Plan Review Details - Permit 06060723
Plan Review Stops For Permit 06060723
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2007-04-03 Cont ID  
Sent By dpalmer Date 2007-04-03 Time 16:01 Rev Time 0.00
Received By dpalmer Date 2007-04-03 Time 16:01 Sent To  
Notes
2007-04-03 16:02:40ADDRESS ON PERMIT APPLICATION CORRECTED PER CONTRACTOR
 AND OK PER ADDRESS REVIEWERS COMMENTS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By lursu Date 2006-06-16 Time 10:40 Rev Time 0.00
Received By lursu Date 2006-06-16 Time 10:38 Sent To  
Notes
2006-06-16 00:00:00IF THE PERMIT APPLIES TO MARRIOT HOTEL
 ,THE CORRECT ADDRESS IS 1001 OKEECHOBEE
 BLVD ( PCN = 74434321120010010) AND NOT
 630 CLEARWATER PARK RD ( PCN =
 74434321120020000) AS ON THE
 APPLICATION.APPLICATION MUST BE
 CORRECTED BT THE APPLICANT!

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2007-03-08 Cont ID  
Sent By jwitmer Date 2007-03-08 Time 13:34 Rev Time 0.77
Received By jwitmer Date 2007-03-08 Time 13:34 Sent To  
Notes
2007-03-08 13:37:20FOR GENERATORPAD AND GENERATOR ONLY!

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2007-01-18 Cont ID  
Sent By jwitmer Date 2007-01-18 Time 10:04 Rev Time 2.22
Received By jwitmer Date 2007-01-18 Time 10:04 Sent To  
Notes
2007-01-18 11:08:54UILDING PLAN REVIEW
 PERMIT: 06060723
 ADD: WEST PALM BEACH MARRIOT
 1001 OKEECHOBEE BLVD
 CONT: HIGGINS ELEC
 TEL: (561)714-4403
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) COMMENT# 2 FROM THE PREVIOUS REVIEW,
 E3.1 & P4.1 BOTH INDICATE A REVISION# 2 OF NEW LOUVERS
 AND A STEEL DOOR.
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) LOUVERS
 B) EXTERIOR DOORS
  
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 CONTRACTOR RESPONSE:
 INDICATES THAT THE LOUVERS ARE EXISTING.
 A PRODUCT APPROVAL FOR THE DOOR ( INGERSOLL-RAND) WAS
 SUBMITTED FOR REVIEW.
 CONTRACTOR FAILED TO HAVE THE DESIGN PROFESSIONAL
 REVIEW AS REQUIRED IN THE CITY ADMINISTRATIVE CODE
 106.3.3.
  
 3) COMMENT# 3 FROM THE PREVIOUS REVIEW,
 WILL A GENERAL CONTRACTOR BE SUBMITTING FOR THE WORK
 MENTIONED IN COMMENT # 2?
 CONTRACTORS RESPONSE;
 THE CONTRACTOR HIGGINS ELECTRIC RESPONSE INDICATES THAT
 THERE IS "ABSOLUTELY NO WIND LOAD" ON THE LOUVERED
 SYSTEM AND NEW DOOR LOCATED BELOW GRADE IN AN EXISTING
 PIT. WIND FROM THE POSITIVE DIRECTION WILL RACE ALONG
 THE GROUND AND EITHER BUILD PRESSURE OR CREATE A
 VENTURIE AFFECT CAUSING NEGATIVE
 PRESSURE WITHIN THE PIT. PLEASE PROVIDE THE POSITVE AND
 NEGATIVE PRESSURES FOR THIS AREA. IT IS NOT CLEAR AS TO
 IF THIS PORTION OF BUILDING IS CONNECTED TO THE
 HIGH-RISEREQUIRING THE DESIGN TO BE ASCE 7-02,
 SECTION 6.5.12.4.2 BUILDINGS . 60'. THE OTHER FACTORS
 OF THE WIND RAISING AROUND THE HIGHRISE
 (NEGATIVE PRESSURES) WILL CREATE GREATER PRESSURES.
 ASCE 7-02 SECTION 6.5.6.2 COMPONENTS AND CLADDING FOR
 BUILDINGS WITH A MEAN ROOF HEIGHT IN EXCESS OF 60' AND
 FOR OTHER STRUCTURES SHALL BE DESIGNED USING THE
 EXPOSURE RESULTING IN THE HIGHEST WIND LOADS FOR ANY
 WIND DIRECTION AT THE SITE. PLEASE PROVIDE PRESSURES.
  
 THE SECOND ISSUE WITH THE CONTRACTORS RESPONSE IS A 10"
 CUSTOM CHANNEL FRAME, PLEASE PROVIDE ADDITIONAL
 INFORMATION, WHAT IS THIS FRAME TO BE USED FOR/
 106.1.2*. WHY IS A WELDER INSTALLING THE FRAME? IS THE
 FRAME BEING WELDED TO EMBEDS OR OTHER STEEL FRAMING? ON
 THE EXTERIOR OF THE BUILDING A C.G.C WILL BE REQUIRED
 TO WORK ON THE EXTERIOR FRAME AND COMPONENTS AND
 CLADDING. A WELDER MAY BE CERTIFIED TO FIELD WELDING
 BUT NOT THE INSTALATION OF THE
 EXTERIOR COMPONENTS AND CLADDING.
  
