Plan Review Details - Permit 06060562
Plan Review Stops For Permit 06060562
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-03 Cont ID  
Sent By mjacobs Date 2006-11-03 Time 07:36 Rev Time 0.00
Received By mjacobs Date 2006-11-03 Time 07:19 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-10-12 Cont ID  
Sent By mjacobs Date 2006-10-12 Time 07:56 Rev Time 0.00
Received By mjacobs Date 2006-10-12 Time 06:34 Sent To  
Notes
2006-10-12 07:56:02BUILDING PLAN REVIEW
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW2ND
 ACTION: DENIED
  
  
 1) PROVIDE CLEAR AND DETAIL INSTRUCTIONS
 FOR THE REMOVAL OF THE AWNINGS DURING
 PERIODS OF 75MPH WINDS VELOCITY.OR THEY
 SHALL BE DESIGN TO WITH-STAND WINDS OF
 140MPH. A NOTORIZE LETTER FROM THE OWNER
 IS REQUIRED STATING THAT THE AWNINGS
 WILL BE REMOVED OR REPOSITIONED DURING
 PERIODS OF HIGH WINDS OF 75MPH.
  
 2)OK
  
 3)OK
  
 4) OK
  
 5) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 6 ) 713.13(2) F.S.THE NOTICE OF
 COMMENCEMENT MUST BE RE-RECORDED BECAUSE
 THE DESCRIBED IMPROVEMENT OR
 CONSTRUCTION DID NOT COMMENCE WITHIN 90
 DAYS OF RECORDING.
  
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-27 Cont ID  
Sent By mjacobs Date 2006-06-27 Time 11:42 Rev Time 0.00
Received By mjacobs Date 2006-06-27 Time 09:29 Sent To PC
Notes
2006-06-27 00:00:00 
 1) PROVIDE CLEAR AND DETAIL INSTRUCTIONS
 FOR THE REMOVAL OF THE AWNINGS DURING
 PERIODS OF 75MPH WINDS VELOCITY.OR THEY
 SHALL BE DESIGN TO WITH-STAND WINDS OF
 140MPH. A NOTORIZE LETTER FROM THE OWNER
 IS REQUIRED STATING THAT THE AWNINGS
 WILL BE REMOVED OR REPOSITIONED DURING
 PERIODS OF HIGH WINDS OF 75MPH.
  
 2)3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH
 A QUICK REMOVAL OR BREAKAWAY MEMBRANE OR
 FABRIC AT WIND VELOCITIES OF 75 MPH,
 SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1. MINIMUM WIND VELOCITY OF 3-SECOND
 WIND GUST 90 MPH
 2. IMPORTANCE FACTOR BASED ON LOW HAZARD
 TO HUMAN LIFE OF 0.77.
 3. EXPOSURE CATEGORY B FOR OR C AS
 DEFINED IN CHAPTER 16 . FOR MORE
 INFORMATION SEE SEC. 3105 FBC.
  
 3)2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 )NOTE: PLANS REQUIRED TO BE SIGNED,
 DATED AND SEALED BY THE ARCHITECT,
 PLEASE SEE FS 481.221 AND FAC 61G1-16
  
  
 4) ENGINEERS SHALL LEGIBLY INDICATE
 THEIR NAME, ADDRESS AND LICENSE NUMBER
 ON EACH SHEET. IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGIN- EERS, ENGINEERS SHALL LEGIBLY
 INDICATE THEIR NAME AND LICENSE NUMBER,
 AS WELL AS, THE NAME, ADDRESS AND
 CERTIFICATE OF AUTHORIZATION NUMBER OF
 THE ENGINEERING BUSINESS ON EACH SHEET.
 A TITLE BLOCK WILL SATISFY THIS
 REQUIREMENT. FAC 61G15-23.002(2) - FS
 471.025
  
 5) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-11-02 Cont ID  
Sent By adarroug Date 2006-11-02 Time 10:58 Rev Time 0.00
Received By adarroug Date 2006-11-02 Time 10:58 Sent To B
Notes
2006-11-02 10:58:32TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-11 Cont ID  
Sent By adarroug Date 2006-10-11 Time 16:08 Rev Time 0.00
Received By adarroug Date 2006-10-11 Time 16:08 Sent To B
Notes
2006-10-11 16:08:59TO "MJACOBS" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:38 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:38 Sent To B
Notes
2006-06-14 00:00:00TO "MISC" BOX#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-27 Time   Rev Time 0.00
Received By adarroug Date 2006-06-09 Time 13:24 Sent To  
Notes
2006-06-09 00:00:00TO "Z" BOX

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-12 Cont ID  
Sent By mflis Date 2006-06-12 Time 14:06 Rev Time 0.00
Received By mflis Date 2006-06-12 Time 14:06 Sent To  
Notes
2006-06-12 00:00:00APPROVED FOR REPAIR/REPLACEMENT OF
 EXISTING CANOPIES. MJF
 6/12/06 ROUTED TO INCOMING FOR FURTHER
 PROCESSING MM
  
  
  