Plan Review Details - Permit 06060302
Plan Review Stops For Permit 06060302
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 15:35 Rev Time 0.50
Received By alange Date 2006-06-27 Time 15:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-08-23 Cont ID  
Sent By jleahy Date 2006-08-23 Time 16:23 Rev Time 1.30
Received By jleahy Date 2006-08-23 Time 16:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-07-15 Cont ID  
Sent By dpalmer Date 2006-07-15 Time 11:21 Rev Time 0.00
Received By dpalmer Date 2006-07-15 Time 11:03 Sent To PC
Notes
2006-07-15 00:00:00******* UNSAT *******
  
 1) NOTE: PLEASE SEE RISER IS NOW BEING
 SHOWN COMPLETELY REVISED FROM PREVIOUS
 RISERAND IS NOW SHOWING "TWO' ATS'S??
 PLEASE SEE RISER SHOWS A NOTE WHICH
 MENTIONS TWO EXSITING PANELS, YET, RISER
 SHOWS ONE AS A MAIN DISCONNECT?
 PLEASE SEE NEW MAIN SHOWS CONNECTIONS TO
 BOTH ATS UNITS. ONE SE RATED AND THE
 OTHER NOT SE RATED??
  
 PLEASE SEE THE SE RATED ATS AS ONLY
 DISCONNECTS THE POWER ON THE FPL/LINE
 SIDE AND DOES NOT DISCONNECT POWER ON
 THE GEN/FEEDER SIDE AS REQUIRED BY
 225.31-225.39
 PLEASE KNOW, PLANS DO NOT INDICATE IF
 THE EXISTING 200A PANEL IS MLO OR MCB
 AND IF THIS PANEL IS GROUPED WITH THE
 OTHER MAINS.
 230.72,225.34
 PLEASE KNOW, IF A MAIN DISCONNECT IS
 LOCATED AHEAD OF THE ATS, THEN THE ATS
 DOES NOT NEED TO BE SE RATED AND ONLY
 RATED AS "SERVICE EQUIPMENT".
 PLEASE EXPLAIN RATIONAL OF THE 2ND NON
 SE RATED ATS? WHY IS THIS BEING USED AS
 THIS IS SHOWN FEEDING THE SAME SE RATED
 ATS.
 PLEASE ALSO SEE THE NEW MAIN DISCONNECT
 IS BEING SHOWN FEEDING THE NEW SE RATED
 ATS AND THE NON SE RATED ATS?
 SPECS SHOULD REFLECT THE ATS BEING
 INSTALLED.
  
 ** PLEASE KNOW, RISER NOW ALSO MENTIONS
 TO ISOLATE NEUTRALS IN PANEL "IF
 NECESSARY". PLEASE KNOW, ALL NEUTRALS
 AND EQUIPMENT GROUNDING CONDUCTORS SHALL
 BE SEPARATED AFTER THE FIRST MEANS OF
 DISONNECT AS NOT TO PARALLEL THE
 NEUTRAL.
 250.6,250.24B
  
 2) NOTE: PLEASE KNOW, THE LATEST LTR
 FROM GENERAC FOR MIN CLEARENCES LEAVES
 THE REQUIRED MIN CLEARNECES TO THE AHJ,
 AND AS STATED AND RECOMMENDED ON A LTR
 OBTAIN FROM GENERAC, THE MIN CLEARNECES
 FOR AIR COOLED UNITS, SHALL BE 3' AND
 LIQUID COLLED UNITS SHALL BE 5' FROM ANY
 SURROUNDING WALLS , ETC.
 THIS IS A NOTE FOR ANY INSTALLATIONS.
  
 3) NOTE: PLEASE SPECIFY THE ELEVATION OF
 THE SLAB FOR THE NEW GEN. THE LTR WHICH
 MENTIONS THE FLOOD ZONEIS OK, HOWEVER
 SLAB ELEVATIONS SHOULD BE NOTED OR
 SHOWN. PLEASE SEE AN ELEV OF 12 IS SHOWN
 IN LTR, BUT UNCLEAR IF THIS IS 12'
 (FEET). IF SO, ELEV SHOULD BE NOTED ON
 SLAB DETAIL TO BE 12'6" MIN. PLEASE
 KNOW, AN ELEVATION CERTIFICATE WILL BE
 REQUIRED BEFORE FINAL.
  
  
 4) NOTE: PLEASE MAKE PLANS INTO TWO SETS
 AND REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS AND LEAVE ANY PREVIOUSLY STAMPED
 SHEETS BE OTHER REVIEWER(S) IN SETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-22 Cont ID  
Sent By dpalmer Date 2006-06-22 Time 21:11 Rev Time 0.00
Received By dpalmer Date 2006-06-22 Time 20:58 Sent To M
Notes
2006-06-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SEE SITE SURVEY WHICH
 WILL REQUIRE ALL SETBACKS AND DIMENSIONS
 FROM DWELLING AND PROPERTY LINES. PLEASE
 SEE THAT THE CLEARENCS OF THE GEN CAN
 NOT BE VERIFIED AT THIS TIME.
 215.5
  
 2) NOTE: PLEASE PROVIDE A SERVICE
 ENTRANCE RATED ATS WHICH DISCONNECTS
 POWER FROM FPL. SPECS SEEM TO INDICATE
 THIS, BU NOT CLEAR.
 CAN NOT VEIRFY THE MEANS OF DISCONNECT
 FROM THE FEEDERS FROM THE GEN. PLEASE
 SEE 230.76,230.79, 230.70
 PLEASE SEE 225.31-225.39 WHICH REQUIRES
 A DISC. PLEASE VERIFY IF THE EXSITING
 PANEL AS SHOWN IS LOCATED AT ATS
 LOCATION AND CONTAINS A MCB?
  
