Plan Review Details - Permit 06051263
Plan Review Stops For Permit 06051263
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2006-09-06 Cont ID  
Sent By amorse Date 2006-09-06 Time 12:06 Rev Time 0.00
Received By amorse Date 2006-09-06 Time 12:06 Sent To P
Notes
2006-09-06 00:00:00 
  
 DENIED
  
 PREVIOUS REVIEW NOTES NOT ADDRESSED:
  
 1) SCOPE OF WORK HARD TO DISCERN. IS NEW
 LAUNDRY AREA ONLY ACCESSABLE FROM
 OUTSIDE? DOES NEW INTERIOR FRAMED WALLS
 HAVE A WINDOW IN THEM? IS EXISTING DOOR
 OPENING A DOUBLE DOOR? A DRAWING WITH
 MORE CLARITY IS REQUIRED TO ACCOMPLISH
 REQUIRED PLAN REVIEW
  
 PLEASE COORDINATE DRAWINGS, WHAT
 RELATIONSHIP DO THE 2 DRAWINGS HAVE WITH
 EACH OTHER? ONE HAS EXISTING WALL AS
 7'-6" WITH A 24"X50" WINDOW OPENING THE
 OTHER IS 12'-0" WITH A DOUBLE 3'-0" SET
 OF DOORS AND A 60"X50" WINDOW. PLAN VIEW
 DOES NOT SHOW ANY WALLS THAT ARE 12'-0"
  
 2) DETAIL SHOWS DOOR AND WINDOW TOGETHER
 IS POST BETWEEN STRUCTURAL? WHAT IS IT'S
 MAKE UP (DOUBLE 2X ?)AND HOW IS IT
 ATTACHED TO THE BEAM AND FLOOR SYSTEM
  
 DRAWINGS ARE REQUIRED TO BE CORRECTED
 THE NOTATIONS ON REVIEW REPORT IS NOT A
 CORRECTION
  
 4)A DETAIL IS REQUIRED ON PATCH FOR
 EXISTING WINDOW OPENING TO BE FILLED
  
 DRAWINGS ARE REQUIRED TO BE CORRECTED
 THE NOTATIONS ON REVIEW REPORT IS NOT A
 CORRECTION
  
 5) IS INTERIOR POST STRUCTURAL? IF SO
 WHAT FRAMING WILL REPLACE IT?
  
 DRAWINGS ARE REQUIRED TO BE CORRECTED
 THE NOTATIONS ON REVIEW REPORT IS NOT A
 CORRECTION. ENGINEER OF RECORD SHOULD BE
 AWARE OF ALL CHANGES TO DETAILS
  
 PLEASE NOTE THAT ENGINEERING SHALL MEET
 ALL THE REQUIREMENTS OF THE FLORIDA
 STATUTES:
  
 AN ENGINEER PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS SHALL
 INDICATE THEIR NAME AND LICENCE #, AS
 WELL AS THE NAME,ADDRESS AND CERTIFICATE
 OF AUTHORIZATION #ON EACH SHEET PER
 61G15-23.002 (2) FAC
  
 ENGINEERS SEAL,SIGNATURE AND DATE ARE ON
 THE BLANK SHEET(BACK OF DRAWING)
 SUCH SIGNATURE, DATE, AND SEAL SHALL BE
 EVIDENCE OF THE AUTHENTICITY OF THAT TO
 WHICH THEY ARE AFFIXED FS 471.O25(1)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2006-07-03 Cont ID  
Sent By amorse Date 2006-07-03 Time 12:12 Rev Time 0.00
Received By amorse Date 2006-07-03 Time 12:12 Sent To PC
Notes
2006-07-03 00:00:00 
 DENIED
  
 1) SCOPE OF WORK HARD TO DISCERN. IS NEW
 LAUNDRY AREA ONLY ACCESSABLE FROM
 OUTSIDE? DOES NEW INTERIOR FRAMED WALLS
 HAVE A WINDOW IN THEM? IS EXISTING DOOR
 OPENING A DOUBLE DOOR? A DRAWING WITH
 MORE CLARITY IS REQUIRED TO ACCOMPLISH
 REQUIRED PLAN REVIEW
  
 2) DETAIL SHOWS DOOR AND WINDOW TOGETHER
 IS POST BETWEEN STRUCTURAL? WHAT IS IT'S
 MAKE UP (DOUBLE 2X ?)AND HOW IS IT
 ATTACHED TO THE BEAM AND FLOOR SYSTEM
  
 3) PRODUCT APPROVALS ARE REQUIRED FOR
 DOORS AND WINDOWS PER 9B-72 FAC
  
 4)A DETAIL IS REQUIRED ON PATCH FOR
 EXISTING WINDOW OPENING TO BE FILLED
  
 5) IS INTERIOR POST STRUCTURAL? IF SO
 WHAT FRAMING WILL REPLACE IT?
  
