Plan Review Details - Permit 06060452
Plan Review Stops For Permit 06060452
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-12-29 Cont ID  
Sent By lmartine Date 2006-12-29 Time 10:38 Rev Time 0.00
Received By lmartine Date 2006-12-29 Time 10:38 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-08-10 Cont ID  
Sent By alange Date 2006-08-10 Time 08:26 Rev Time 0.00
Received By alange Date 2006-08-10 Time 08:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:01 Rev Time 2.00
Received By alange Date 2006-06-30 Time 07:01 Sent To  
Notes
2006-06-30 00:00:00DENIED
  
  
 1. 713.13 F.S.A NOTICE OF COMMENCEMENT
 SHALL BE RECORDED AT PALM BEACH COUNTY
 COURTHOUSE AND A COPY SUBMITTED TO THIS
 OFFICE BEFORE A PERMIT CAN BE ISSUED.
 BLANK FORMS ARE AVAILABLE FROM THIS
 OFFICE.
 NOTE: THE NOTICE OF COMMENCEMENT MUST BE
 RE-RECORDED IF THE DESCRIBED IMPROVEMENT
 OR CONSTRUCTION IS NOT COMMENCED WITHIN
 90 DAYS OF RECORDING.
  
 2.PLANS SHALL BE DESIGNED TO ASCE
 7-02.
  
 3.SHOW GUARD RAIL DETAIL FOR BALCONY
 FBC 2004 R 312.1 AND 312.2
  
 4.FOOTING DEPTHS SHALL BE A MINIMUM OF
 12" SEE R-403.1.4
  
 5.THOSE PRODUCT APPROVALS WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.WPB
 AMENDMENT TO FBC 106.3.3.
  
 6.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
 SHOW HOW PLANS WILL COMPLY WITH THE
 SECTION(S) SELECTED.2004 FBC EXISTING
 BUILDING 301.5
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. SUBMIT ONE COPY OF
 OLD PAGES FOR REFERENCE . A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET
 OR SPECIFICATION PAGE WHERE THE CHANGES
 CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ART LANGE
 CONSTRUCTION SERVICES DEPARTMENT
 BUILDING PLANS EXAMINER
 561-805-6672
  
  

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2007-04-26 Cont ID  
Sent By dpalmer Date 2007-04-26 Time 12:20 Rev Time 0.00
Received By dpalmer Date 2007-04-26 Time 11:39 Sent To PC
Notes
2007-04-26 12:20:29NEW SET BROUGHTIN, OK, STAMPED
2007-04-26 11:54:58PLANS UNDER "R" IN LARGE BINS WAITING FOR SECOND
 SIGNED, AND SEALED SET. CALLED AND SPOKE TO TYLER.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2007-04-14 Cont ID  
Sent By dpalmer Date 2007-04-14 Time 08:45 Rev Time 0.00
Received By dpalmer Date 2007-04-14 Time 08:32 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2007-04-11 Cont ID  
Sent By dpalmer Date 2007-04-11 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2007-04-11 Time 08:58 Sent To PC
Notes
2007-04-11 09:32:15** UNSAT **
  
 1) NOTE: PLEASE SHOW ALL PANELS ON PLANS. PLEASE ALSO
 LABEL AS NOTED ON PANEL SCHEDULES. *( PANEL A, PANEL E
 ETC)*
 110.26, 240.24, 408.7
  
 2) NOTE: PLEASE INDICATE IF THERE IS A NEW OR EXISTING
 GFI ON KITCHEN ISLAND AS PREVIOUSLY REDLINED ON PLANS.
 210.52C2, 210.8A6
  
 3) NOTE: PLEASE VERIFY IF THE SMOKE DEVICES ARE SMOKE
 DETECTORS OR SMOKE ALARMS. IF THEY ARE LV AND USED TO
 DETECTSMOKE ONLY , THEN LEAVE AS SD, IF THEY ARE
 DEVICES WHICH ARE 120V, DETECT AND SOUND AND ALARM AT
 THE UNIT WHICH SIGNALS ALL OTHER DEVICES TO SOUND,
 PLEASE LABEL AS SA.
 PLEASE SEE FBC DEFINITIONS IN R313,AND NFPA-72 2002.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW, IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-11-13 Cont ID  
Sent By dpalmer Date 2006-11-13 Time 11:34 Rev Time 0.00
Received By dpalmer Date 2006-11-09 Time 08:14 Sent To PC
Notes
2006-11-13 11:36:54** REDLINED PLANS.
  