 THE OTHER ISSUE WITH THE EXTERIOR OF THE BUILDING
 ENVELOPE IS THE INSTALATION OF THE DOOR, THIS PERMIT
 APPLICATION DOES NOT HAVE ANY SUB-CONTRACTORS SIGNED ON
 QUALIFIED TO DO WORK IN THIS AREA.
  
 AS TO THE LOUVERS BEING INSTALLED BY THE MAINTENCE
 DEPARTMENT, THIS IS AN ALTERATION TO THE EXTERIOR OF
 THE BUILDING, NOT A MAINTENCE ISSUE. TO BE CONSIDERED
 NEW WORK BEING ACCOMPLISHED, THE MAINTENCE PERSONNEL
 ARE NOT LICENSED TO DO THIS TYPE OF WORK!!!!!
 FL S S 489.489.105(3) CONTRACTOR.
  
 4) NEW COMMENT, IT APPEARS THAT THE CONTRACTOR HIGGINS
 ELECTRIC IS ADVERTISING HIMSELF TO BE A ENGINEER BY
 HAVING ENGINEERING, DESIGN AND INSTALLATION.
 ONE SET OF LETTERHEAD WILL BE RETAINED. PLEASE PROVIDE
 ENGINEERS SEAL, SEAL AND SIGN ALL DOCUMENTS . PLANS,
 SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND
 BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
 61G15-23.002 SEAL, SIGNATURE AND DATE SHALL BE
 AFFIXED.
 (1) A PROFESSIONAL ENGINEER SHALL SIGN HIS NAME AND
 AFFIX HIS SEAL TO ALL PLANS, SPECIFICATIONS, REPORTS,
 FINAL BID DOCUMENTS PROVIDED TO THE OWNER OR THE
 OWNER?S REPRESENTATIVE, OR OTHER DOCUMENTS PREPARED OR
 ISSUED BY SAID REGISTRANT AND BEING FILED FOR PUBLIC
 RECORD. THE DATE THAT THE SIGNATURE AND SEAL IS AFFIXED
 AS PROVIDED HEREIN SHALL BE ENTERED ON SAID PLANS,
 SPECIFICATIONS, REPORTS, OR OTHER DOCUMENTS IMMEDIATELY
 UNDER THE SIGNATURE OF THE PROFESSIONAL ENGINEER.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-11-13 Cont ID  
Sent By jwitmer Date 2006-11-13 Time 14:23 Rev Time 1.22
Received By jwitmer Date 2006-11-13 Time 14:23 Sent To  
Notes
2006-11-13 14:25:55BUILDING PLAN REVIEW
 PERMIT: 06060723
 ADD: WEST PALM BEACH MARRIOT
 1001 OKEECHOBEE BLVD
 CONT: HIGGINS ELEC
 TEL: (561)714-4403
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) NEW COMMENT, E3.1 & P4.1 BOTH INDICATE A REVISION# 2
 OF NEW LOUVERS AND A STEEL DOOR.
 FL BLD CODE 1609.1.4: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) LOUVERS
 B) EXTERIOR DOORS
  
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 3) WILL A GENERAL CONTRACTOR BE SUBMITTING FOR THE
 WORK
 MENTIONED IN COMMEENT # 2?
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-08-10 Cont ID  
Sent By jwitmer Date 2006-08-10 Time 07:07 Rev Time 2.22
Received By jwitmer Date 2006-08-10 Time 07:07 Sent To  
Notes
2006-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06060723
 ADD: WEST PALM BEACH MARRIOT
 1001 OKEECHOBEE BLVD
 CONT: HIGGINS ELEC
 TEL: (561)714-4403
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) ADDRESSING ISSUES. THE PERMIT
 APPLICATION INDICATES 630 CLEARWATER RD.
 IF THIS GENERATOR IS TO BE INSTALLED IN
 THE MARRIOT AS PLANS INDICATE THEY
 REQUESTED A NEW ADDRESS YEARS AGO AND
 ARE CURRENTLY USING 1001 OKECCHOBEE
 BLVD. PLEASE CORRECT THE PERMIT
 APPLICATION AND ADDRESS IN THE PLAN
 TITLEBLOCK.
  
 3) PROVIDE A RERECORDED NOTICE OF
 COMMENCEMENT WITH THE CORRECT ADDRESS.
 FL S S 713.13NOTICE OF COMMENCEMENT,
 TO BE FILED WITH THE CLERK OF THE COURT
 BEFORE A PERMIT WILL BE ISSUED. NOTE:
 713.13(2) IF THE WORK DESCRIBED IN THE
 NOTICE OF COMMENCEMENT IS NOT ACTUALLY
 COMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID.
  
 4) GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
 F) FLOOD ZONE(B)
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-03-30 Cont ID  
Sent By dpalmer Date 2007-03-30 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2007-03-30 Time 08:46 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-02-11 Cont ID  
Sent By dpalmer Date 2007-02-11 Time 18:37 Rev Time 0.00
Received By dpalmer Date 2007-02-11 Time 17:51 Sent To  
Notes
2007-02-11 18:38:38** UNSAT **
  
 1) NOTE: PLEASE SEE PREVIOUS ZONING REVIEW COMMENTS AS
 SCREENING DOES SEEM TO HAVE BEEN SUBMITTED.
  
