Plan Review Details - Permit 06051268
Plan Review Stops For Permit 06051268
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2006-06-01 Cont ID  
Sent By lursu Date 2006-06-01 Time 14:44 Rev Time 0.00
Received By lursu Date 2006-06-01 Time 09:55 Sent To  
Notes
2006-06-01 00:00:00ADD EXT #0001 UNDER 5335 N MILITARY TRL
 FOR SUITE 40

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2006-11-14 Cont ID  
Sent By mjacobs Date 2006-11-14 Time 16:08 Rev Time 0.00
Received By mjacobs Date 2006-11-14 Time 15:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By mjacobs Date 2006-09-07 Time 16:45 Rev Time 0.00
Received By mjacobs Date 2006-09-07 Time 14:05 Sent To  
Notes
2006-09-07 00:00:00 
  
 1) SHEET A-3 HAS CONFLICTING
 INFORMATION.THE LIFE SAFETY SUMMARY
 INDICATES A SPRINKLER SYSTEM,HOWEVER,
 BELOW STATES A TYPE IV UNSPRINKLERED
 BUILDING. SO IS THERE A SPRINKLER SYSTEM
 IN THE BUILDING OR NOT?
  
 2) THE OCCUPANT LOAD STATED ON SHEET A-3
 IS INCORRECT. SEE TABLE 1004.1.2 FOR
 MORE INFORMATION AND MAKE THE
 ADJUSTMENTS ACCORDINGLY IN REFERENCE TO
 THE OCCUPANT LOAD.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By mjacobs Date 2006-06-15 Time 09:26 Rev Time 0.00
Received By mjacobs Date 2006-06-15 Time 09:16 Sent To  
Notes
2006-06-15 00:00:00 
 1) ALL PLANS SUBMITTED AFTER OCTOBER, 1,
 2004 SHALL BE DESIGNED TO THE 2004
 FLORIDA BUILDING CODE.
  
 2) (2004 FBC) 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE &
 EXTENT OF THE WORK PROPOSED & SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND REVELENT
 LAWS, ORDINANCES, AND RULES AND
 REGULATIONS AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 3) 110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD
 KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726
  

Review Stop E ELECTRICAL
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2006-12-14 Time 11:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2006-10-27 Cont ID  
Sent By dpalmer Date 2006-10-27 Time 19:38 Rev Time 0.00
Received By dpalmer Date 2006-10-27 Time 19:15 Sent To  
Notes
2006-10-27 19:39:24REDLINED,,,
  
  
 ALL EM./EXT LTS ARE REQUIRED TO BE WIRED AHEAD OF ANY
 LIGHTING CONTROLLED/SWITCHED CIRCUITS. 700.12E.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-09-07 Cont ID  
Sent By dpalmer Date 2006-09-07 Time 12:25 Rev Time 0.00
Received By dpalmer Date 2006-09-07 Time 10:29 Sent To  
Notes
2006-09-07 00:00:00** UNSAT 2ND REVIEW **
  
 ** PLANS ARE NOW SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW. PLEASE
 SEE NEW NOTE ADDED TO END OF NOTES.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: NO, PLEASE SEE PLANS DO NOT
 COMPLY AND INDICATE REQUIREMENTS FOR
 CHAPTER 13 IN THE 2004 FBC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE PROVIDE AN ACCEPTABLE METHOD,
 SCHEDULING , DEVICES AND TIME LIMITS ON
 DEVICES BEING USED.
 ALL REQUIRED OVER RIDE DEVICE LOCATIONS
 SHALL BE INDICATED ON PLANS.
 PLEASE SEE ALL SEPARATE SPACES.
  
 3) NOTE: OK.
  
 4) NOTE: OK.
  
 5) NOTE: OK.
  
 6) NOTE: OK.
  
 7) NOTE: NO, PLEASE SEE CONTINUOUS LOADS
 ARE THAT OF WHICH ARE 3 OR MORE HRS AND
 SHOULD BE INDICATED AT 125%.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE LOAD
 CALCULATIONS WHICH MEET NEC 220.
 220.3,220.10,220.11,220.13 ETC
 AND ALL CONTINUOUS LOADS AT 125%.
 215.5
  
 8) NOTE: OK.
  
