE | | SIGNATURE KNOWN TO THIS | | OFFICE AND ON RECORD IN THIS OFFICE. | | FS 471.025, FAC 61G15-23.002 | | | | ** PLEASE BE SURE TO SEE ANY OTHER | | COMMENTS FROM OTHER TRADES WHICH MAY | | AFFECT ELECTRICAL PLANS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
4 |
Status |
P |
Date |
2007-03-07 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2007-03-07 |
Time |
16:53 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2007-03-07 |
Time |
16:53 |
Sent To |
|
|
Notes |
2007-03-07 16:53:34 | *****APPROVED***** | | | | | | | | | | TO BE STAMPED WHEN OTHER PLAN REVIEWS HAVE BEEN | | SATISFIED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-18 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2007-01-18 15:50:43 | NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY | | CONTRACTOR WITHOUT THIS REVIEW BEING DONE. |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2006-12-21 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-12-21 |
Time |
12:36 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-12-21 |
Time |
12:36 |
Sent To |
|
|
Notes |
2006-12-21 12:37:41 | *****APPROVED***** | | | | | | | | | | TO BE STAMPED WHEN OTHER PLAN REVIEWS HAVE BEEN | | SATISFIED |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-08-18 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-08-18 |
Time |
10:37 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-08-18 |
Time |
10:37 |
Sent To |
|
|
Notes |
2006-08-18 00:00:00 | ***DENIED*** | | | | 1) PLEASE SEE OTHER REVIEW COMMENTS | | REGARDING ADDRESSING AND MAKE | | CORRECTION. THE ADDRESS SHOULD REFLECT | | 1001 OKEECHOBEE BLVD. | | | | 2) NFPA 101, 2003 EDITION SHALL BE | | REFERENCED. | | | | 3) PLEASE CLEARLY IDENTIFY LOCATION OF | | GENERATOR AND FUEL TANK WITH RELATION TO | | BUILDING OPENINGS AND ILLUSTRATE | | DISTANCES. PLEASE SUBMIT SITE PLAN FOR | | REVIEW. | | | | 4) WORK TO COMPLY WITH NFPA 110, 2002 | | EDITION. | | | | 5) DEPENDANT UPON LOCATION OF EQUIPMENT, | | SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY | | BE REQUIRED AND SHALL BE ILLUSTRATED. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
3 |
Status |
P |
Date |
2007-03-12 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-12 |
Time |
09:08 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-12 |
Time |
09:08 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
2 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-12-01 |
Time |
08:58 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-12-01 |
Time |
08:58 |
Sent To |
|
|
Notes |
2006-12-01 08:58:50 | DENIED: | | | | 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION | | INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE | | SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823, | | INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE | | CORRELATE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
FUEL |
DIESEL GENERATOR |
Rev No |
1 |
Status |
F |
Date |
2006-08-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-08-21 |
Time |
08:12 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-08-21 |
Time |
08:12 |
Sent To |
|
|
Notes |
2006-08-21 00:00:00 | DENIED: | | | | PLEASE PROVIDE INFORMATION ON THE | | SHUTOFF VALVES ON THE SUB-BASE FUEL | | TANK.SHOW COMPLIANCE WITH 2004 FMC | | CHAPTER 13. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | E-MAIL [email protected]. | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
5 |
Status |
P |
Date |
2007-05-07 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-05-07 |
Time |
10:04 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-05-07 |
Time |
10:04 |
Sent To |
|
|
Notes |
2007-05-07 10:04:57 | REVISION OK - CHANGED PIPING TO GALV. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
4 |
Status |
P |
Date |
2007-02-28 |
|
|
Cont ID |
|
Sent By |
kstevens |
Date |
2007-02-28 |
Time |
13:46 |
Rev Time |
0.00 |
Received By |
kstevens |
Date |
2007-02-28 |
Time |
13:46 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
3 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-18 |
Time |
15:50 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2007-01-18 15:51:16 | NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY | | CONTRACTOR WITHOUT THIS REVIEW BEING DONE. | | PLANS DID CONTAIN NEW GAS SHEETS FOR REVIEW. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2006-12-09 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-12-09 |