 PLEASE SEE 210.52C1, IF KITCHEN ISLAND,VERIFY IF NEW OR
 EXISTING.
  
 PLEASE KNOW, REVISED PANEL SCHEDULES WILL BE REQUIRED
 BEFORE FINAL.
 240.4,408.4,310.16
2006-11-09 14:38:12SPOKE TO DAN, HE IS GOING TO CALL BACK FOR SCOPE OF
 WORK AS IT APPEARS IT HAS SUBSTANTIALLY INCREASED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-08-03 Cont ID  
Sent By dpalmer Date 2006-08-03 Time 17:10 Rev Time 0.00
Received By dpalmer Date 2006-08-03 Time 17:10 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 07:19 Rev Time 0.00
Received By dpalmer Date 2006-06-15 Time 07:08 Sent To M
Notes
2006-06-15 00:00:00*********** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT ELECTRICAL
 PLAN/DETAIL FOR SCOPE OF WORK BEING
 PERMITTED.
 PLEASE SEE MINOR ELECTRICAL WHICH SEEMS
 TO BE SHOWN ON "A3" IS NOT CLEAR FOR NEW
 OR EXISTING??
 THE ELECTRICAL IS SHOWN IN LT GRAY??
 215.5, 106.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2007-04-24 Cont ID  
Sent By adarroug Date 2007-04-24 Time 09:25 Rev Time 0.00
Received By adarroug Date 2007-04-24 Time 09:25 Sent To E
Notes
2007-04-24 09:25:50TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2007-04-13 Cont ID  
Sent By adarroug Date 2007-04-13 Time 09:24 Rev Time 0.00
Received By adarroug Date 2007-04-13 Time 09:24 Sent To E
Notes
2007-04-13 09:24:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2007-04-10 Cont ID  
Sent By adarroug Date 2007-04-10 Time 08:51 Rev Time 0.00
Received By adarroug Date 2007-04-10 Time 08:51 Sent To E
Notes
2007-04-10 08:51:28TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-12-26 Cont ID  
Sent By adarroug Date 2006-12-26 Time 16:41 Rev Time 0.00
Received By adarroug Date 2006-12-26 Time 16:41 Sent To E
Notes
2006-12-26 16:41:44TO "BTROBAUG" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2006-12-16 Cont ID  
Sent By adarroug Date 2006-12-16 Time 16:07 Rev Time 0.00
Received By adarroug Date 2006-12-16 Time 16:07 Sent To Z
Notes
2006-12-16 16:08:09TO "Z" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2006-11-06 Cont ID  
Sent By adarroug Date 2006-11-06 Time 11:09 Rev Time 0.00
Received By adarroug Date 2006-11-06 Time 11:09 Sent To E
Notes
2006-11-06 11:09:36TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-09-22 Cont ID  
Sent By adarroug Date 2006-09-22 Time 08:59 Rev Time 0.00
Received By adarroug Date 2006-09-22 Time 08:59 Sent To B
Notes
2006-09-22 00:00:00TO "ALANGE" DESK/REV
 9/22/06-REV PULLED AND PUT UP FRONT TO
 P/U PER CONTRACTORS REQUEST

