Plan Review Details - Permit 06060583
Plan Review Stops For Permit 06060583
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-09-01 Cont ID  
Sent By alange Date 2006-09-01 Time 14:21 Rev Time 0.50
Received By alange Date 2006-09-01 Time 14:21 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 10:31 Rev Time 0.33
Received By alange Date 2006-06-28 Time 10:31 Sent To  
Notes
2006-06-28 00:00:00DENIED
  
 SHOW GENERATOR SLAB DETAIL AND METHOD OF
 ATTACHMENT TO SLAB.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 20:04 Rev Time 0.00
Received By dpalmer Date 2006-09-20 Time 19:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-25 Cont ID  
Sent By dpalmer Date 2006-08-25 Time 19:02 Rev Time 0.00
Received By dpalmer Date 2006-08-25 Time 18:30 Sent To B
Notes
2006-08-25 00:00:00*** UNSAT2ND REVIEW ***
  
 ** PLEASE SEE NOTES FROM PREVIOUS
 REVIEW.
  
 1) NOTE: PLEASE SEE PLANS LAYOUT DOES
 NOT CLEARLY SHOW THE LOCATIO OF THE ATS
 AND IF THE NEW MAIN LOATED IN THE ATS IS
 LOCATED AND GROUPED WITH THE EXISTING
 ELECTRICAL PANEL WHICH CONTAINS A MAIN
 DISCONNECT.
 PLEASE SEE IF THE ATS AS SPECIFIED IS
 GOING TO BE INSTALLED AND THIS ATS IS
 OUTSIDE AND THE MCB PANEL IS INSIDE, A
 DISCONNECT FOR THE FEEDERS COMING FROM
 THE GEN WILL BE REQUIRED GROUPED WITH
 THE NEW MAIN OUTSIDE. THIS CAN BE DONE
 WITH A DISCONNECT RATED FOR THE LOAD
 SERVED, NO OCP IS REQUIRED, OR PLEASE
 SEE THAT GENERAC NOW ALSO MANUFACTURES A
 NEW ATS TO MEET THIS NEED. (RTSE) WHICH
 CONTAINS TWO CIRCUITS BREAKERS. ONE
 WHICH PROVIDES A DISCONNECT OF THE
 POWERE FROM FPL AND THE OTHER WHICH
 DISCONNECTS THE FEEDERS FROM THE
 GENERATOR. GENERAC IS MAKING THESE AS
 CODE HAS MADE A DIFFERENCE IN THEIR
 MANUFACTURING PRACTICES.
  
 PLEASE REVISE PLANS.
  
 2) NOTE: PLEASE CORRELATE PLANS
 SUBMITTED SHOWING THE SET BACK OF GEN
 AND THE SETBACK WHICH IS SHOWN ON
 SITE/SURVEY.
 PLEASE SEE ONE SHOWS 12FT AND THE OTHER
 9FT.
  
 3) NOTE: PLEASE SEE FS 713.13(2) AS THE
 NOC SUBMITTED WHICH WAS RECORDED ON
 5/23/06 HAS SINCE EXOIRED. PLEASE KNOW
 NOC'S ARE ONLY VALID FOR 90DAYS UNLESS
 WORK HAS COMMENCED. PLEASE RE-RECORD THE
 NOC BEFORE PICKIGN UP PERMIT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By dpalmer Date 2006-06-23 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2006-06-23 Time 12:41 Sent To M
Notes
2006-06-23 00:00:00***** UNSAT ***********
  
 1) NOTE: PLEASE PROVIDE LOCATION ALL ALL
 EQUIPMENT ON HOUSE LAYOUT PLANS.
 WHERE IS THE ELECTRICLA PANEL LOCATED?
 MUST MEET 225.34
  
 2) NOTE: PLEASE SEE ZONING COMMNETS AND
 ALL DIMENSIONS TO BE SHOWN.
 ** PLEASE BE SURE MANUFACTURES CUT/SPECS
 SHEETS CLEARLY INDICATE MIN CLEARENCES
 ON ALL SIDES OF EQUIPMENT.
 **PLEASE SEE MECH COMMENTS.
  
 3) NOTE: PLEASE SEE GROUNDING ELECTRODE
 CONDUCTOR IS TO BE SIZED PER 250.66
 THE SIZE OF #6 SHOWN AS EXISTING DOES
 NOT MEET NEC AND WOULD BE REQ'D TO BE
 UPGRADED.
  