 *** NEW NOTE **
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT COMMENTS. THIS IS ONLYNOTICE
 GIVEN AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 07:50 Sent To  
Notes
2006-06-12 00:00:00********** UNSAT *************
  
 ** PLEASE SEE PLANS ARE ONLY SUBMITTED
 FOR "PLAN REVIEW" AND HAVE NOT BEEN
 SUBMITTED FOR PERMIT.
  
 1) NOTE: PLEASE SEE PLANS SUBMITTED
 SEEEM TO HAVE GOTTEN WET AND THE
 SIGNATURE FOR THE ARCHITTECT ON BOTH
 SETS HAVE BE DISTORTED.
 FS481.221
  
 2) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1,.1.2,.1.3
 PLEASE PROVIDE AN ACCEPTABLE METHOD,
 SCHEDULING , DEVICES AND TIME LIMITS ON
 DEVICES BEING USED.
 ALL REQUIRED OVER RIDE DEVICE LOCATIONS
 SHALL BE INDICATED ON PLANS.
 PLEASE SEE ALL SEPARATE SPACES.
  
 3) NOTE: PLEASE CLARIFY FEEDERS TO
 EXISTING PANEL. RISER SHOWS PARALLEL,
 CONDUITS FOR A 400A SERVICE?
 IS THE PANEL EXISTING 200A OR 400A?
 IS THE EXISTING FEEDER ONE OR TWO 2"
 CONDUITS?
 215.5
  
 4) NOTE: PLEASE SEE PLANS ARE INDICATING
 DESIGN AND CODES UNDER THE 2001 FBC.
 PLEASE KNOW, OCT 1ST, 2005 , THE FBC WAS
 CHANGED TO THE 2004 FBC
 PLEASE ADJUST PLANS AND CODES REFLECTED.
 215.5
  
 5) NOTE: PLEASE SEE MANY CIRCUITS ON
 PANEL SCHEDULE ARE SHOWN AS "EXISTING"??
 HOW IS THIS POSSIBLE WHEN THIS IS A NEW
 BUILD OUT OF AN EXISTING SPACE??
 PLEASE CORRLEATE PLANS.
  
 6) NOTE: PLEASE SEE 408.4, PANEL
 SCHEDULE SHALL INDICATE ALL CIRCUITS
 SPECIFIC TO ROOMS AND AREAS. IE; BATH
 LTS, OFFICE LTS, OFFICE RECEPTS ETC.
 215.5
  
 7) NOTE: PLEASE PROVIDE LOAD
 CALCULATIONS WHICH MEET NEC 220.
 220.3,220.10,220.11,220.13 ETC
 AND ALL CONTINUOUS LOADS AT 125%.
 215.5
  
 8) NOTE: PLEASE COMPLETE ALL CIRCUITS ON
 PLANS AND CORRELATE WITH THE PANEL
 SCHEDULE.
 PLEASE SEE 700.12E FOR CIRCUITING OF EM
 /EXT LTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2006-11-14 Cont ID  
Sent By mawillia Date 2006-11-14 Time 09:59 Rev Time 0.00
Received By mawillia Date 2006-11-14 Time 09:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By mwennerg Date 2006-09-08 Time 11:12 Rev Time 0.00
Received By mwennerg Date 2006-09-08 Time 11:12 Sent To  
Notes
2006-09-08 00:00:00***DENIED***
  
 1) PLEASE SEE BUILDING REVIEW COMMENT
 REGARDING CONFLICTING INFORMATION REF:
 FIRE SPRINKLER SYSTEM. PLEASE CORRECT
 AND NOTE THAT IF SYSTEM IS PRESENT,
 SEPARATE SHOP DRAWINGS AND PERMIT WILL
 BE REQUIRED FOR REMODEL.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2006-06-15 Cont ID  
Sent By mwennerg Date 2006-06-15 Time 10:47 Rev Time 0.00
Received By mwennerg Date 2006-06-15 Time 10:47 Sent To  
Notes
2006-06-15 00:00:00FOR PLAN REVIEW ONLY
  
 ***DENIED***
  
 1) IN ADDITION TO APPLICABLE BUILDING
 CODES, LIFE SAFETY SHALL COMPLY WITH
 NFPA 101, 2003 EDITION.
  