 2) NOTE: PLEASE SEE GENERATOR LOAD SUMMARY ON E5.1
 WHICH SHOWS HQ ON LOAD SUMMARY. IS THIS ANOTHER UNIT OR
 IS THIS EQ? THIS SEEMS TO HAVE BEEN A MISPRINT AND MAY
 HAVE BEEN REDLINED, HOWEVER AS THE PLANS AND RISER HAVE
 BEEN COMPLETELY REVISED ON SO MANY OCCASIONS, THIS IS
 NOT BEING ASSUMED.
  
 3) NOTE: PLEASE SEE THE LOAD ON EMDP IS NOT THE SAME
 LOAD AS SHOWN ON MDP2 FOR THE SAME ?
 PLEASE CORRECT AND CORRELATE.
 220, 215.5, 240.4, 310.16 ETC
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE A 4X FEED WAS ASSESSED FOR THE
 INSTALLATION OF GENERATOR/ GAS /ELECTRICAL ETC.
 A FEE OF $6300 IS NOW DUE.
  
 5) NOTE: PLEASE SEE THE NOTICE OF COMMENCEMENT
 SUBMITTED WILL BE REQUIRED TO BE RE-RECORDED AND
 SUBMITTED BEFORE PICKING UP PERMIT AS IT HAS BECOME
 VOID PER FS 713.13(2). THIS IS INFORMATION GIVEN AT
 THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2007-01-13 Cont ID  
Sent By dpalmer Date 2007-01-13 Time 17:28 Rev Time 0.00
Received By dpalmer Date 2007-01-13 Time 15:38 Sent To  
Notes
2007-01-13 17:29:32** UNSAT 3RD REVIEW**
  
  
 ** PLEASE SEE COMMENTS BELOW ARE BASED ON THE REVISED
 PLANS SUBMITTED.
 ** PLEASE SEE AS REQUESTED ON THE PREVIOUS REVIEW, NO
 PREVIOUS REVIEWED ORIGINAL PLANS WERE SUBMITTED FOR
 REFERENCE. PLEASE SUBMIT ONE SET OF EACH OF THE
 PREVIOUS PLANS.
  
 1) NOTE:PLEASE SUBMIT TWO SETS OF PLANS WITH ALL
 SHEETS PLACED INTO SETS AND SHEETS ATTACHED.
 PLEASE SEE MORE THAN TWO SETS OF MANUFACTURES SPEC/CUT
 SHEETS WERE SUBMITTED AND EACH OF THESE CONTAIN
 DIFFERENT SHEETS. PLEASE SUBMIT ONLY THE TWO SETS NEED
 FOR REVIEW OF SAID SHEETS.
 106.1.2, 106.1.
  
 ***PLEASE SEE COORDINATION BETWEEN THE RISER, LOADS AND
 PANELS NEED TO BE ADDRESSED.
 THE COMMENTS BELOW ARE BEING NOTED, HOWEVER DUE TO THE
 NEW REVISED RISER AND THE AMOUNT OF NEEDED CHANGES
 THERE MAY BE NEW COMMENTS ON THE NEXT REVIEW.
  
 2) NOTE:
 A) PLEASE SEE MDP2-8 SHOWS A 400A BREAKER FEEDING WHAT
 IS LABELED ATS-EQ.
 PLEASE SEE THE LOAD ON THIS IS BEING SHOWN AS
 34.7/35.1/34.5 WHICH IS THE LOAD SHOWN ON PANEL HEQ.
 B) PLEASE SEE HOWEVER RISER IS NOW SHOWING THE MDP3
 BEING FED FROM THE ATS-EQ NOW WITH OUT ANY LOAD
 CONSIDERATION BEING SHOWN. PLEASE SEE THE LOAD ALONE
 BEING SHOWN ON MDP3 IS 416.7 KVA WHICH IS NOT ON MDP2
 OR IN THE GENERATOR LOAD SUMMARY.
 PLEASE CORRELATE THE GENERATOR LOAD SUMMARY WITH ALL
 LOADS.
 C) PLEASE SEE THE RISER NOW SHOWS A 175AMP DISCONNECT
 BEING INSTALLED FROM THE ATS EQ TO THE MDP3? HOW IS IT
 POSSIBLE FOR THIS TO BE 175AMPS WHEN THE LOAD UNDER
 NORMAL EXCEEDS THAT OF THIS EQUIPMENT? PLEASE SEE THE
 NOTE ABOVE AS ONCE AGAIN, NO LOADS FOR THE MDP3 IS
 BEING SHOWN AS PART OF THE LOAD ON THE GENERATOR, YET
 IT IS BEING SHOWN CONNECTED TO THIS SYSTEM.
 D) PLEASE CLEAR UP RISER AND WHETHER OR NOT THE MDP3 IS
 FED FROM THE SAME BREAKER THAT IS BEING SHOWN FOR
 ATS-EQ AND HEQ. IF THE HEQ IS FED FROM THE 400A BREAKER
 ON MDP2 THIS IS FINE HOWEVER THE ADDITION OF THE NEW
 MDP3 HAS CREATED AN ENTIRE NEW LIST OF COMMENTS.
 E) PLEASE SEE BASED ON THE ADDITION OF MDP3 ON THE
 RISER, THE FEEDERS BEING SHOWN AS ATS-2 AND ATS-3 ARE
 NOT SUFFICIENT UNDER NORMAL OR LOADS UNDER EMERGENCY.
 HOW CAN THE NORMAL SIDE OR THE EMERGENCY SIDE INDICATE
 CONDUCTORS LESS THAN THE LOAD AS SHOWN?
  
