Plan Review Details - Permit 06060419
Plan Review Stops For Permit 06060419
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-28 Cont ID  
Sent By rnuquist Date 2006-06-28 Time 20:29 Rev Time 0.00
Received By rnuquist Date 2006-06-28 Time 20:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2006-07-18 Cont ID  
Sent By btrobaug Date 2006-07-18 Time 05:59 Rev Time 0.50
Received By btrobaug Date 2006-07-18 Time 05:41 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-20 Cont ID  
Sent By btrobaug Date 2006-06-20 Time 08:29 Rev Time 0.33
Received By btrobaug Date 2006-06-20 Time 08:19 Sent To P
Notes
2006-06-20 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-15 Cont ID  
Sent By adarroug Date 2006-07-15 Time 10:15 Rev Time 0.00
Received By adarroug Date 2006-07-15 Time 10:15 Sent To E
Notes
2006-07-15 00:00:00TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 10:25 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 10:25 Sent To E
Notes
2006-06-19 00:00:00TO "E" BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-07-15 Cont ID  
Sent By adarroug Date 2006-06-28 Time 10:13 Rev Time 0.00
Received By adarroug Date 2006-06-08 Time 10:54 Sent To  
Notes
2006-06-08 00:00:00TO "Z" BOX

Review Stop P PLUMBING
Rev No 1 Status P Date 2006-06-20 Cont ID  
Sent By mperson Date 2006-06-20 Time 15:49 Rev Time 0.33
Received By mperson Date 2006-06-20 Time 15:48 Sent To B
Notes
2006-06-20 00:00:00 
  
 ******PROVISO******
 1) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004
 SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL
 BE MOUNTED ON A SUBSTANTIAL BASE IN A
 MANNER THAT WILL ELIMINATE STRAIN ON
 PIPING.SLAB SHALL BE A NOMINAL 4"
 THICK.

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-18 Cont ID  
Sent By mmclean Date 2006-06-18 Time 19:32 Rev Time 0.00
Received By mmclean Date 2006-06-18 Time 19:31 Sent To I
Notes
2006-06-18 00:00:00NOTE: THE PROPOSED POOL EQUIPMENT WILL
 BE 7FT FROM SIDE PROPERTY INE.
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  