 6) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2006-08-11 Cont ID  
Sent By dpalmer Date 2006-08-11 Time 19:56 Rev Time 0.00
Received By dpalmer Date 2006-08-11 Time 19:43 Sent To P
Notes
2006-08-11 00:00:00*** UNSAT 2ND REVIEW ****
  
 ** PLEASE SEE COMMENTS BELOW WHICH STILL
 NEED TO BE ADDRESSED.
 NOTES AR TAKEN DIRECTLY FROM THE
 PREVIOUS REVIEW.
  
 1) NOTE:NO, PLEASE SEE PLANS/DRAWINGS
 SUBMITTED ARE NOT ACCEPTABLE FOR MIN
 REQUIRED PLANS/DRAWING WHICH SHALL BE
 DONE IN "DRAFTMAN QUALITY".
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBCADMINISTRATIVE
 SECTION 106.1.3 WHICH REQUIRES PLANS TO
 BE SUBMITTED WITH MIN 1/8" SCALE AND
 CLARITY. ETC.
 PLEASE SEE ONE OF THE SHEETS SUBMITTED
 ARE SIGNED, DATED AND SEALED ON THE BACK
 OF THE SHEET WHICH IS BLANK.???
 PLEASE SEE FS 471.025
  
 2) NOTE;?? RESPONSE ON CITY'S COMMENTS
 MENTIONS RELOCATE, HOWEVER PLANS
 MENTIONS TO ADDED NEW WASHER AND DRYER.
 PLEASE SEE CONDUCTOR SIZES ARE NOT
 MENTIONED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE WASHER AND DRYER
 SEEM TO BE MOVED TO SOME SORT OF NEW
 ROOM, HOWEVER IS UNCLEAR.
 PLEASE VERIFY IF THESE ARE JUST EXISITNG
 RELOCATED OR NEW? IF NEW PLEASE PROVIDE
 LOAD CALCULATIONS FOR ADDED LOADS TO THE
 THE EXISTING SERVICE AND INDICATE SIZE
 OF EXISTING SERVICE/PANEL.
 215.5,220
  
 3) NOTE:NO?? WHERE IS LT REQUIRED?
 NEW? EXISTING?
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE IF THIS IS A NEW
 ROOM, A LIGHTING OUTLET AND CONTROL
 SHALL BE REQUIRED.
 210.70
  
 4) NOTE: OK, HOWEVER PLEASE BE SURE
 APPLICATION IS NOTARIZED BEFORE
 RESUBMITTING.
  
 ** PREIVOUS REVIEW NOTE
 PLEASE SEE PERMIT APPLICATION
 WAS NOT SIGNED BY THE CONTRACTOR.
 PLEASE DO SO.
  
 ** NEW NOTE **
  
 5) NOTE: PLEASE SEE FS 553.80 (2)(B)
 WITH RESPECTTO DESIGN PROFESSIONALS
 AND REPEAT COMMENTS.
  
  
 ** PLEASE KNOW, ONE SET OF THE SUBMITTED
 SHEETS ARE BEING RETAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2006-06-12 Cont ID  
Sent By dpalmer Date 2006-06-12 Time 17:23 Rev Time 0.00
Received By dpalmer Date 2006-06-12 Time 16:54 Sent To P
Notes
2006-06-12 00:00:00**** UNSAT ****
  
 1) NOTE: PLEASE SEE FBCADMINISTRATIVE
 SECTION 106.1.3 WHICH REQUIRES PLANS TO
 BE SUBMITTED WITH MIN 1/8" SCALE AND
 CLARITY. ETC.
 PLEASE SEE ONE OF THE SHEETS SUBMITTED
 ARE SIGNED, DATED AND SEALED ON THE BACK
 OF THE SHEET WHICH IS BLANK.???
 PLEASE SEE FS 471.025
  
 2) NOTE; PLEASE SEE WASHER AND DRYER
 SEEM TO BE MOVED TO SOME SORT OF NEW
 ROOM, HOWEVER IS UNCLEAR.
 PLEASE VERIFY IF THESE ARE JUST EXISITNG
 RELOCATED OR NEW? IF NEW PLEASE PROVIDE
 LOAD CALCULATIONS FOR ADDED LOADS TO THE
 THE EXISTING SERVICE AND INDICATE SIZE
 OF EXISTING SERVICE/PANEL.
 215.5,220
  
 3) NOTE: PLEASE SEE IF THIS IS A NEW
 ROOM, A LIGHTING OUTLET AND CONTROL
 SHALL BE REQUIRED.
 210.70
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION
 WAS NOT SIGNED BY THE CONTRACTOR.
 PLEASE DO SO.
  
  
 ** PLEASE KNOW, ONE SET OF THE SUBMITTED
 SHEETS ARE BEING RETAINED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2006-08-10 Cont ID  
Sent By adarroug Date 2006-08-10 Time 11:41 Rev Time 0.00
Received By adarroug Date 2006-08-10 Time 11:41 Sent To E
Notes
2006-08-10 00:00:00TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2006-07-03 Time   Rev Time 0.00
Received By adarroug Date 2006-06-05 Time 13:18 Sent To  
Notes
2006-06-05 00:00:00TO "E" BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2006-09-06 Cont ID  
Sent By jleech Date 2006-09-06 Time 09:51 Rev Time 0.00
Received By jleech Date 2006-09-06 Time 09:51 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2006-06-19 Time   Rev Time 0.00
Received By jleech Date 2006-06-19 Time 08:02 Sent To  
Notes
2006-06-19 00:00:00DENIED;
 1.SEE ELECTRICAL PLAN REVIEW NOTES.
 2.W/M BRANCH DRAIN SHALL BE 3" SEE
 SEC.406.3, AND A CLEANOUT IS REQUIRED
 ABOVE THE FIXTURE DRAIN.
 3.A REMOVABLE VENTED GRILL IS REQUIRED
 FOR THE STUDER VENT PLEASE INDICATE ONE
 PLANS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695