Plan Review Details - Permit 06060603
Plan Review Stops For Permit 06060603
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 08:21 Rev Time 0.00
Received By tgordon Date 2006-07-25 Time 09:08 Sent To  
Notes
2006-07-25 00:00:00TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-09-07 Cont ID  
Sent By tgordon Date 2006-09-07 Time 12:03 Rev Time 0.45
Received By tgordon Date 2006-09-07 Time 12:03 Sent To  
Notes
2006-09-07 00:00:00REVISION TO PERMIT TO INCLUDE DUCT WORK.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 08:04 Rev Time 0.45
Received By tgordon Date 2006-08-08 Time 08:04 Sent To  
Notes
2006-08-08 00:00:00*** DENIED ***
 1) BUILDING PLANS ON FILE SHOW DOORS
 SEPARATING THE LIVING ROOM FROM THE NEW
 FAMILY ROOM, PLEASE PROVIDE RETURN AIR
 TO THE EXISTING LIVING AREA, OR REVISE
 BUILDING PLANS.
  
 2) SHOW LOCATION OF CONDENSER UNIT ON
 MECHANICAL PLANS.
  
 3) NEED JOB ADDRESS ON ALL PLANS.
  
 4) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 5) THE PERMIT APPLIED FOR WAS FOR AN
 EXACT CHANGE OUT OF AIR HANDLER AND
 CONDENSER UNIT, NOT FOR REPLACEMENT OF
 DUCT WORK AND NEW DUCT WORK TO A NEW
 ADDITION. SECOND NOTICE REGARDING
 APPLYING FOR PROPER PERMIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  