 2) AN EXIT SIGN IS SHOWN EXITING PERSONS
 THROUGH THE SHAMPOO/HAIR DRYING AREA. IT
 WOULD APPEAR THAT A BETTER LOCATION
 WOULD BE THE HALLWAY LEADING TO THE REAR
 EXIT. PLEASE SEE NFPA 101, SEC. 7.5.2.1.
  
 3) PLEASE PROVIDE MAXIMUM TRAVEL
 DISTANCE INFORMATION TO LIFE SAFETY
 PLAN.
  
 4) 2A 10B,C RATED FIRE EXTINGUISHER(S)
 REQUIRED MOUNTED AT DISTANCE NOT TO
 EXCEED 75' TRAVEL DISTANCE REQUIREMENT.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2006-10-24 Cont ID  
Sent By adarroug Date 2006-10-24 Time 11:21 Rev Time 0.00
Received By adarroug Date 2006-10-24 Time 11:21 Sent To  
Notes
2006-10-26 11:26:40TO "COMM" BD#44
2006-10-24 11:21:57WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-08-15 Time 11:13 Rev Time 0.00
Received By adarroug Date 2006-08-15 Time 11:13 Sent To  
Notes
2006-09-05 00:00:00TO "BOB"#3
2006-08-15 00:00:00WAITING FOR "BOB"-PROJECT TO PERMIT-

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2006-08-15 Cont ID  
Sent By adarroug Date 2006-06-15 Time 11:12 Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 13:27 Sent To  
Notes
2006-06-05 00:00:00TO "BOB"#5

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2006-06-06 Cont ID  
Sent By tgordon Date 2006-06-06 Time 09:46 Rev Time 0.30
Received By tgordon Date 2006-06-06 Time 09:45 Sent To  
Notes
2006-06-06 00:00:00MECHANICAL PLANS ON PAGE A-3 ARE NOT FOR
 REVIEW, MECHANICAL PLANS WILL BE
 SUBMITTED BY MECHANICAL CONTRACTOR, PER
 ROBERT CHANNELLE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2006-11-14 Cont ID  
Sent By jleech Date 2006-11-14 Time 07:43 Rev Time 0.00
Received By jleech Date 2006-11-14 Time 07:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2006-09-08 Cont ID  
Sent By jleech Date 2006-09-08 Time 08:36 Rev Time 0.00
Received By jleech Date 2006-09-08 Time 08:36 Sent To  
Notes
2006-09-08 00:00:00DENIED;
 A BOTTLE WATER COOLER DOES NOT MEET THE
 REQUIREMENT OF THE FBC-2004 PLUMBING
 SECTION 410. DRINKING FOUNTAIN IS
 REQUIRED. PLEASE REVISE FLOOR PLAN AND
 SHOW D/F ON RISER DIAGRAM.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2006-06-13 Cont ID  
Sent By jleech Date 2006-06-13 Time 09:27 Rev Time 0.00
Received By jleech Date 2006-06-13 Time 09:27 Sent To  
Notes
2006-06-13 00:00:00DENIED;
 1.SHEET A-1 CODE TO BE USED IS FBC-2004.
 2.ADD NOTE TO GENERAL NOTES,"NO DEAD
 ENDS, SINK TO BE REMOVED SHALL BE
 DISCONNECTED AT THE BRANCH DRAIN".
 3.DRINKING FOUNTAIN REQUIRED. SEE
 FBC-2004 PLUMBING TABLE 403.1.
 4.THERMAL EXPANSION CONTROL IS REQUIRED
 PER. 607.3.
 5.MAXIMUM DISTANCE OF A HOROZONTAL WASTE
 ARM, (3 SINKS ADDED) IS 6' SEE TABLE
 906.1.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 1 Status P Date 2006-06-15 Cont ID  
Sent By mmclean Date 2006-06-15 Time 09:57 Rev Time 0.00
Received By mmclean Date 2006-06-15 Time 09:57 Sent To  
Notes
2006-06-15 00:00:00CHANGE OF USE, NO NEED FOR PLANS TO BE
 STAMPED. APPROVED FOR THE TYPE OF USE AT
 LOCATION.