Plan Review Stops For Permit 06051268 |
Review Stop |
AD |
ADDRESSING |
Rev No |
1 |
Status |
P |
Date |
2006-06-01 |
|
|
Cont ID |
|
Sent By |
lursu |
Date |
2006-06-01 |
Time |
14:44 |
Rev Time |
0.00 |
Received By |
lursu |
Date |
2006-06-01 |
Time |
09:55 |
Sent To |
|
|
Notes |
2006-06-01 00:00:00 | ADD EXT #0001 UNDER 5335 N MILITARY TRL | | FOR SUITE 40 |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-11-14 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-11-14 |
Time |
15:39 |
Sent To |
PC |
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-09-07 |
Time |
16:45 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-09-07 |
Time |
14:05 |
Sent To |
|
|
Notes |
2006-09-07 00:00:00 | | | | | 1) SHEET A-3 HAS CONFLICTING | | INFORMATION.THE LIFE SAFETY SUMMARY | | INDICATES A SPRINKLER SYSTEM,HOWEVER, | | BELOW STATES A TYPE IV UNSPRINKLERED | | BUILDING. SO IS THERE A SPRINKLER SYSTEM | | IN THE BUILDING OR NOT? | | | | 2) THE OCCUPANT LOAD STATED ON SHEET A-3 | | IS INCORRECT. SEE TABLE 1004.1.2 FOR | | MORE INFORMATION AND MAKE THE | | ADJUSTMENTS ACCORDINGLY IN REFERENCE TO | | THE OCCUPANT LOAD. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2006-06-15 |
|
|
Cont ID |
|
Sent By |
mjacobs |
Date |
2006-06-15 |
Time |
09:26 |
Rev Time |
0.00 |
Received By |
mjacobs |
Date |
2006-06-15 |
Time |
09:16 |
Sent To |
|
|
Notes |
2006-06-15 00:00:00 | | | 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1, | | 2004 SHALL BE DESIGNED TO THE 2004 | | FLORIDA BUILDING CODE. | | | | 2) (2004 FBC) 106.1.1 INFORMATION ON | | CONSTRUCTION DOCUMENTS. CONSTRUCTION | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | TO INDICATE THE LOCATION, NATURE & | | EXTENT OF THE WORK PROPOSED & SHOW IN | | DETAIL THAT IT WILL CONFORM TO THE | | PROVISIONS OF THIS CODE AND REVELENT | | LAWS, ORDINANCES, AND RULES AND | | REGULATIONS AS DETERMINED BY THE | | BUILDING OFFICIAL. | | | | 3) 110.2* W. P. B. ADMINISTRATIVE CODE, | | INFORMATION THAT IS REQUIRED FOR RECORD | | KEEPING & FOR CERTIFICATE OF OCCUPANCY: | | A) THE EDITION OFTHE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | B) THE USE AND OCCUPANCY, IN ACCORDANCE | | WITH THE PROVISIONS OF CHAPTER 3. | | C) THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6, TABLE 601. | | D) THE DESIGN OCCUPANT LOAD, SEE 1004. | | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | F) ANY SPECIAL STIPULATIONS & CONDITIONS | | OF THE BUILDING PERMIT. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | TEL:(561)805-6726 | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
Received By |
btrobaug |
Date |
2006-12-14 |
Time |
11:03 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2006-10-27 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-10-27 |
Time |
19:38 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-10-27 |
Time |
19:15 |
Sent To |
|
|
Notes |