 240.4, 310.16, 230.70, 220, 240.21, 215.5, 215.3,
 230.42, 230.79, 225.39 ETC.
 PLEASE KNOW THERE ARE NUMEROUS SECTIONS WHICH COULD BE
 NOTED.2002 NEC
 PLEASE REVISE RISER AND COORDINATE ALL.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-11-20 Cont ID  
Sent By dpalmer Date 2006-11-20 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2006-11-20 Time 07:30 Sent To  
Notes
2006-11-20 09:02:28*** UNSAT 2ND REVIEW ***
  
  
 *** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH IS
 STILL IN NEED OF ADDRESSING. PLEASE ALSO WEE NOTES
 WHICH ARE NEW BASED ON REVISED ITEMS NOW SHOWN ON
 PLANS.
  
 ** PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW AND MARKED WITH AN OK! , NO! (WITH
 FURTHER EXPLANATION) OR SOME MAY BE LABELED WITH OK/NO
 AS PART OF THE COMMENT MAY HAVE BEEN ADDRESSED ONLY.
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE:NO, PLEASE SEE THE COMMENT AS PREVIOUSLY
 NOTED WAS TO OBTAIN CORRECT LOCATION TO BE COORDINATED
 WITH THE FIRE MARSHAL'S OFFICE AND SHALL BE SHOWN AND
 NOTED ON THE PLANS THIS WAY. THE PLANS RESPONSE AND
 "KEY NOTE" READS TO BE LOCATED WITH THE OWNER. THIS IS
 THE DECISION OF THE FIRE MARSHAL'S OFFICE AND THE CODE
 ONLY. PLEASE ALSO SEE CODE SECTION AS PREVIOUSLY GIVEN.
 FOR LOCATION REQUIREMENTS
  
 ** PREVIOUS REVIEW NOTE REVIEW # 1 **
 PLEASE SEE GEN ANNUCIATOR PANEL SHALL BE LOCATED IN THE
 FIRE COMMAND ROOM, OR LOCATION OF FACP, NEAREST POINT
 DESIGNATED BY THE FIRE MARSHAL'S OFFICE.
 NFPA-101 CHAPTER 11.8.5.
  
 6) NOTE: OK. RESPONSE LETTER MENTIONS THERE IS A DIESEL
 DRIVEN FIRE PUMP.
  
  
 7) NOTE: OK/ NO,
 PLEASE SEE SPECIFICATIONS FROM THE MANUFACTURE STILL
 INDICATE AS 706 GALLONS. RESPONSE LETTER MENTIONS THAT
 THE TANK WILL BE BAFFLED, YET THE SPECIFICATIONS FROM
 THE MANUFACTURE NEED TO INDICATE THIS AT THIS TIME.
 PLEASE SEE REVIEW COMMENTS FROM OTHER TRADES.
  
  
  
  
 8) NOTE: OK, HOWEVER SEE NEW NOTES.
  
  
 9) NOTE:NO, PLEASE SEE PREVIOUS NOTE, AS SHOWN ON
 PLANS, 4-POLE TRANSFER SWITCHES WILL BE REQUIRED. THIS
 IS BASED ON THE RISER AS SHOWN. THE GENERATOR IS BEING
 SHOWN AS SEPARETLY DERIVED, EVEN THOUGH NOTE MENTIONS
 IT WILL NOT BE.
 PLEASE SEE RISER.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE SEE NOTES MENTIONS THAT THE GEN WILL "NOT" BE A
 "SEPARATELY
 DERIVED SYSTEM" YET, GENERATOR SEEMS TO
 BE SHOWN WITH A BOND FROM THE GEN FRAME AND GROUND BAR
 TO THE GEN WINDINGS?
 PLEASE KNOW, IF THIS OCCURS, THEN THIS "IS" A SDS AND
 SHALL THEN CONTAIN A
 4-POLE ATS'S, GE SYSTEM AND NOTED AS SO.
 PLEASE VERIFY AND ADJUST PLANS AS NEEDED.
  
 10) NOTE: NO, PLEASE SEE THIS WAS SUBMITTED; HOWEVER
 PLEASE SEE THE SHEETS IN FACT CONTAIN RAISED SEALS OVER
 A "PHOTO-COPIED" SIGNATURE FROM THE ENGINEER OF RECORD.
 ( MR. ALBERT KWAN) PLEASE SEE FLORIDA STATUTES 471.025,
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002. PLEASE
 KNOW THIS IS REVIEW WHETHER OR NOT COMMENT IS MADE BY
 BUILDING REVIEW.
 PLEASE ALSO SEE SHEET MENTIONS TO BE 6INCHES ABOVE
 FLOOR ELEVATION HOWEVER, EQUIPMENT SHALL BE 6 INCHES
 ABOVE THE BFE BASED ON THE 100 YR YEAR STORM SURGES
 LEVELS OR SURGE LEVELS BASED ON A CAT 4 STORM. PLEASE
 SEE SLOSH CHARTS ETC.
 PLEASE SEE SECTIONS GIVEN IN PREVIOUS REVIEW NOTE.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE BUILDING REVIEW COMMENTS WITH RESPECT TO THE
 GEN SLAB DETAIL. PLEASE SEE NO DETAIL, CONNECTIONS,
 ELEVATIONS WERE SUBMITTED.
 PLEASE ALSO SEE NOTE MENTIONS THE GEN @ OR ABOVE BFE.
 PLEASE KNOW, THE GEN/ ASSOCIATED EQUIPMENT SHALL BE 6"
 ABOVE THE BFE.
 PLEASE SEE NFPA-110 CHAPTER 7, 7.2, 7.3,
 7.4, 7.9 ETC.
 ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT, EPSS
 REQUIREMENTS ETC,THE SLAB WILL BE REQUIRED TO BE
 SIGNED, DATED AND SEALED BY AN ENGINEER.
 FS 471.003
  
 11) NOTE:NO, SAME NOTE.
  