 3) NOTE: PLEASE INDICATE LOCATION OF ALL
 EQUIPMENT ON A LAYOUT FOR HOUSE.
 215..
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
 PLEASE ALSO INDICATE THE RATING FOR ATS.
  
 5) NOTE: PLEASE SEE LOAD CALCULATIONS,
 PLEASE SHOW HEAT LOADS AT 100% OR
 PROVIDE LOAD SHEDDING. ** AS SHOWN EVEN
 AT 100%, THERE IS NOT A LOAD ISSUE FOR
 GEN.
 702.5,220, ETC.
 215.5
  
 6) NOTE: PLEASE SEE THAT THE RESPONSIBLE
 LICENSE CONTRACTOR SHALL PRINT NAME AND
 SIGN PLANS.
 FBC 106.2.1, 106.3.2.1 ADMIN SECT AS
 ADOPTED BY THE CITY OF WEST PALM BEACH
  
 7) NOTE: PLEASE BE SURE THE MANUFACTURES
 SPECS / CUT SHEETS SHALL INDICATE THE
 MIN CLEARENCES SET BY THE MANUFACTURE.
 215.5
  
 8) NOTE: PLEASE SUBMIT THE ELEVATION OF
 GENERATOR.FYI, IF IN A FLOOD ZONE, MUST
 BE 6" ABOVE BFE.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 13:14 Rev Time 0.15
Received By mperson Date 2006-06-23 Time 13:14 Sent To B
Notes
2006-06-23 00:00:00NOTE: GAS PERMIT REQUIRED. GAS CONTRAC-
 TOR TO SUBMIT PLANS WITH PERMIT APPLICA-
 TION. ALL GAS INSPECTIONS TO BE COMPLETE
 BEFORE FINAL GEN/RES INSPECTION.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2006-08-10 Cont ID  
Sent By mmiller Date 2006-08-10 Time 15:23 Rev Time 0.00
Received By mmiller Date   Time   Sent To E
Notes
2006-08-10 00:00:00SENT TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2006-08-03 Cont ID  
Sent By adarroug Date 2006-08-03 Time 15:06 Rev Time 0.00
Received By adarroug Date 2006-08-03 Time 15:06 Sent To Z
Notes
2006-08-03 00:00:00TO "Z" BOX/RESUB--NEW SHEETS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2006-07-11 Cont ID  
Sent By adarroug Date 2006-07-11 Time 08:49 Rev Time 0.00
Received By adarroug Date 2006-07-11 Time 08:49 Sent To E
Notes
2006-07-11 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-07-03 Cont ID  
Sent By adarroug Date 2006-07-03 Time 14:49 Rev Time 0.00
Received By adarroug Date 2006-07-03 Time 14:49 Sent To Z
Notes
2006-07-03 00:00:00TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-06-19 Cont ID  
Sent By adarroug Date 2006-06-19 Time 11:27 Rev Time 0.00
Received By adarroug Date 2006-06-19 Time 11:27 Sent To E
Notes
2006-06-19 00:00:00TO "GEN-RES" "E"

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-06-27 Cont ID  
Sent By alange Date 2006-06-27 Time 15:35 Rev Time 0.00
Received By alange Date 2006-06-07 Time 16:49 Sent To  
Notes
2006-06-07 00:00:00TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2006-07-11 Cont ID  
Sent By tgordon Date 2006-07-11 Time 11:59 Rev Time 0.15
Received By tgordon Date 2006-07-11 Time 11:59 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2006-06-23 Cont ID  
Sent By tgordon Date 2006-06-23 Time 09:52 Rev Time 0.15
Received By tgordon Date 2006-06-23 Time 09:51 Sent To P
Notes
2006-06-23 00:00:00*** DENIED ***
 1) PLEASE SEE ZONING REVIEW AND CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.

Review Stop P PLUMBING
Rev No 1 Status N Date 2006-06-23 Cont ID  
Sent By mperson Date 2006-06-23 Time 13:14 Rev Time 0.00
Received By mperson Date 2006-06-23 Time 13:14 Sent To G
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status N Date 2006-08-08 Cont ID  
Sent By mmclean Date 2006-08-08 Time 10:02 Rev Time 0.00
Received By mmclean Date 2006-08-08 Time 10:02 Sent To  
Notes
2006-08-09 00:00:00ALREADY REVIEWED AND STAMPED 7/8/06

Review Stop Z ZONING
Rev No 2 Status P Date 2006-07-08 Cont ID  
Sent By mmclean Date 2006-07-08 Time 09:10 Rev Time 0.00
Received By mmclean Date 2006-07-08 Time 09:10 Sent To I
Notes
2006-07-08 00:00:00NOTE:
 THE PROPOSED GENERATOR SHALL NOT BE
 CLOSER THAN 1FT FROMSIDE PROPERTY
 LINE.

Review Stop Z ZONING
Rev No 1 Status F Date 2006-06-16 Cont ID  
Sent By mmclean Date 2006-06-16 Time 16:40 Rev Time 0.00
Received By mmclean Date 2006-06-16 Time 16:40 Sent To I
Notes
2006-06-16 00:00:00DENIED,
 1. NEED TO PROVIDE THE SETBACK OF THE
 PROPOSED GENERATOR FROM THE STRUCTURE &
 SIDE SETBACK (PROPERTY LINE) ON TWO COPY
 OF SURVEY.
  
 SEC 94-303 MECHANICAL/POOL
 EQUIPMENT/GENERATOR MAY NOT PROJECT MORE
 THAN FOUR FEET INTO A SETBACK.
  
  
 MICHELLE MCLEAN
 ZONING TECHNICIAN
 805-6720
  
  
  
  