Plan Review Details - Permit 06060425
Plan Review Stops For Permit 06060425
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2006-06-30 Cont ID  
Sent By amorse Date 2006-06-30 Time 08:39 Rev Time 0.75
Received By amorse Date 2006-06-30 Time 08:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By amorse Date 2006-06-22 Time 11:59 Rev Time 0.75
Received By amorse Date 2006-06-22 Time 11:59 Sent To PC
Notes
2006-06-22 00:00:00 
  
  
 DENIED
  
 1) SHUTTER #4 IS IN THE END ZONE(5) AND
 HAS A PRESSURE OF -72.16 AND 1 SPAN OF
 7'-7" THIS DOES NOT MEET THE MAX SLAT
 SPAN AS REQUIRED ON TABLE 1 PAGE 4
  
 2) THERE IS CONFUSION BETWEEN ENGINEERED
 DRAWING AND SKETCH WITH THE SIZE OF
 OPENING FOR #5. SKETCH AND SCHEDULE
 HAS 1 OPENING, ENGINEERING HAS 2. IF WE
 FOLLOW THE ENGINEERED SHEET THE SLAT
 SPAN EXCEEDS THE MAX FOR STATED PRESSURE
 ON OPENING #4, IF IT IS 1 OPENING IT
 WOULD THEN BE IN ZONE 5 BUT WILL HAVE A
 LARGER AREAAND A NEW PRESSURE SHOULD
 BE ASSIGNED. WITH 2 SPANS IT STILL MAY
 NOT MEET THE MAX ALLOWABLE SPAN ON PG. 4
  
 3) STORM BAR SIZE SCHEDULE ON PAGE 7 ARE
 NOT SHOWN FOR WORST CASE PRESSURES AND
 CORRECT LENGTHS. ARE THEIR HEADERS OR
 ARE THEY COMPLETE HEIGHT TO UNDER SIDE
 OF DECK ABOVE OR BOTH? PLEASE SHOW ON
 PAGE 3
  
 4) MULLION AND HEADER SIZES AND SPANS
 WILL DEPEND ON THE ANSWERS TO NOTES 1&2,
 PLEASE FILLOUT AS REQUIRED BY
 ENGINEERING
  
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-06-29 Cont ID  
Sent By dpalmer Date 2006-06-29 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2006-06-29 Time 12:04 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By dpalmer Date 2006-06-15 Time 07:02 Rev Time 0.00
Received By dpalmer Date 2006-06-15 Time 07:01 Sent To B
Notes
2006-06-15 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE A DETAIL FOR
 ELECTRICAL HOOK-UP OF SHUTTER MOTORS.
 THIS DETAIL CAN BE TYPICAL.
 PLEASE BE SURE THE PERSON RESPONSIBLE
 FOR PLAN/DESIGN TO PRINT NAME AND SIGN
 PLAN/DETAIL.
 FBC 106.2.1, 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2006-06-29 Time   Rev Time 0.00
Received By adarroug Date 2006-06-26 Time 15:28 Sent To  
Notes
2006-06-26 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-06-22 Time   Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 14:45 Sent To  
Notes
2006-06-08 00:00:00TO "E" BOX