 ** PREVIOUS REVIEW NOTE FROM REVIEW #1 **
 PLEASE BE SURE THE ENGINEER OF RECORD SIGNS PLANS WITH
 HIS LEGAL/EASILY RECOGNIZABLE SIGNATURE KNOWN TO THIS
 OFFICE AND ON RECORD IN THIS OFFICE.
 FS 471.025, FAC 61G15-23.002
  
  
 **** NEW NOTES FROM THE 2ND REVIEW ***
  
 12) NOTE: PLEASE SUBMIT THE MANUFACTURE
 SPECIFICATION/CUT SHEETS ON THE WP HOUSING FOR THE
 GENERATOR.
 FBC 106.1.2,
 110.3,90.7
  
 13) NOTE: PLEASE BE SURE EITHER PLANS OR MANUFACTURE
 SPECIFICATIONS INDICATE THE FUEL CONSUMPTION BASED ON
 DIESEL ONLY.
 SPECS APPEAR TO SHOW AS BI-FUEL ONLY.
  
 14) NOTE: PLEASE SEE RESPONSE LETTER MENTIONS SHEETS
 EQ.1, IS THIS NOT E0.1? THIS ONLY APPEARS TO BE A
 MISPRINT.
 PLEASE EXPLAIN RATIONAL ON THE SIZING OF THE BREAKERS
 FROM THE GENERATOR. PLEASE SEE THE EMDP HAS A LOAD OF
 238A'S +/- WITH A 300A BREAKER FEEDING THIS 600A PANEL
 BOARD. WHEREAS THE PANEL "HEQ" WHICH IS ONLY RATED
 400A'S AND HAS ONLYA LOAD OF 105A'S +/- , YET HAS A
 350A BREAKER AT THE GENERATOR FOR OVER CURRENT
 PROTECTION.
 THIS IS UNCLEAR WHY THE EQUIPMENT WITH LOAD WHICH IS
 SUBSTANTIALLY MORE CONTAINS A LOWER OVER CURRENT
 PROTECTION.
 PLEASE EXPLAIN AND CORRELATE.
 FBC 106.1.2 ADMIN SECT.
  
 15) NOTE: PLEASE SEE FEEDER SCHEDULE ON RISER AND THAT
 ON MDP2, PLEASE CORRELATE. PLEASE ALSO SEE FEEDER
 SCHEDULE.
  
 16) NOTE: PLEASE SEE RISER SHOWS A TRANSFORMER T-8
 BEING FED FROM HEQ, YET HEQ WITH THE CIRCUITS AS SHOWN
 ON RISER INDICATE THESE AS ?SPARE? ON SCHEDULE???
 PLEASE CORRELATE CIRCUITING AS SHOWN FROM RISER TO
 PANEL SCHEDULE.
 FBC 106.1.2 ADMIN SECTION.
  
 17) NOTE: PLEASE HIGH-LIGHT THE SPECIFIC TRANSFER
 SWITCH BEING USED ON THE MANUFACTURE SPECS/CUT SHEETS
 SUBMITTED. THERE IS A "SUGGESTED SPECIFICATION" BOOKLET
 SUBMITTED, HOWEVER PLEASE INDICATE ON SPECS.
 110.3,90.7.
 FBC 106.1.2
  
  
  
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-30 Cont ID  
Sent By dpalmer Date 2006-06-30 Time 07:55 Rev Time 0.00
Received By dpalmer Date 2006-06-30 Time 06:46 Sent To  
Notes
2006-06-30 00:00:00********* UNSAT *********
  
 1) NOTE: PLEASE SEE ADDRESSING REVIEW
 AND COMMENTS AS THE CORRECT ADDRESS FOR
 THE MARRIOT IS 1001 OKEECHOBEE BLVD.
 THIS ADDRESS WAS CHANGED A COUPLE OF
 YEARS AGO.
 PLEASE ADJUST ALL PLANS/TITLE BLOCKS ARE
 REQUIRED FAC 61G15-23.002/61G1-16.004
  
 2) NOTE: PLEASE CLARIFY THE KW RATING OF
 THE GEN AS ONE SHEET IN THE
 SUBMITTAL/SPEC PACKAGE CONTAINS 400KW?
  
 3) NOTE: PLEASE BE SURE TO PROVIDE ALL MANUFACTURES
 CUT/SPEC SHEETS FOR GEN AND
 ATS. APPEARS TO BE MISSING COVER SHEETS
 ETC.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE: PLEASE SEE THAT PLANS REFLECT
 ALL CURRENT CODES IN AFFECT.
 NFPA-70 2002, NFPA-101 2003, NFPA-110
 2002.
  
 5) NOTE: PLEASE SEE GEN ANNUCIATOR PANEL
 SHALL BE LOCATED IN THE FIRE COMMAND
 ROOM, OR LOCATION OF FACP, NEAREST POINT DESIGNATED BY
 THE FIRE MARSHAL'S OFFICE.
 NFPA-101 CHAPTER 11.8.5.
  
