Plan Review Details - Permit 06060696
Plan Review Stops For Permit 06060696
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-16 Cont ID  
Sent By lursu Date 2006-06-16 Time 09:36 Rev Time 0.00
Received By lursu Date 2006-06-13 Time 11:00 Sent To  
Notes
2006-06-16 00:00:00ADDRESS VERIFIED AS: 5501 S FLAGLER DR
 ,THRU FD -MW,ENTRANCE ON FLAGLER OK
2006-06-13 00:00:00PERMIT UNDER REVIEW.FIELD VERIFICATION
 NECESSARY .THE MAIN ENTRANCE IS ON
 BUNKER RANCH RD IN CP ADDRESS IS 100
 BUNKER RANCH RD ,IN PAPA ADDR :5501 S
 FLAGLER DR .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-29 Cont ID  
Sent By alange Date 2006-06-29 Time 13:11 Rev Time 0.00
Received By alange Date 2006-06-29 Time 13:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By btrobaug Date 2006-07-10 Time 12:22 Rev Time 0.50
Received By btrobaug Date 2006-07-10 Time 09:17 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-26 Cont ID  
Sent By dpalmer Date 2006-06-26 Time 09:46 Rev Time 0.00
Received By dpalmer Date 2006-06-26 Time 09:31 Sent To M
Notes
2006-06-26 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE BE SURE SITE/SURVEY
 INDICATES THE MIN BASE FLOOD ELEVATION
 (BFE) AND PLEASE INDICATE SLAB AT A MIN
 OF 6" ABOVE BFE.
  
 *** PLEASE ALSO KNOW THAT A FLOOD
 ELEVATION CERTIFICATE WILL ALSO BE
 REQUIRED BEFORE FINAL ELECTRICAL
 INSPECTON.
  
 2) NOTE: PLEASE SEE THAT MANUFACTURES
 SPEC/CUT SHEETS INDICATE ALL MIN
 CLEARENCES AROUND EQUIPMENT.
 110.3, 215.5
 FBC ADMIN SECT 106.1.2
  
 3) NOTE: PLEASE BE SURE ALL
 PLANS/DESIGNS ALSO CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR PLANS.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2006-07-10 Cont ID  
Sent By mperson Date 2006-07-10 Time 11:43 Rev Time 0.33
Received By mperson Date 2006-07-10 Time 11:43 Sent To E
Notes
2006-07-10 00:00:00NOTE: REFERENCE GAS PERMIT #06060729

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 15:12 Rev Time 0.45
Received By mperson Date 2006-06-28 Time 15:12 Sent To B
Notes
2006-06-28 00:00:00NOTE: SEE GAS PERMIT APPLICATION
 #06060729 ATTACHED TO GEN/RES PERMIT
 APPLICATION #06060696 FOR COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-25 Cont ID  
Sent By adarroug Date 2006-06-25 Time 16:44 Rev Time 0.00
Received By adarroug Date 2006-06-25 Time 16:44 Sent To E
Notes
2006-06-25 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-10 Cont ID  
Sent By btrobaug Date 2006-07-10 Time 12:22 Rev Time 0.00
Received By btrobaug Date 2006-06-14 Time 16:40 Sent To PC
Notes
2006-06-14 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 13:58 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 13:58 Sent To P
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By mperson Date 2006-06-28 Time 14:18 Rev Time 0.00
Received By mperson Date 2006-06-28 Time 14:18 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-23 Cont ID  
Sent By mmclean Date 2006-06-23 Time 11:15 Rev Time 0.00
Received By mmclean Date 2006-06-23 Time 11:15 Sent To I
Notes
2006-06-23 00:00:00PROVISO:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 6 FROM PROPERTY LINE AND 7FT
 FROM REAR PROPERTY LINE.