Plan Review Details - Permit 06060425
Plan Review Stops For Permit 06060425 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2006-06-30 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-06-30 |
Time |
08:39 |
Rev Time |
0.75 |
Received By |
amorse |
Date |
2006-06-30 |
Time |
08:39 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-06-22 |
|
|
Cont ID |
|
Sent By |
amorse |
Date |
2006-06-22 |
Time |
11:59 |
Rev Time |
0.75 |
Received By |
amorse |
Date |
2006-06-22 |
Time |
11:59 |
Sent To |
PC |
|
Notes |
2006-06-22 00:00:00 | | | | | | | DENIED | | | | 1) SHUTTER #4 IS IN THE END ZONE(5) AND | | HAS A PRESSURE OF -72.16 AND 1 SPAN OF | | 7'-7" THIS DOES NOT MEET THE MAX SLAT | | SPAN AS REQUIRED ON TABLE 1 PAGE 4 | | | | 2) THERE IS CONFUSION BETWEEN ENGINEERED | | DRAWING AND SKETCH WITH THE SIZE OF | | OPENING FOR #5. SKETCH AND SCHEDULE | | HAS 1 OPENING, ENGINEERING HAS 2. IF WE | | FOLLOW THE ENGINEERED SHEET THE SLAT | | SPAN EXCEEDS THE MAX FOR STATED PRESSURE | | ON OPENING #4, IF IT IS 1 OPENING IT | | WOULD THEN BE IN ZONE 5 BUT WILL HAVE A | | LARGER AREAAND A NEW PRESSURE SHOULD | | BE ASSIGNED. WITH 2 SPANS IT STILL MAY | | NOT MEET THE MAX ALLOWABLE SPAN ON PG. 4 | | | | 3) STORM BAR SIZE SCHEDULE ON PAGE 7 ARE | | NOT SHOWN FOR WORST CASE PRESSURES AND | | CORRECT LENGTHS. ARE THEIR HEADERS OR | | ARE THEY COMPLETE HEIGHT TO UNDER SIDE | | OF DECK ABOVE OR BOTH? PLEASE SHOW ON | | PAGE 3 | | | | 4) MULLION AND HEADER SIZES AND SPANS | | WILL DEPEND ON THE ANSWERS TO NOTES 1&2, | | PLEASE FILLOUT AS REQUIRED BY | | ENGINEERING | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2006-06-29 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-29 |
Time |
12:11 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-29 |
Time |
12:04 |
Sent To |
B |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-15 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-15 |
Time |
07:02 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-15 |
Time |
07:01 |
Sent To |
B |
|
Notes |
2006-06-15 00:00:00 | *** UNSAT *** | | | | 1) NOTE: PLEASE PROVIDE A DETAIL FOR | | ELECTRICAL HOOK-UP OF SHUTTER MOTORS. | | THIS DETAIL CAN BE TYPICAL. | | PLEASE BE SURE THE PERSON RESPONSIBLE | | FOR PLAN/DESIGN TO PRINT NAME AND SIGN | | PLAN/DETAIL. | | FBC 106.2.1, 215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-06-29 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-26 |
Time |
15:28 |
Sent To |
|
|
Notes |
2006-06-26 00:00:00 | TO "DPALMER" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
2006-06-22 |
Time |
|
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-08 |
Time |
14:45 |
Sent To |
|
|
Notes |
2006-06-08 00:00:00 | TO "E" BOX |
|
|
|