Plan Review Details - Permit 06060499
Plan Review Stops For Permit 06060499 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-07-17 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-07-17 |
Time |
16:51 |
Rev Time |
0.00 |
Received By |
amorse |
Date |
2006-07-17 |
Time |
16:51 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-06-28 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-06-28 |
Time |
07:03 |
Rev Time |
0.50 |
Received By |
amorse |
Date |
2006-06-28 |
Time |
07:03 |
Sent To |
PC |
|
Notes |
2006-06-28 00:00:00 | | | | | DENIED | | | | 1) PERMIT APPLICATION HAS ONLY LAYOUT | | PLEASE SUBMIT MAUFACTURER SPEC'S AND | | ENGINEERING FOR BASE AND POLE TO MEET | | 140 MPH EXP. B WIND LOADS FOR WPB | | | | 2) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-07-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-07-15 |
Time |
11:58 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-07-15 |
Time |
11:44 |
Sent To |
B |
|
Notes |
2006-07-15 00:00:00 | ** PLANS REDLINED ** | | | | PANEL SCHEDULE HAS NO LOADS ON THIS PANE | | AS NOTED ON E-1. | | ALSO LOAD SHOWN ON PANEL SCHEDULE SHOULD | | BE THAT OF THE LOAD INDICATED ON THE | | LOAD CALCS ON SHEET ON UPPER RIGHT HAND | | CORNER. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-13 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-13 |
Time |
15:18 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-13 |
Time |
14:54 |
Sent To |
B |
|
Notes |
2006-06-13 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE SEE THE LOADS STILL NEED | | TO BE SHOWN ON A PANEL SCHEDULE TO BE | | SUBMITTED. | | PLEASE INDICATE THE CONTINOUS LAODS AT | | 125%. | | 215.3,215.5,230.42, 408.4 | | | | ) NOTE: PLEASE SEE BUILDING REVIEW | | COMMENTS FOR WIND LOAD CALCULATIONS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-07-12 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-07-12 |
Time |
15:39 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-12 |
Time |
15:39 |
Sent To |
E |
|
Notes |
2006-07-12 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-06-28 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-08 |
Time |
18:27 |
Sent To |
|
|
Notes |
2006-06-08 00:00:00 | TO "E" BOX |
|
|
|