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-11 Cont ID  
Sent By adarroug Date 2006-08-11 Time 17:40 Rev Time 0.00
Received By adarroug Date 2006-08-11 Time 17:40 Sent To Z
Notes
2006-08-11 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-31 Cont ID  
Sent By adarroug Date 2006-07-31 Time 11:51 Rev Time 0.00
Received By adarroug Date 2006-07-31 Time 11:51 Sent To E
Notes
2006-07-31 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-20 Cont ID  
Sent By adarroug Date 2006-07-20 Time 18:07 Rev Time 0.00
Received By adarroug Date 2006-07-20 Time 18:07 Sent To Z
Notes
2006-07-20 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-14 Cont ID  
Sent By adarroug Date 2006-06-14 Time 09:02 Rev Time 0.00
Received By adarroug Date 2006-06-14 Time 09:02 Sent To E
Notes
2006-06-14 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:01 Rev Time 0.00
Received By alange Date 2006-06-08 Time 16:59 Sent To  
Notes
2006-06-08 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2006-08-08 Cont ID  
Sent By tgordon Date 2006-08-08 Time 10:35 Rev Time 0.15
Received By tgordon Date 2006-08-08 Time 10:35 Sent To B
Notes
2006-08-08 00:00:00MECHANICAL PERMIT #06060461 WAS VOIDED
 8-7-06.
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By tgordon Date 2006-06-15 Time 16:03 Rev Time 0.20
Received By tgordon Date 2006-06-15 Time 16:03 Sent To P
Notes
2006-06-15 00:00:00*** DENIED ***
 1)NO MECHANICAL PLANS WERE SUBMITTED FOR
 REVIEW. PLEASE SUBMIT MECHANICAL PLANS
 FOR REVIEW, OR YOU MAY WISH TO VOID YOUR
 MECHANICAL PERMIT NUMBER 06060461 SO
 YOUR BUILDING PLANS MAY BY-PASS A
 MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-08-08 Cont ID  
Sent By jleech Date 2006-08-08 Time 08:08 Rev Time 0.00
Received By jleech Date 2006-08-08 Time 08:08 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-19 Cont ID  
Sent By jleech Date 2006-06-19 Time 14:05 Rev Time 0.00
Received By jleech Date 2006-06-19 Time 14:05 Sent To B
Notes
2006-06-19 00:00:00NOT ENOUGH INFORMATION TO DO A PLUMBING
 PLAN REVIEW; IF ONLY A FIXTURE CHANGE
 OUT PLEASE STATE ON PLANS IF FIXTURES
 ARE ADDED OR CHANGED PLEASE SHOW ON
 DRAWINGS AND ADD A RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 4 Status P Date 2006-12-22 Cont ID  
Sent By mmclean Date 2006-12-22 Time 13:38 Rev Time 0.00
Received By mmclean Date 2006-12-22 Time 13:38 Sent To I
Notes
2006-12-22 13:39:18REVISION FOR GARDEN PATIO SLAB & FOOTINGS.

Review Stop Z ZONING
Rev No 3 Status P Date 2006-08-12 Cont ID  
Sent By mmclean Date 2006-08-12 Time 08:03 Rev Time 0.00
Received By mmclean Date 2006-08-12 Time 08:03 Sent To B
Notes
2006-08-12 00:00:00ADDITIONAL PERMIT REQUIRED FOR THE
 PROPOSED GARDEN PATIO
  
  
 ROUTED TO ART TO VERIFY ALL DOCUMENTS
 AND ISSUE PERMIT.

Review Stop Z ZONING
Rev No 2 Status F Date 2006-07-28 Cont ID  
Sent By mmclean Date 2006-07-28 Time 18:29 Rev Time 0.00
Received By mmclean Date 2006-07-28 Time 18:29 Sent To I
Notes
2006-07-28 00:00:00DENIED,
 1. NEED TO INDICATE CLEARLY THE PROPOSED
 WORK ON THE TWO COPY OF SITEPLAN.
 (BESIDES THE DRIVEWAY).
 2. MUST PULL A SEPERATE PERMIT FOR THE
 WALL/GATE/FENCE WITH EASEMENT APPROVAL
 FROM THE CITY OF WEST PALM BEACH UTILITY
 DEPT.
 3. IF THE GARDEN PATIO IS APART OF THE
 PROPOSED EXTERIOR RENOVATION, PLEASE
 SHOW THE SETBACK FROM THE PROPERTY LINE.
  
 NOTE: MUST MAINTAIN THE REQUIRED HEIGHT
 OF THE STRUCTURE 33FT (INCLUDING
 CHIMNEY).
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By mmclean Date 2006-06-12 Time 16:11 Rev Time 0.00
Received By mmclean Date 2006-06-12 Time 16:11 Sent To I
Notes
2006-06-12 00:00:00DENIED,
 1. MUST PROVIDE A COPY OF CURRENT SURVEY
 SHOWING THE EXISTING STRUCTURE.
  
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720