Time |
10:13 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-12-09 |
Time |
10:12 |
Sent To |
|
|
Notes |
2006-12-09 10:13:23 | RE SUB | | SEPERATE GAS PERMIT REQUIRED. |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2006-07-29 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-07-29 |
Time |
07:14 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-07-29 |
Time |
07:14 |
Sent To |
|
|
Notes |
2006-07-29 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | UNSAT | | (A) SHTP4.1 THE FOLLOWING INFORMATION IS | | REQUIRED FOR THE GAS PERMIT: | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. TYPE OF GAS, (LP OR NATURAL) | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | 402.4(33). | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES A.3.1(4). | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | GAS CODE SECTION 304 | | . | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2001 FUEL GAS CODE SEC 402.2. | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | STANDARDS NFPA 54, NFPA 58, AND THE | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | (B) SEE OTHER PLAN REVIEW COMMENTS, THAT | | MAY EFFECT GAS PLAN REVIEW. | | | | (C) WHEN RESUBMITTING PLANS PLEASE | | INDICATE THE REVISION & REMOVE & REPLACE | | ANY PAGES AS NECESSARY. A TRANSMITTAL | | LETTER LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER, WITH A DESCRIPTION OF | | THE REVISION MADE, IDENTIFYING THE SHEET | | OR SPECIFICATION PAGE WHERE THE CHANGES | | CAN BE FOUND WILL HELP TO EXPEDITE YOUR | | PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
6 |
Status |
N |
Date |
2007-03-30 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-30 |
Time |
17:44 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-30 |
Time |
17:44 |
Sent To |
|
|
Notes |
2007-03-30 17:45:10 | TO COMM BOARD # 19 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
5 |
Status |
N |
Date |
2007-03-28 |
|
|
Cont ID |
|
Sent By |
spalmer |
Date |
2007-03-28 |
Time |
17:21 |
Rev Time |
0.00 |
Received By |
spalmer |
Date |
2007-03-28 |
Time |
17:21 |
Sent To |
|
|
Notes |
2007-03-28 17:22:00 | WAITING FOR COMM BOARD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2007-02-02 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2007-02-02 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2007-02-02 |
Time |
11:21 |
Sent To |
|
|
Notes |
2007-02-08 11:23:26 | TO "COMM" BD#38 | 2007-02-02 11:21:44 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-12-22 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-12-22 |
Time |
13:14 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-12-22 |
Time |
13:14 |
Sent To |
|
|
Notes |
2007-01-11 16:54:46 | TO "COMM" BD#7 | 2006-12-22 13:15:05 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-11-04 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-11-04 |
Time |
18:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-11-04 |
Time |
18:13 |
Sent To |
|
|
Notes |
2006-11-07 14:24:04 | TO "COMM" BD#31 | 2006-11-04 18:13:59 | WAITING FOR"COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-23 |
|
|
Cont ID |
|
Sent By |
alange |
Date |
2006-08-23 |
Time |
14:31 |
Rev Time |
0.00 |
Received By |
alange |
Date |
2006-06-14 |
Time |
15:43 |
Sent To |
|
|
Notes |
2006-06-24 00:00:00 | TO COMM BOARD # 33, NEEDS Z,B,M,E,P,F | 2006-06-14 00:00:00 | WAITING FOR "COMM" BD |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2007-03-12 |
|
|
Cont ID |
|
Sent By |
rregueir |
Date |
2007-03-08 |
Time |
09:53 |
Rev Time |
0.00 |
Received By |
rregueir |
Date |
2007-03-12 |
Time |
09:07 |
Sent To |
|
|
Notes |
2007-03-08 09:53:40 | ALL MECHANICAL REVIEW COMMENTS HAVE BEEN SATISFIED. | | | | | | RONALD J REGUEIRO | | 561-805-6719 | | [email protected] |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2007-01-18 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2007-01-18 |
Time |
15:51 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
Notes |
2007-01-18 15:51:39 | NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY | | CONTRACTOR WITHOUT THIS REVIEW BEING DONE. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2006-12-01 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-12-01 |
Time |
07:12 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-12-01 |