 4) NOTE: PLEASE SEE BLDG COMMENTS AS NO
 SLAB DETAIL WAS SUBMITTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status N Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 19:49 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 19:49 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
2006-09-20 00:00:00NO PLANS SUBMITTED, AND CAME IN BEFORE
 THE GAS PLANS WERE REQUIRED AT THE SAME
 TIME.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-09-14 Cont ID  
Sent By adarroug Date 2006-09-14 Time 11:46 Rev Time 0.00
Received By adarroug Date 2006-09-14 Time 11:46 Sent To E
Notes
2006-09-14 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-08-24 Cont ID  
Sent By adarroug Date 2006-08-24 Time 14:24 Rev Time 0.00
Received By adarroug Date 2006-08-24 Time 14:24 Sent To B
Notes
2006-08-24 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-08-18 Cont ID  
Sent By adarroug Date 2006-08-18 Time 13:30 Rev Time 0.00
Received By adarroug Date 2006-08-18 Time 13:30 Sent To Z
Notes
2006-08-18 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:03 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:03 Sent To E
Notes
2006-06-14 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-28 Cont ID  
Sent By alange Date 2006-06-28 Time 10:32 Rev Time 0.00
Received By alange Date 2006-06-09 Time 14:29 Sent To  
Notes
2006-06-09 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2006-06-26 Cont ID  
Sent By tgordon Date 2006-06-26 Time 14:27 Rev Time 0.15
Received By tgordon Date 2006-06-26 Time 14:27 Sent To B
Notes
2006-06-26 00:00:00*** PROVISO ***
 1) PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT - PERMANENTLY INSTALLED
 EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES SHALL BE INSTALLED IN ACCORDANCE
 WITH MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.
  
 NFPA 37 INSTALLATION & USE OF STATIONARY
 COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED
 OUTDOORS SHALL BE MINIMUM OF 5 FT FROM
 OPENINGS IN WALLS & AT LEAST 5 FT FROM
 STRUCTURES HAVING COMBUSTIBLE WALLS.A
 MINIMUM CLEARANCE IS NOT REQUIRED WHEN
 (1) THE ADJACENT WALL HAS A MINIMUM FIRE
 RESISTANCE RATING OF 1 HOUR OR (2) THE
 WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS
 BEEN DEMONSTRATED THAT A FIRE WITHIN THE
 ENCLOSURE WILL NOT IGNITE COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE.
 INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS
 SHOULD NOT TERMINATE UNDER STRUCTURES OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO
 THE VENTILATION INTAKES.
  
 2004 FMC 804.3.5 #3, WHERE THE
 TERMINATION IS LOCATED BELOW AN ADJACENT
 ROOF STRUCTURE, THE TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE
 ROOF STRUCTURE.
  
 PLEASE NOTE, WHILE ZONING ALLOWS
 MECHANICAL EQUIPMENT TO ENCROACH 4 FT
 INTO THE REQUIRED SETBACK, GENERATORS
 SHALL MAINTAIN THE REQUIRED ABOVE
 MENTIONED CLEARANCES TO THE ADJACENT
 PROPERTY STRUCTURES, I.E. FENCE,
 BUILDING, WINDOWS, DOORS, OR OPENINGS.
  
 PROVIDE MANUFACTURE'S INSTALLATION
 INSTRUCTIONS AT THE JOBSITE FOR THE
 FIELD INSPECTOR.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-09-20 Cont ID  
Sent By dpalmer Date 2006-09-20 Time 19:50 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2006-08-23 Cont ID  
Sent By mmclean Date 2006-08-23 Time 18:05 Rev Time 0.00
Received By mmclean Date 2006-08-23 Time 18:05 Sent To I
Notes
2006-08-23 00:00:00NOTE:THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 7FTFROM REAR PROPERTY LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-12 Time 16:37 Rev Time 0.00
Received By mmclean Date 2006-06-12 Time 16:37 Sent To I
Notes
2006-06-12 00:00:00DENIED,
 1. MUST PROVIDE THE SETBACK OF THE
 GENERATOR FROM STRUCTURE, SIDE SETBACK &
 REAR SETBACK. (DISTANCE FROM PROPERTY
 LINE & STRUCUTRE).
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720