Plan Review Details - Permit 06060244
Plan Review Stops For Permit 06060244 |
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-07-26 |
|
|
Cont ID |
|
Sent By |
jleahy |
Date |
2006-07-26 |
Time |
16:24 |
Rev Time |
0.39 |
Received By |
jleahy |
Date |
2006-07-26 |
Time |
16:23 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-06-30 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-06-30 |
Time |
16:36 |
Rev Time |
1.00 |
Received By |
btrobaug |
Date |
2006-06-30 |
Time |
14:40 |
Sent To |
PC |
|
Notes |
2006-06-30 00:00:00 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE 3-3/0 FEEDERS FROM THE UTILITY TO | | THE 600 AMP METER ARE INCORRECT. THERE | | IS 300 AMP OVERCURRENT PROTECTION IN THE | | MAIN GEAR. SEE 310.16. SHEET E2 DOES NOT | | CORRELATE WITH E1, WHICH SHOWS 250 | | ALUMINUM. | | | | 2} INDICATE THE PRIMARY AND SECONDARY | | FEEDER AND CONDUIT SIZES FROM THE | | DISCONNECTS TO THE 25KVA TRANSFORMER, | | RISER #1. | | | | 3} THE OCP FOR THE SECONDARY OF THE | | 25KVA TRANSFORMER IS NOT INDICATED, ONLY | | A 100 AMP DISCONNECT IS SHOWN, BUT THE | | OCP SIZE MUST COMPLY WITH 430.3(B). | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | | | | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-06-08 |
Time |
08:02 |
Rev Time |
0.33 |
Received By |
btrobaug |
Date |
2006-06-08 |
Time |
07:38 |
Sent To |
PC |
|
Notes |
2006-06-08 00:00:00 | | | | | THE SCOPE OF THIS WORK REQUIRES | | ENGINEERING PER CHAPTER 471.003, FLORIDA | | STATUTES. ALL SERVICES DESIGNED OVER 240 | | VOLTS ARE OUT OF THE SCOPE OF EXEMPTION. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-07-17 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-07-17 |
Time |
11:20 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-07-17 |
Time |
11:20 |
Sent To |
E |
|
Notes |
2006-07-17 00:00:00 | TO "BTROBAUG" DESK/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-06-23 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-23 |
Time |
14:03 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-23 |
Time |
14:03 |
Sent To |
E |
|
Notes |
2006-06-23 00:00:00 | TO "E" BOX/RESUB |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-06-08 |
|
|
Cont ID |
|
Sent By |
btrobaug |
Date |
2006-06-08 |
Time |
07:38 |
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2006-06-07 |
Time |
10:55 |
Sent To |
E |
|
Notes |
2006-06-07 00:00:00 | TO "E" BOX |
|
|
|