Time |
07:12 |
Sent To |
|
|
Notes |
2006-12-01 07:27:29 | DENIED: | | COMMENTS FROM REVIEW DATED 10-28-06: | | | | COMMENT 1:REQUEST FOR CLEARANCES TO THE PROPERTY | | LINE, ADJACNT BUIDLINGS, FRESH AIR INTAKES, DOORS, | | WINDOWS, LOUVERS, ETC.RESPONSE INDICATES REVISED | | DRAWING PROVIDE THIS INFORMATION. THE ONLY DIMENSION | | PROVIDED IS ON PLAN SHEET E3.1 WHICH INDICATES 6 FEET | | FROM THE BUILDING.PER 2004 FMC 401.5.1, FRESH AIR | | INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FEET FROM | | ANY HAZARDOUS OR NOXIOUS CONTAMINANT. | | | | COMMENT 2:INDICATE IF PROTECTION FROM DAMAGE IS | | REQUIRED IN ACCORDANCE WITH 2004 FMC 401.5.RESPONSE | | INDICATES "SEE REVISED DRAWINGS".PLANS DO NOT | | INDICATE ANY PROTECTION OR ANNOTATE HOW THIS IS | | ACCOMPLISHED. | | | | COMMENT 3:OKAY. | | **************NEW COMMENT*********** | | | | 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION | | INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE | | SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823, | | INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE | | CORRELATE. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS | | AT (561)805-6719 OR E-MAIL [email protected]. |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2006-08-21 |
|
|
Cont ID |
|
Sent By |
pkrauss |
Date |
2006-08-21 |
Time |
07:28 |
Rev Time |
0.00 |
Received By |
pkrauss |
Date |
2006-08-21 |
Time |
07:03 |
Sent To |
|
|
Notes |
2006-08-21 00:00:00 | DENIED: | | 1.PLEASE PROVIDE DISTANCES/CLEARANCES | | TO THE FOLLOWING; PROPERTY LINES, | | BUILDINGS, FRESH AIR INTAKES, WINDOWS, | | DOORS, LOUVERS, ETC.SHOW COMPLIANCE | | WITH 2004 FMC 401.5. | | | | 2.INDICATE IF PROTECTION FROM DAMAGE | | IS REQUIRED IN ACCORDANCE WITH 2004 FMC | | 303.4. | | | | 3.PROVIDE DETAIL INFORMATION ON THE | | ANCHORING OF THE GENERATOR. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | E-MAIL [email protected]. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
N |
Date |
2006-07-29 |
|
|
Cont ID |
|
Sent By |
pschmitz |
Date |
2006-07-29 |
Time |
07:13 |
Rev Time |
0.00 |
Received By |
pschmitz |
Date |
2006-07-29 |
Time |
06:55 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
5 |
Status |
P |
Date |
2007-04-03 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2007-04-03 |
Time |
15:13 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2007-04-03 |
Time |
15:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
Z |
ZONING |
Rev No |
4 |
Status |
F |
Date |
2007-02-26 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2007-02-26 |
Time |
14:21 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2007-02-26 |
Time |
14:20 |
Sent To |
|
|
Notes |
2007-02-26 14:26:15 | PLEASE PROVIDE EXACT LOCATION OF SCREEN ON SITE PLAN. | | THEARCHITECTURAL DETAILINGOF THE SCREEN MUST BE | | PROVIDED FOR REVIEW. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
3 |
Status |
F |
Date |
2007-01-17 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2007-01-17 |
Time |
14:52 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2007-01-17 |
Time |
14:52 |
Sent To |
|
|
Notes |
2007-01-17 15:11:04 | PLEASE PROVIDE DRAWINGS FOR THE PROPOSED SCREEN. THE | | DIMENSIONED DRAWINGS MUST INCLUDE INFORMATION REGARDING | | MATERIALS. AS PER THE DOWNTOWN CODE, THE PROPOSED | | SCREEN MUST BE ARCHITECTURALLY COMPATIBLE WITH THE | | BUILDING ANDDESIGNED AS AS INTEGRAL PART OF THE | | OVERALL STRUCTURE. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
F |
Date |
2006-11-21 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2006-11-21 |
Time |
11:48 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2006-11-21 |
Time |
11:47 |
Sent To |
|
|
Notes |
2006-11-21 12:00:18 | THE DMP REQUIRES MECHANICAL EQUIPMENT TO BE SCREENED. | | MORE SPECIFICALLY, THE CODE REQUIRES DEVICES WHICH | | CONTAIN FUEL TANKS, SUCH AS GENERATORS, TO BE SCREENED. | | PLEASE REVIEW SEC. 94-444(B) OF THE CODE FOR THE | | GUIDELINES. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2006-07-18 |
|
|
Cont ID |
|
Sent By |
astelly |
Date |
2006-07-18 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
astelly |
Date |
2006-07-18 |
Time |
14:44 |
Sent To |
|
|
Notes |
2006-07-18 00:00:00 | PLEASE SUBMIT A SITE PLAN SHOWING THE | | LOCATION OF THE GENERATOR FOR REVIEW. |
|
|