 6) NOTE: PLEASE CLARIFY IF THE FIRE PUMP
 IS FED FROM THIS GEN. ??
 IF SO, PLEASE KNOW, THERE MUST BE A MIN
 OF 8HRS "ON-SITE" FUEL FOR 100% OF THE
 FULL LOAD RATING OF THE FIRE PUMP AND
 OTHER ASSOCIATED EM EQUIPMENT.2003
 NFPA-20 9.6.2.2
 PLEASE ALSO PROVIDE GPH WITHOUT THE TIE
 IN OF THE NAT GAS LINE AND WITH THE TIE
 IN OF THE NAT GAS LIN.
  
  
 7) NOTE: PLEASE SEE FIRE REVIEW AND
 MECHANICAL REVIEW COMMENTS WITH RESPECT
 TO FUEL PIPING/ TANK SIZE AND STORAGE.
 7.9.12LISTED GENERATOR SUB-BASE
 SECONDARY CONTAINMENT FUEL TANKS OF 2498
 L (660 GAL) CAPACITY AND BELOW SHALL BE
 PERMITTED TO BE INSTALLED OUTDOORS OR
 INDOORS WITHOUT DIKING OR REMOTE
 IMPOUNDING.
 7.9.12.1A MINIMUM CLEARANCE OF 0.9 M
 (36 IN.) SHALL BE MAINTAINED ON ALL
 SIDES.
 7.9.3.1GALVANIZED FUEL LINES SHALL NOT
 BE USED.
 **
 PLEASE SEE TANK SIZE IS BEING INDICATED
 AS 706 GALS.
  
  
 8) NOTE: PLEASE SEE ATS-LS IS BEING FROM
 A 400A OCP AND EQUIPMENT IS RATED FOR
 300A'S AND FEED FROM GEN IS 250A'S??
 PLEASE CORRELATE.
 215.5
  
 9) NOTE: PLEASE SEE NOTES MENTIONS THAT
 THE GEN WILL "NOT" BE A "SEPARATELY
 DERIVED SYSTEM" YET, GENERATOTR SEEMS TO
 BE SHOWN WITH A BOND FRON THE GEN FRAME
 AND GRND BAR TO THE GEN WINDINGS?
 PLEASE KNOW, IF THIS OCCURS, THEN THIS
 "IS" A SDS AND SHALL THEN CONTAIN A
 4-POLE ATS'S, GE SYSTEM ANDNOTED AS
 SO.
 PLEASE VERIFY AND ADJUST PLANS AS
 NEEDED.
  
 10) NOTE: PLEASE BUILDING REVIEW
 COMMENTS WITH RESPECT TO THE GEN SLAB
 DETAIL. PLEASE SEE NO DETAIL,
 CONNECTIONS, ELEVATIONS WERE SUBMITTED.
 PLEASE ALSO SEE NOTE MENTIONS THE GEN @
 OR ABOVE BFE. PLEASE KNOW, THE GEN/
 ASSOCIATED EQUIPMENT SHALL BE 6" ABOVE
 THE BFE.
 PLEASE SEE NFPA-110 CHAPTER 7, 7.2,7.3,
 7.4,7.9 ETC.
 ** PLEASE KNOW, DUE TO THE SIZE, WEIGHT,
 EPSS REQUIREMNTS ETC,THE SLAB WILL BE
 REQUIRED TO BE SIGNED, DATED AND SEALED
 BY AN ENGINEER.
 FS 471.003
  
 11) NOTE: PLEASE BE SURE THE ENGINEER OF
 RECORD SIGNS PLANS WITH HIS LEGAL/EASILY RECOGNIZABLE
 SIGNATURE KNOWN TO THIS
 OFFICE AND ON RECORD IN THIS OFFICE.
 FS 471.025, FAC 61G15-23.002
  
 ** PLEASE BE SURE TO SEE ANY OTHER
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2007-03-07 Cont ID  
Sent By mawillia Date 2007-03-07 Time 16:53 Rev Time 0.00
Received By mawillia Date 2007-03-07 Time 16:53 Sent To  
Notes
2007-03-07 16:53:34*****APPROVED*****
  
  
  
  
 TO BE STAMPED WHEN OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2007-01-18 Cont ID  
Sent By dpalmer Date 2007-01-18 Time 15:50 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2007-01-18 15:50:43NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY
 CONTRACTOR WITHOUT THIS REVIEW BEING DONE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2006-12-21 Cont ID  
Sent By mawillia Date 2006-12-21 Time 12:36 Rev Time 0.00
Received By mawillia Date 2006-12-21 Time 12:36 Sent To  
Notes
2006-12-21 12:37:41*****APPROVED*****
  
  
  
  
 TO BE STAMPED WHEN OTHER PLAN REVIEWS HAVE BEEN
 SATISFIED

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-08-18 Cont ID  
Sent By mwennerg Date 2006-08-18 Time 10:37 Rev Time 0.00
Received By mwennerg Date 2006-08-18 Time 10:37 Sent To  
Notes
2006-08-18 00:00:00***DENIED***
  
 1) PLEASE SEE OTHER REVIEW COMMENTS
 REGARDING ADDRESSING AND MAKE
 CORRECTION. THE ADDRESS SHOULD REFLECT
 1001 OKEECHOBEE BLVD.
  
 2) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED.
  