2006-10-27 19:39:24 | REDLINED,,, | | | | | | ALL EM./EXT LTS ARE REQUIRED TO BE WIRED AHEAD OF ANY | | LIGHTING CONTROLLED/SWITCHED CIRCUITS. 700.12E. |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2006-09-07 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-09-07 |
Time |
12:25 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-09-07 |
Time |
10:29 |
Sent To |
|
|
Notes |
2006-09-07 00:00:00 | ** UNSAT 2ND REVIEW ** | | | | ** PLANS ARE NOW SUBMITTED FOR PERMIT. | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS | | REVIEW STILL NEED TO BE ADDRESSED. | | PLEASE SEE NOTES BELOW ARE TAKEN | | DIRECTLY FROM PREVIOUS REVIEW. PLEASE | | SEE NEW NOTE ADDED TO END OF NOTES. | | | | | | | | 1) NOTE: OK. | | | | 2) NOTE: NO, PLEASE SEE PLANS DO NOT | | COMPLY AND INDICATE REQUIREMENTS FOR | | CHAPTER 13 IN THE 2004 FBC. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE SEE FBC CHAPTER 13, | | 13-415.1.ABC.1.1,.1.2,.1.3 | | PLEASE PROVIDE AN ACCEPTABLE METHOD, | | SCHEDULING , DEVICES AND TIME LIMITS ON | | DEVICES BEING USED. | | ALL REQUIRED OVER RIDE DEVICE LOCATIONS | | SHALL BE INDICATED ON PLANS. | | PLEASE SEE ALL SEPARATE SPACES. | | | | 3) NOTE: OK. | | | | 4) NOTE: OK. | | | | 5) NOTE: OK. | | | | 6) NOTE: OK. | | | | 7) NOTE: NO, PLEASE SEE CONTINUOUS LOADS | | ARE THAT OF WHICH ARE 3 OR MORE HRS AND | | SHOULD BE INDICATED AT 125%. | | | | ** PREVIOUS REVIEW NOTE ** | | PLEASE PROVIDE LOAD | | CALCULATIONS WHICH MEET NEC 220. | | 220.3,220.10,220.11,220.13 ETC | | AND ALL CONTINUOUS LOADS AT 125%. | | 215.5 | | | | 8) NOTE: OK. | | | | *** NEW NOTE ** | | | | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH | | RESPECT TO DESIGN PROFESSIONALS AND | | REPEAT COMMENTS. THIS IS ONLYNOTICE | | GIVEN AT THIS TIME. | | | | ** IMPORTANT** | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE | | PICKED UP FOR CORRECTIONS, PLEASE BE | | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED | | SHEETS AND ONLY INSERT NEW REVISED | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW | | AND STAMPING. DO NOT LEAVE ANY | | OLD/VOIDED SHEETS IN SETS. | | PLEASE KNOW ONLY ONE SET OF THE | | OLD/VOIDED SHEETS SHOULD BE SUBMITTED | | FOR REFERENCE. | | THIS WILL HELP IN THE REVIEW PROCESS AND | | AVOID ANY DELAYS. | | | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CONSTUCTION SERVICES DEPT. | | CITY OF WEST PALM BEACH | | 561-805-6717 | | [email protected] | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2006-06-12 |
|
|
Cont ID |
|
Sent By |
dpalmer |
Date |
2006-06-12 |
Time |
08:26 |
Rev Time |
0.00 |
Received By |
dpalmer |
Date |
2006-06-12 |
Time |
07:50 |
Sent To |
|
|
Notes |
2006-06-12 00:00:00 | ********** UNSAT ************* | | | | ** PLEASE SEE PLANS ARE ONLY SUBMITTED | | FOR "PLAN REVIEW" AND HAVE NOT BEEN | | SUBMITTED FOR PERMIT. | | | | 1) NOTE: PLEASE SEE PLANS SUBMITTED | | SEEEM TO HAVE GOTTEN WET AND THE | | SIGNATURE FOR THE ARCHITTECT ON BOTH | | SETS HAVE BE DISTORTED. | | FS481.221 | | | | 2) NOTE: PLEASE SEE FBC CHAPTER 13, | | 13-415.1.ABC.1.1,.1.2,.1.3 | | PLEASE PROVIDE AN ACCEPTABLE METHOD, | | SCHEDULING , DEVICES AND TIME LIMITS ON | | DEVICES BEING USED. | | ALL REQUIRED OVER RIDE DEVICE LOCATIONS | | SHALL BE INDICATED ON PLANS. | | PLEASE SEE ALL SEPARATE SPACES. | | | | 3) NOTE: PLEASE CLARIFY FEEDERS TO | | EXISTING PANEL. RISER SHOWS PARALLEL, | | CONDUITS FOR A 400A SERVICE? | | IS THE PANEL EXISTING 200A OR 400A? | | IS THE EXISTING FEEDER ONE OR TWO 2" | | CONDUITS? | | 215.5 | | | | 4) NOTE: PLEASE SEE PLANS ARE INDICATING | | DESIGN AND CODES UNDER THE 2001 FBC. | | PLEASE KNOW, OCT 1ST, 2005 , THE FBC WAS | | CHANGED TO THE 2004 FBC | | PLEASE ADJUST PLANS AND CODES REFLECTED. | | 215.5 | | | | 5) NOTE: PLEASE SEE MANY CIRCUITS ON | | PANEL SCHEDULE ARE SHOWN AS "EXISTING"?? | | HOW IS THIS POSSIBLE WHEN THIS IS A NEW | | BUILD OUT OF AN EXISTING SPACE?? | | PLEASE CORRLEATE PLANS. | | | | 6) NOTE: PLEASE SEE 408.4, PANEL | | SCHEDULE SHALL INDICATE ALL CIRCUITS | | SPECIFIC TO ROOMS AND AREAS. IE; BATH | | LTS, OFFICE LTS, OFFICE RECEPTS ETC. | | 215.5 | | | | 7) NOTE: PLEASE PROVIDE LOAD | | CALCULATIONS WHICH MEET NEC 220. | | 220.3,220.10,220.11,220.13 ETC | | AND ALL CONTINUOUS LOADS AT 125%. | | 215.5 | | | | 8) NOTE: PLEASE COMPLETE ALL CIRCUITS ON | | PLANS AND CORRELATE WITH THE PANEL | | SCHEDULE. | | PLEASE SEE 700.12E FOR CIRCUITING OF EM | | /EXT LTS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE TO CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | CONSTUCTION SERVICES DEPT. | | 561-805-6717 | | [email protected] |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
mawillia |
Date |
2006-11-14 |
Time |
09:59 |
Rev Time |
0.00 |
Received By |
mawillia |
Date |
2006-11-14 |
Time |
09:59 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-09-08 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-09-08 |
Time |
11:12 |
Sent To |
|
|
Notes |
2006-09-08 00:00:00 | ***DENIED*** | | | | 1) PLEASE SEE BUILDING REVIEW COMMENT | | REGARDING CONFLICTING INFORMATION REF: | | FIRE SPRINKLER SYSTEM. PLEASE CORRECT | | AND NOTE THAT IF SYSTEM IS PRESENT, | | SEPARATE SHOP DRAWINGS AND PERMIT WILL | | BE REQUIRED FOR REMODEL. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2006-06-15 |
|
|
Cont ID |
|
Sent By |
mwennerg |
Date |
2006-06-15 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
mwennerg |
Date |
2006-06-15 |
Time |
10:47 |
Sent To |
|
|
Notes |
2006-06-15 00:00:00 | FOR PLAN REVIEW ONLY | | | | ***DENIED*** | | | | 1) IN ADDITION TO APPLICABLE BUILDING | | CODES, LIFE SAFETY SHALL COMPLY WITH | | NFPA 101, 2003 EDITION. | | | | 2) AN EXIT SIGN IS SHOWN EXITING PERSONS | | THROUGH THE SHAMPOO/HAIR DRYING AREA. IT | | WOULD APPEAR THAT A BETTER LOCATION | | WOULD BE THE HALLWAY LEADING TO THE REAR | | EXIT. PLEASE SEE NFPA 101, SEC. 7.5.2.1. | | | | 3) PLEASE PROVIDE MAXIMUM TRAVEL | | DISTANCE INFORMATION TO LIFE SAFETY | | PLAN. | | | | 4) 2A 10B,C RATED FIRE EXTINGUISHER(S) | | REQUIRED MOUNTED AT DISTANCE NOT TO | | EXCEED 75' TRAVEL DISTANCE REQUIREMENT. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2006-10-24 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-10-24 |
