Plan Review Details - Permit 06060432
Plan Review Stops For Permit 06060432
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 08:14 Rev Time 0.00
Received By alange Date 2006-07-26 Time 08:14 Sent To  
Notes
2006-07-26 00:00:00REVIEWED AND STAMPED NEW PAGES

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:43 Rev Time 0.33
Received By alange Date 2006-06-30 Time 07:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-28 Cont ID  
Sent By dpalmer Date 2006-10-28 Time 15:18 Rev Time 0.00
Received By dpalmer Date 2006-10-28 Time 14:54 Sent To PC
Notes
2006-10-28 15:19:03REDLINED***
  
  
 ALL KITCHEN COUNTER SPACE RECEPTS TO BE GFI/GFI
 PROTECTED PER 210.8A6
  
 BATHS OT BE PER 210.52D,210.11C3

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-23 Cont ID  
Sent By dpalmer Date 2006-07-23 Time 14:50 Rev Time 0.00
Received By dpalmer Date 2006-07-23 Time 13:49 Sent To M
Notes
2006-07-23 00:00:00********** PROVISO ***********
  
 ** THE FOLLOWING SHALL BE REVISED BEFORE
 ROUGH ELECTRICAL INSPECTION.
  
  
 1) PLEASE PROVIDE A REVISED PANEL
 SCHEDULE LISITNG ALL THE MIN REQUIRED
 DEDICATED CIRCUITS AS SHOWN ON PLANS.
 FRIG, MICRO, SMALL APPL, BATH,ETC
 210.52B1,210.11C1,210.11C3,220.16,408.4
 ETC.
  
 2) PLEASE SEE THAT ALL RECEPTS SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/ GFI
 PROTECTED.
 2108A6
  
 3) PLEASE SEE SPACING SHALL MEET
 210.52C1-5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-14 Cont ID  
Sent By dpalmer Date 2006-06-14 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2006-06-14 Time 11:48 Sent To P
Notes
2006-06-14 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE MISSING GFI RECEPT
 SPACING FOR NEW KITCHEN LAYOUT PER
 210.52C 1-5.
  
 2) NOTE: PLEASE SEE 210.8A6
  
 3) NOTE: PLEASE SEE MIN OF TWO SM APPL
 CIRCUITS SHALL BE INDICATED.
 210.52B1,210.11C1, 220.16 ETC
  
 4) NOTE: PLEASE SEE MISSING SD'S PER
 NFPA-72 11.5.1.1. PLEASE SHOW AS
 EXISITNG MEETING CURRENT CODES OR NEW
 ARE REQUIRED TO BE INSTALLED.
 R-313
  
 5) NOTE: PLEASE SEE THAT PLANS/DESIGN
 SHALL CONTAIN THE CURRENT CODES IN
 EFFECT FOR PROJECT. 2004 FBC , 2002 NEC.
 PLEASE SEE THE PLANS/DESIGN SHALL
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND
 DESIGN.
 FBC ADMIN SECT 104.2.1,106.1.2
  
 PLEASE SEE ANY OTHER COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-25 Cont ID  
Sent By adarroug Date 2006-10-25 Time 18:32 Rev Time 0.00
Received By adarroug Date 2006-10-25 Time 18:32 Sent To E
Notes
2006-10-25 18:32:58TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-07-21 Cont ID  
Sent By adarroug Date 2006-07-21 Time 14:10 Rev Time 0.00
Received By adarroug Date 2006-07-21 Time 14:09 Sent To E
Notes
2006-07-21 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-30 Cont ID  
Sent By alange Date 2006-06-30 Time 07:43 Rev Time 0.00
Received By alange Date 2006-06-08 Time 17:00 Sent To  
Notes
2006-06-08 00:00:00TO "E" BOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 08:09 Rev Time 0.00
Received By alange Date 2006-07-26 Time 08:09 Sent To  
Notes
2006-07-26 00:00:00MECHANICAL PERMIT REMOVED, RECEIVED
 NOTORIZED LETTER

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2006-07-24 Cont ID  
Sent By tgordon Date 2006-07-24 Time 16:48 Rev Time 0.20
Received By tgordon Date 2006-07-24 Time 16:48 Sent To P
Notes
2006-07-24 00:00:00*** DENIED ***
 1) AS NOTED IN LAST REVIEW 6-21-06 NOTE
 #1, NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06060436 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-21 Cont ID  
Sent By tgordon Date 2006-06-21 Time 09:30 Rev Time 0.20
Received By tgordon Date 2006-06-21 Time 09:30 Sent To B
Notes
2006-06-21 00:00:00*** DENIED ***
 1) NO MECHANICAL PLANS WERE SUBMITTED
 FOR REVIEW. PLEASE SUBMIT MECHANICAL
 PLANS FOR REVIEW, OR YOU MAY WISH TO
 VOID YOUR MECHANICAL PERMIT NUMBER
 06060436 SO YOUR BUILDING PLANS MAY
 BY-PASS A MECHANICAL REVIEW.
  
 2) PLEASE SEE ELECTRICAL REVIEW NOTE #5
 AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-07-26 Cont ID  
Sent By alange Date 2006-07-26 Time 08:13 Rev Time 0.00
Received By alange Date 2006-07-26 Time 08:13 Sent To  
Notes
2006-07-26 00:00:00ELECTRICL CORRECTION MADE FOR #5

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By jleech Date 2006-06-20 Time 14:16 Rev Time 0.00
Received By jleech Date 2006-06-20 Time 14:16 Sent To M
Notes
2006-06-20 00:00:00DENIED;
 SEE ELECTRICAL PLAN REVIEWER'S NOTE # 5.