 3) PLEASE CLEARLY IDENTIFY LOCATION OF
 GENERATOR AND FUEL TANK WITH RELATION TO
 BUILDING OPENINGS AND ILLUSTRATE
 DISTANCES. PLEASE SUBMIT SITE PLAN FOR
 REVIEW.
  
 4) WORK TO COMPLY WITH NFPA 110, 2002
 EDITION.
  
 5) DEPENDANT UPON LOCATION OF EQUIPMENT,
 SAFEGUARDS AGAINST MECHANICAL DAMAGE MAY
 BE REQUIRED AND SHALL BE ILLUSTRATED.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2007-03-12 Cont ID  
Sent By rregueir Date 2007-03-12 Time 09:08 Rev Time 0.00
Received By rregueir Date 2007-03-12 Time 09:08 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By pkrauss Date 2006-12-01 Time 08:58 Rev Time 0.00
Received By pkrauss Date 2006-12-01 Time 08:58 Sent To  
Notes
2006-12-01 08:58:50DENIED:
  
 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION
 INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE
 SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823,
 INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE
 CORRELATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 08:12 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 08:12 Sent To  
Notes
2006-08-21 00:00:00DENIED:
  
 PLEASE PROVIDE INFORMATION ON THE
 SHUTOFF VALVES ON THE SUB-BASE FUEL
 TANK.SHOW COMPLIANCE WITH 2004 FMC
 CHAPTER 13.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].
  

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2007-05-07 Cont ID  
Sent By kstevens Date 2007-05-07 Time 10:04 Rev Time 0.00
Received By kstevens Date 2007-05-07 Time 10:04 Sent To  
Notes
2007-05-07 10:04:57REVISION OK - CHANGED PIPING TO GALV.

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2007-02-28 Cont ID  
Sent By kstevens Date 2007-02-28 Time 13:46 Rev Time 0.00
Received By kstevens Date 2007-02-28 Time 13:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2007-01-18 Cont ID  
Sent By dpalmer Date 2007-01-18 Time 15:50 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2007-01-18 15:51:16NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY
 CONTRACTOR WITHOUT THIS REVIEW BEING DONE.
 PLANS DID CONTAIN NEW GAS SHEETS FOR REVIEW.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-12-09 Cont ID  
Sent By pschmitz Date 2006-12-09 Time 10:13 Rev Time 0.00
Received By pschmitz Date 2006-12-09 Time 10:12 Sent To  
Notes
2006-12-09 10:13:23RE SUB
 SEPERATE GAS PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-07-29 Cont ID  
Sent By pschmitz Date 2006-07-29 Time 07:14 Rev Time 0.00
Received By pschmitz Date 2006-07-29 Time 07:14 Sent To  
Notes
2006-07-29 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
 (A) SHTP4.1 THE FOLLOWING INFORMATION IS
 REQUIRED FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304
 .
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 8. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 (B) SEE OTHER PLAN REVIEW COMMENTS, THAT
 MAY EFFECT GAS PLAN REVIEW.
  
 (C) WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE
 ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 END OF COMMENTS, QUESTIONS 561-805-6692

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2007-03-30 Cont ID  
Sent By spalmer Date 2007-03-30 Time 17:44 Rev Time 0.00
Received By spalmer Date 2007-03-30 Time 17:44 Sent To  
Notes
2007-03-30 17:45:10TO COMM BOARD # 19

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2007-03-28 Cont ID  
Sent By spalmer Date 2007-03-28 Time 17:21 Rev Time 0.00
Received By spalmer Date 2007-03-28 Time 17:21 Sent To  
Notes
2007-03-28 17:22:00WAITING FOR COMM BOARD

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2007-02-02 Cont ID  
Sent By adarroug Date 2007-02-02 Time 11:21 Rev Time 0.00
Received By adarroug Date 2007-02-02 Time 11:21 Sent To  
Notes
2007-02-08 11:23:26TO "COMM" BD#38
2007-02-02 11:21:44WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-12-22 Cont ID  
Sent By adarroug Date 2006-12-22 Time 13:14 Rev Time 0.00
Received By adarroug Date 2006-12-22 Time 13:14 Sent To  
Notes
2007-01-11 16:54:46TO "COMM" BD#7
2006-12-22 13:15:05WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-11-04 Cont ID  
Sent By adarroug Date 2006-11-04 Time 18:13 Rev Time 0.00
Received By adarroug Date 2006-11-04 Time 18:13 Sent To  
Notes
2006-11-07 14:24:04TO "COMM" BD#31
2006-11-04 18:13:59WAITING FOR"COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-23 Cont ID  
Sent By alange Date 2006-08-23 Time 14:31 Rev Time 0.00
Received By alange Date 2006-06-14 Time 15:43 Sent To  
Notes
2006-06-24 00:00:00TO COMM BOARD # 33, NEEDS Z,B,M,E,P,F
2006-06-14 00:00:00WAITING FOR "COMM" BD

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2007-03-12 Cont ID  
Sent By rregueir Date 2007-03-08 Time 09:53 Rev Time 0.00
Received By rregueir Date 2007-03-12 Time 09:07 Sent To  
Notes
2007-03-08 09:53:40ALL MECHANICAL REVIEW COMMENTS HAVE BEEN SATISFIED.
  