Time |
11:21 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-10-24 |
Time |
11:21 |
Sent To |
|
|
Notes |
2006-10-26 11:26:40 | TO "COMM" BD#44 | 2006-10-24 11:21:57 | WAITING FOR "COMM" BD |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2006-08-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-08-15 |
Time |
11:13 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-08-15 |
Time |
11:13 |
Sent To |
|
|
Notes |
2006-09-05 00:00:00 | TO "BOB"#3 | 2006-08-15 00:00:00 | WAITING FOR "BOB"-PROJECT TO PERMIT- |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2006-08-15 |
|
|
Cont ID |
|
Sent By |
adarroug |
Date |
2006-06-15 |
Time |
11:12 |
Rev Time |
0.00 |
Received By |
adarroug |
Date |
2006-06-05 |
Time |
13:27 |
Sent To |
|
|
Notes |
2006-06-05 00:00:00 | TO "BOB"#5 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
N |
Date |
2006-06-06 |
|
|
Cont ID |
|
Sent By |
tgordon |
Date |
2006-06-06 |
Time |
09:46 |
Rev Time |
0.30 |
Received By |
tgordon |
Date |
2006-06-06 |
Time |
09:45 |
Sent To |
|
|
Notes |
2006-06-06 00:00:00 | MECHANICAL PLANS ON PAGE A-3 ARE NOT FOR | | REVIEW, MECHANICAL PLANS WILL BE | | SUBMITTED BY MECHANICAL CONTRACTOR, PER | | ROBERT CHANNELLE. |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2006-11-14 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-11-14 |
Time |
07:43 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-11-14 |
Time |
07:43 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2006-09-08 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-09-08 |
Time |
08:36 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-09-08 |
Time |
08:36 |
Sent To |
|
|
Notes |
2006-09-08 00:00:00 | DENIED; | | A BOTTLE WATER COOLER DOES NOT MEET THE | | REQUIREMENT OF THE FBC-2004 PLUMBING | | SECTION 410. DRINKING FOUNTAIN IS | | REQUIRED. PLEASE REVISE FLOOR PLAN AND | | SHOW D/F ON RISER DIAGRAM. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2006-06-13 |
|
|
Cont ID |
|
Sent By |
jleech |
Date |
2006-06-13 |
Time |
09:27 |
Rev Time |
0.00 |
Received By |
jleech |
Date |
2006-06-13 |
Time |
09:27 |
Sent To |
|
|
Notes |
2006-06-13 00:00:00 | DENIED; | | 1.SHEET A-1 CODE TO BE USED IS FBC-2004. | | 2.ADD NOTE TO GENERAL NOTES,"NO DEAD | | ENDS, SINK TO BE REMOVED SHALL BE | | DISCONNECTED AT THE BRANCH DRAIN". | | 3.DRINKING FOUNTAIN REQUIRED. SEE | | FBC-2004 PLUMBING TABLE 403.1. | | 4.THERMAL EXPANSION CONTROL IS REQUIRED | | PER. 607.3. | | 5.MAXIMUM DISTANCE OF A HOROZONTAL WASTE | | ARM, (3 SINKS ADDED) IS 6' SEE TABLE | | 906.1. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
P |
Date |
2006-06-15 |
|
|
Cont ID |
|
Sent By |
mmclean |
Date |
2006-06-15 |
Time |
09:57 |
Rev Time |
0.00 |
Received By |
mmclean |
Date |
2006-06-15 |
Time |
09:57 |
Sent To |
|
|
Notes |
2006-06-15 00:00:00 | CHANGE OF USE, NO NEED FOR PLANS TO BE | | STAMPED. APPROVED FOR THE TYPE OF USE AT | | LOCATION. |
|
|