  
 RONALD J REGUEIRO
 561-805-6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2007-01-18 Cont ID  
Sent By dpalmer Date 2007-01-18 Time 15:51 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2007-01-18 15:51:39NO REVIEW DONE, PLANS WERE PULLED FROM REVIEW BY
 CONTRACTOR WITHOUT THIS REVIEW BEING DONE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-12-01 Cont ID  
Sent By pkrauss Date 2006-12-01 Time 07:12 Rev Time 0.00
Received By pkrauss Date 2006-12-01 Time 07:12 Sent To  
Notes
2006-12-01 07:27:29DENIED:
 COMMENTS FROM REVIEW DATED 10-28-06:
  
 COMMENT 1:REQUEST FOR CLEARANCES TO THE PROPERTY
 LINE, ADJACNT BUIDLINGS, FRESH AIR INTAKES, DOORS,
 WINDOWS, LOUVERS, ETC.RESPONSE INDICATES REVISED
 DRAWING PROVIDE THIS INFORMATION. THE ONLY DIMENSION
 PROVIDED IS ON PLAN SHEET E3.1 WHICH INDICATES 6 FEET
 FROM THE BUILDING.PER 2004 FMC 401.5.1, FRESH AIR
 INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FEET FROM
 ANY HAZARDOUS OR NOXIOUS CONTAMINANT.
  
 COMMENT 2:INDICATE IF PROTECTION FROM DAMAGE IS
 REQUIRED IN ACCORDANCE WITH 2004 FMC 401.5.RESPONSE
 INDICATES "SEE REVISED DRAWINGS".PLANS DO NOT
 INDICATE ANY PROTECTION OR ANNOTATE HOW THIS IS
 ACCOMPLISHED.
  
 COMMENT 3:OKAY.
 **************NEW COMMENT***********
  
 1.PLAN SHEET E0.1 GENERATOR SPECIFICATIONS, REVISION
 INDICATES THE SUB-BASE FUEL TANK AS 540 GAL & THE
 SUBMITTAL ON THE GENERAC POWER SYSTEM DWG OE7823,
 INDICATES THE TANK CAPACITY AS 706 GAL.PLEASE
 CORRELATE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-21 Cont ID  
Sent By pkrauss Date 2006-08-21 Time 07:28 Rev Time 0.00
Received By pkrauss Date 2006-08-21 Time 07:03 Sent To  
Notes
2006-08-21 00:00:00DENIED:
 1.PLEASE PROVIDE DISTANCES/CLEARANCES
 TO THE FOLLOWING; PROPERTY LINES,
 BUILDINGS, FRESH AIR INTAKES, WINDOWS,
 DOORS, LOUVERS, ETC.SHOW COMPLIANCE
 WITH 2004 FMC 401.5.
  
 2.INDICATE IF PROTECTION FROM DAMAGE
 IS REQUIRED IN ACCORDANCE WITH 2004 FMC
 303.4.
  
 3.PROVIDE DETAIL INFORMATION ON THE
 ANCHORING OF THE GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719 OR
 E-MAIL [email protected].

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-07-29 Cont ID  
Sent By pschmitz Date 2006-07-29 Time 07:13 Rev Time 0.00
Received By pschmitz Date 2006-07-29 Time 06:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2007-04-03 Cont ID  
Sent By astelly Date 2007-04-03 Time 15:13 Rev Time 0.00
Received By astelly Date 2007-04-03 Time 15:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 2007-02-26 Cont ID  
Sent By astelly Date 2007-02-26 Time 14:21 Rev Time 0.00
Received By astelly Date 2007-02-26 Time 14:20 Sent To  
Notes
2007-02-26 14:26:15PLEASE PROVIDE EXACT LOCATION OF SCREEN ON SITE PLAN.
 THEARCHITECTURAL DETAILINGOF THE SCREEN MUST BE
 PROVIDED FOR REVIEW.

Review Stop Z ZONING
Rev No 3 Status F Date 2007-01-17 Cont ID  
Sent By astelly Date 2007-01-17 Time 14:52 Rev Time 0.00
Received By astelly Date 2007-01-17 Time 14:52 Sent To  
Notes
2007-01-17 15:11:04PLEASE PROVIDE DRAWINGS FOR THE PROPOSED SCREEN. THE
 DIMENSIONED DRAWINGS MUST INCLUDE INFORMATION REGARDING
 MATERIALS. AS PER THE DOWNTOWN CODE, THE PROPOSED
 SCREEN MUST BE ARCHITECTURALLY COMPATIBLE WITH THE
 BUILDING ANDDESIGNED AS AS INTEGRAL PART OF THE
 OVERALL STRUCTURE.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-11-21 Cont ID  
Sent By astelly Date 2006-11-21 Time 11:48 Rev Time 0.00
Received By astelly Date 2006-11-21 Time 11:47 Sent To  
Notes
2006-11-21 12:00:18THE DMP REQUIRES MECHANICAL EQUIPMENT TO BE SCREENED.
 MORE SPECIFICALLY, THE CODE REQUIRES DEVICES WHICH
 CONTAIN FUEL TANKS, SUCH AS GENERATORS, TO BE SCREENED.
 PLEASE REVIEW SEC. 94-444(B) OF THE CODE FOR THE
 GUIDELINES.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-07-18 Cont ID  
Sent By astelly Date 2006-07-18 Time 14:44 Rev Time 0.00
Received By astelly Date 2006-07-18 Time 14:44 Sent To  
Notes
2006-07-18 00:00:00PLEASE SUBMIT A SITE PLAN SHOWING THE
 LOCATION OF THE GENERATOR FOR REVIEW.